From version < 46.1 >
edited by Xiaoling
on 2024/08/06 18:14
To version < 52.1 >
edited by Karry Zhuang
on 2024/11/29 14:23
>
Change comment: Uploaded new attachment "image-20241129142314-1.png", version {1}

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Xiaoling
1 +XWiki.karry
Content
... ... @@ -19,8 +19,8 @@
19 19  * **EC Range & Resolution:**
20 20  ** **ECK0.01** : 0.02 ~~ 20 μS/cm
21 21  ** **ECK0.1**: 0.2 ~~ 200.0 μS/cm
22 -** **ECK1.0** : 2 ~~ 2,000 μS/cm  Resolution: 1 μS/cm
23 -** **ECK10.0** : 20 ~~ 20,000 μS/cm  Resolution: 10 μS/cm
22 +** **ECK1.0** : 0 ~~ 2,000 μS/cm  Resolution: 1 μS/cm
23 +** **ECK10.0** : 10 ~~ 20,000 μS/cm  Resolution: 10 μS/cm
24 24  
25 25  * **EC Accuracy**: ±1% FS
26 26  
... ... @@ -671,12 +671,10 @@
671 671  == 4.3 Impedance requirements for current signals ==
672 672  
673 673  
674 -(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:420px" %)
675 -|=(% style="width: 140px" %)Supply Voltage|=(% style="width: 70px;" %)9V|=(% style="width: 70px;" %)**12V**|=(% style="width: 70px;" %)**20V**|=(% style="width: 70px;" %)**24V**
676 -|(% style="width:137px" %)**Max Impedance**|(% style="width:70px" %)**<250Ω**|(% style="width:68px" %)**<400Ω**|(% style="width:68px" %)**<500Ω**|(% style="width:70px" %)**<900Ω**
674 +(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:400px" %)
675 +|(% style="width:132px" %)**Supply Voltage**|(% style="width:67px" %)**9V**|(% style="width:67px" %)**12V**|(% style="width:67px" %)**20V**|(% style="width:67px" %)**24V**
676 +|(% style="width:132px" %)**Max Impedance**|(% style="width:65px" %)**<250Ω**|(% style="width:67px" %)**<400Ω**|(% style="width:67px" %)**<500Ω**|(% style="width:65px" %)**<900Ω**
677 677  
678 -
679 -
680 680  == 4.4 Mechinical Drawing ==
681 681  
682 682  
... ... @@ -775,7 +775,7 @@
775 775  == 5.1 Specification ==
776 776  
777 777  
778 -* **Measuring range**: 0.11000.0NTU
776 +* **Measuring range**: 0.1~~1000.0NTU
779 779  
780 780  * **Accuracy**: ±5%
781 781  
... ... @@ -800,9 +800,9 @@
800 800  == 5.3 Impedance requirements for current signals ==
801 801  
802 802  
803 -(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:420px" %)
804 -|=(% style="width: 140px" %)Supply Voltage|=(% style="width: 70px;" %)9V|=(% style="width: 70px;" %)**12V**|=(% style="width: 70px;" %)**20V**|=(% style="width: 70px;" %)**24V**
805 -|(% style="width:137px" %)**Max Impedance**|(% style="width:70px" %)**<250Ω**|(% style="width:68px" %)**<400Ω**|(% style="width:68px" %)**<500Ω**|(% style="width:70px" %)**<900Ω**
801 +(% border="1" cellspacing="3" style="background-color:#f2f2f2; width:400px" %)
802 +|(% style="width:132px" %)**Supply Voltage**|(% style="width:67px" %)**9V**|(% style="width:67px" %)**12V**|(% style="width:67px" %)**20V**|(% style="width:67px" %)**24V**
803 +|(% style="width:132px" %)**Max Impedance**|(% style="width:65px" %)**<250Ω**|(% style="width:67px" %)**<400Ω**|(% style="width:67px" %)**<500Ω**|(% style="width:65px" %)**<900Ω**
806 806  
807 807  == 5.4 Mechinical Drawing ==
808 808  
... ... @@ -876,3 +876,11 @@
876 876  For example, the returned data is 15 03 02 (% style="color:red" %)**02 9A**(%%) 09 4C
877 877  
878 878  02 9A is the turbidity value, converted to decimal, it is 666, and then divided by 10, the actual value is 66.6, 02 9A means the current turbidity value is 66.6 NTU
877 +
878 +
879 += 6.  Water Quality Sensor Datasheet =
880 +
881 +
882 +* **[[Water Quality Sensor Transmitter Datasheet>>https://www.dropbox.com/scl/fi/9tofocmgapkbddshznumn/Datasheet_WQS-xB-WQS-xS_Water-Quality-Sensor-Transmitter.pdf?rlkey=wxua12ur9swk30rkqnh2boo9z&st=axga6epf&dl=0]]**
883 +
884 +
image-20241129142314-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +1.2 MB
Content
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0