... ... @@ -42,27 +42,125 @@
42 42  
43 43  == 1.7 RS485 Commands ==
44 44  
45 +=== 1.7.1 Query data ===
45 45  
47 +The address of the EC K10 sensor is 11
48 +
49 +The query data command is 11 03 00 00 00 02 C6 9B
50 +
51 +For example, the returned data is 11 03 04 (% style="color:red" %)**02 AE**(%%) 01 64 8B D0. 02 AE is converted to decimal 686,  K=10, EC: 6860uS/cm
52 +
53 +
54 +The address of the EC K1 sensor is 12
55 +
56 +The query data command is 12 03 00 00 00 02 C6 A8
57 +
58 +For example, the returned data is 12 03 04 (% style="color:red" %)**02 AE**(%%) 01 64 B8 D0. 02 AE is converted to decimal 686,  K=1, EC: 686uS/cm.
59 +
60 +
61 +=== 1.7.2 Calibration Method ===
62 +
63 +
64 +This device uses one-point calibration, and you need to prepare a known E standard solution. When mileage K=1, 1~~2000 uses 1413uS/cm standard solution, and when mileage K=10, 10~~20000 uses 12.88mS/cm standard solution. The calibration steps are as follows:
65 +(1) Place the electrode in distilled water and clean it. When mileage 1~~2000 uses 1413HS/cm standard solution, enter the following calibration command after the data is stable.
66 +
67 +(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:676.25px" %)
68 +|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Function code|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address high|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Quantity high|=(% style="width: 1px; background-color: rgb(79, 129, 189); color: white;" %)Quantity low|=(% style="width: 139.083px; background-color: rgb(79, 129, 189); color: white;" %)Data length|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Data|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 high
69 +|(% style="width:99px" %)0X12|(% style="width:112px" %)0X10|(% style="width:135px" %)0X00|(% style="width:126px" %)0X26|(% style="width:85px" %)0X00|(% style="width:1px" %)0X02|(% style="width:1px" %)0X04|(% style="width:1px" %)(((
70 +0X00
71 +
72 +0X00
73 +
74 +0X37
75 +
76 +0X32
77 +)))|(% style="width:1px" %)0XBD|(% style="width:1px" %)0XFC
78 +
79 +return
80 +
81 +(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:676.25px" %)
82 +|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Function code|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address high|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Quantity high|=(% style="width: 1px; background-color: rgb(79, 129, 189); color: white;" %)Quantity low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 high
83 +|(% style="width:99px" %)0X12|(% style="width:112px" %)0X10|(% style="width:135px" %)0X00|(% style="width:126px" %)0X26|(% style="width:85px" %)0X00|(% style="width:1px" %)0X02|(% style="width:1px" %)0XA2|(% style="width:1px" %)0XA0
84 +
85 +
86 +(2) Place the electrode in distilled water to clean it. Use 12.88mS/cm standard solution for the range of 10~~20000. After the data is stable, enter the following calibration command
87 +
88 +(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:676.25px" %)
89 +|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Function code|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address high|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Quantity high|=(% style="width: 1px; background-color: rgb(79, 129, 189); color: white;" %)Quantity low|=(% style="width: 139.083px; background-color: rgb(79, 129, 189); color: white;" %)Data length|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Data|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 high
90 +|(% style="width:99px" %)0X11|(% style="width:112px" %)0X10|(% style="width:135px" %)0X00|(% style="width:126px" %)0X26|(% style="width:85px" %)0X00|(% style="width:1px" %)0X02|(% style="width:1px" %)0X04|(% style="width:1px" %)(((
91 +0X00
92 +
93 +0X01
94 +
95 +0XF7
96 +
97 +0X20
98 +)))|(% style="width:1px" %)0X33|(% style="width:1px" %)0X75
99 +
100 +Return
101 +
102 +(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:676.25px" %)
103 +|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Function code|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address high|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Address low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)Quantity high|=(% style="width: 1px; background-color: rgb(79, 129, 189); color: white;" %)Quantity low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 low|=(% style="width: 50px;background-color:#4F81BD;color:white" %)CRC16 high
104 +|(% style="width:99px" %)0X11|(% style="width:112px" %)0X06|(% style="width:135px" %)0X00|(% style="width:126px" %)0X26|(% style="width:85px" %)0X00|(% style="width:1px" %)0X02|(% style="width:1px" %)0XEB|(% style="width:1px" %)0X50
105 +
106 +
107 +
108 +
109 +
110 +
46 46  = 2. DR-PH01 Water PH Sensor =
47 47  
48 48  == 2.7 RS485 Commands ==
49 49  
50 50  
116 +The address of the pH  sensor is 10
51 51  
118 +The query data command is 10 03 00 00 00 01 87 4B. After the query, 7 bytes will be returned.
119 +
120 +For example, the returned data is 10 03 02 (% style="color:red" %)**02 AE**(%%) C4 9B.
121 +
122 +02 AE is the pH value, which is converted into decimal to get 686, and then two decimal places are added to get the actual value. 02 AE means the current pH value is 6.86.
123 +
124 +
52 52  = 3. DR-ORP1 Water ORP Sensor =
53 53  
54 54  == 3.7 RS485 Commands ==
55 55  
56 56  
130 +The address of the ORP sensor is 13
57 57  
132 +The query data command is 13 03 00 00 00 01 87 78
133 +
134 +For example, the returned data is 13 03 02 (% style="color:red" %)**02 AE**(%%) 80 9B.
135 +
136 +02 AE is the ORP value, converted to decimal, the actual value is 686, 02 AE means the current ORP value is 686mV
137 +
138 +
58 58  = 4. DR-DO1 Dissolved Oxygen Sensor =
59 59  
60 60  == 4.7 RS485 Commands ==
61 61  
62 62  
144 +The address of the dissolved oxygen sensor is 14
63 63  
146 +The query data command is 14 03 00 14 00 01 C6 CB
147 +
148 +After the query, 7 bytes will be returned. For example, the returned data is 14 03 02 (% style="color:red" %)**03 78**(%%) B5 55. 03 78 is the value of dissolved oxygen.
149 +
150 +Converted to decimal, it is 888. Add two decimal places to get the actual value. 03 78 means the current dissolved oxygen is 8.88mg/L
151 +
152 +
64 64  = 5. DR-TS1 Water Turbidity Sensor =
65 65  
66 66  == 5.7 RS485 Commands ==
67 67  
157 +
158 +The address of the dissolved oxygen sensor is 15
159 +
160 +The query data command is 15 03 00 00 00 01 87 1E
161 +
162 +For example, the returned data is 15 03 02 (% style="color:red" %)**02 9A**(%%) 09 4C
163 +
164 +02 9A is the turbidity value, converted to decimal, it is 666, and then divided by 10, the actual value is 66.6, 02 9A means the current turbidity value is 66.6 NTU
165 +
68 68