... ... @@ -948,11 +948,10 @@
948 948  02 9A is the turbidity value, converted to decimal, it is 666, and then divided by 10, the actual value is 66.6, 02 9A means the current turbidity value is 66.6 NTU
949 949  
950 950  
951 -= 6. DR-ECK Water EC Probe =
951 += 6. DR-CL Water CL Probe =
952 952  
953 953  == 6.1 Specification: ==
954 954  
955 -
956 956  * **Power Input**: DC7~~30
957 957  
958 958  * **Power Consumption** : 0.19W
... ... @@ -960,20 +960,41 @@
960 960  * **Interface**: RS485. 9600 Baud Rate
961 961  
962 962  * **CL Range & Resolution:**
963 -** **CL2ML/CL10ML** : 0.01mg/L
964 964  ** **CL2ML:**0-2mg/L
965 965  ** **CL10ML:**0-10mg/L
964 +** **Resolution:**0.01mg/L
966 966  
967 -* **EC Accuracy**: ±1% FS
966 +* **CL Accuracy**: ±5% FS
968 968  * **Temperature Accuracy: **±0.5 °C
969 969  * **Working environment:**
970 -** Ambient Temperature: 0–60°C
971 -** Relative Humidity: <85% RH(Specifically refers to the cable male and female)
972 -** ECK200.0 Continuous monitoring of cross-section water quality, aquaculture, sewage treatment, environmental protection, pharmaceuticals, food, tap water, seawater and other high conductivity environments
969 +** Ambient Temperature: 0–50°C
970 +** pH:4-9
971 +** Flow rate: 30L/h~~60L/h (flow tank installation)
973 973  * **IP Rated**: IP68
974 974  
975 975  * **Max Pressure**: 0.6MPa
976 976  
976 +== 6.2 Wiring ==
977 977  
978 +[[image:image-20240720172548-2.png||height="348" width="571"]]
978 978  
980 +== 6.3 Mechinical Drawing ==
981 +
982 +[[image:1752573238705-910.png||height="694" width="278"]]
983 +
984 +== 6.4 Installation ==
985 +
986 +Flow-through installation: Use the matching flow slot for installation. The device and the flow slot are installed tightly.
987 +
988 +The measuring end is completely immersed in the measured liquid to ensure a steady flow rate without bubbles.
989 +
990 +It is recommended that the flow rate be controlled at 30-60Lh to ensure the accuracy of the test.
991 +
992 +[[image:1752573643879-991.png||height="360" width="343"]]
993 +
994 +
995 +
996 +
997 += 7.  Water Quality Sensor Datasheet =
998 +
979 979  * **[[Water Quality Sensor Transmitter Datasheet>>https://www.dropbox.com/scl/fi/9tofocmgapkbddshznumn/Datasheet_WQS-xB-WQS-xS_Water-Quality-Sensor-Transmitter.pdf?rlkey=wxua12ur9swk30rkqnh2boo9z&st=axga6epf&dl=0]]**
image-20240720172548-2.png
Size
... ... @@ -1,1 +1,1 @@
1 -1.5 MB
1 +262.2 KB
Content
1752573238705-910.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +111.3 KB
Content
1752573643879-991.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +163.2 KB
Content