19
20
21 = 1.Introduction =
22
23 == 1.1 What is RS485-LN RS485 to LoRaWAN Converter ==
24
25 (((
26 (((
27 The Dragino RS485-LN is a (% style="color:blue" %)**RS485 to LoRaWAN Converter**(%%). It converts the RS485 signal into LoRaWAN wireless signal which simplify the IoT installation and reduce the installation/maintaining cost.
28 )))
29
30 (((
31 RS485-LN allows user to (% style="color:blue" %)**monitor / control RS485 devices**(%%) and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, smartphone detection, building automation, and so on.
32 )))
33
34 (((
35 (% style="color:blue" %)**For data uplink**(%%), RS485-LN sends user-defined commands to RS485 devices and gets the return from the RS485 devices. RS485-LN will process these returns according to user-define rules to get the final payload and upload to LoRaWAN server.
36 )))
37
38 (((
39 (% style="color:blue" %)**For data downlink**(%%), RS485-LN runs in LoRaWAN Class C. When there downlink commands from LoRaWAN server, RS485-LN will forward the commands from LoRaWAN server to RS485 devices.
40
41 (% style="color:blue" %)**Demo Dashboard for RS485-LN**(%%) connect to two energy meters: [[https:~~/~~/app.datacake.de/dashboard/d/58844a26-378d-4c5a-aaf5-b5b5b153447a>>url:https://app.datacake.de/dashboard/d/58844a26-378d-4c5a-aaf5-b5b5b153447a]]
42 )))
43 )))
44
45 [[image:1653267211009-519.png||height="419" width="724"]]
46
47
48 == 1.2 Specifications ==
49
50
51 **Hardware System:**
52
53 * STM32L072CZT6 MCU
54 * SX1276/78 Wireless Chip 
55 * Power Consumption (exclude RS485 device):
56 ** Idle: 32mA@12v
57 ** 20dB Transmit: 65mA@12v
58
59 **Interface for Model:**
60
61 * RS485
62 * Power Input 7~~ 24V DC. 
63
64 **LoRa Spec:**
65
66 * Frequency Range:
67 ** Band 1 (HF): 862 ~~ 1020 Mhz
68 ** Band 2 (LF): 410 ~~ 528 Mhz
69 * 168 dB maximum link budget.
70 * +20 dBm - 100 mW constant RF output vs.
71 * +14 dBm high efficiency PA.
72 * Programmable bit rate up to 300 kbps.
73 * High sensitivity: down to -148 dBm.
74 * Bullet-proof front end: IIP3 = -12.5 dBm.
75 * Excellent blocking immunity.
76 * Low RX current of 10.3 mA, 200 nA register retention.
77 * Fully integrated synthesizer with a resolution of 61 Hz.
78 * FSK, GFSK, MSK, GMSK, LoRaTM and OOK modulation.
79 * Built-in bit synchronizer for clock recovery.
80 * Preamble detection.
81 * 127 dB Dynamic Range RSSI.
82 * Automatic RF Sense and CAD with ultra-fast AFC.
83 * Packet engine up to 256 bytes with CRC
84
85
86 == 1.3 Features ==
87
88 * LoRaWAN Class A & Class C protocol (default Class C)
89 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915/IN865/RU864
90 * AT Commands to change parameters
91 * Remote configure parameters via LoRa Downlink
92 * Firmware upgradable via program port
93 * Support multiply RS485 devices by flexible rules
94 * Support Modbus protocol
95 * Support Interrupt uplink (Since hardware version v1.2)
96
97
98 == 1.4 Applications ==
99
100 * Smart Buildings & Home Automation
101 * Logistics and Supply Chain Management
102 * Smart Metering
103 * Smart Agriculture
104 * Smart Cities
105 * Smart Factory
106
107
108 == 1.5 Firmware Change log ==
109
110 [[RS485-LN Image files – Download link and Change log>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/]]
111
112
113 == 1.6 Hardware Change log ==
114
115 (((
116 (((
117 v1.2: Add External Interrupt Pin.
118
119 v1.0: Release
120
121
122 )))
123 )))
124
125 = 2. Power ON Device =
126
127 (((
128 The RS485-LN can be powered by 7 ~~ 24V DC power source. Connection as below
129
130 * Power Source VIN to RS485-LN VIN+
131 * Power Source GND to RS485-LN VIN-
132
133 (((
134 Once there is power, the RS485-LN will be on.
135 )))
136
137 [[image:1653268091319-405.png]]
138
139
140 )))
141
142 = 3. Operation Mode =
143
144 == 3.1 How it works? ==
145
146 (((
147 The RS485-LN is configured as LoRaWAN OTAA Class C mode by default. It has OTAA keys to join network. To connect a local LoRaWAN network, user just need to input the OTAA keys in the network server and power on the RS485-LN. It will auto join the network via OTAA.
148
149
150 )))
151
152 == 3.2 Example to join LoRaWAN network ==
153
154 Here shows an example for how to join the TTN V3 Network. Below is the network structure, we use [[LG308>>url:http://www.dragino.com/products/lora-lorawan-gateway/item/140-lg308.html]] as LoRaWAN gateway here. 
155
156 [[image:1653268155545-638.png||height="334" width="724"]]
157
158
159 (((
160 (((
161 The RS485-LN in this example connected to two RS485 devices for demonstration, user can connect to other RS485 devices via the same method. The connection is as below:
162 )))
163
164 (((
165 485A+ and 485B- of the sensor are connected to RS485A and RA485B of RS485-LN respectively.
166 )))
167
168 [[image:1653268227651-549.png||height="592" width="720"]]
169
170 (((
171 The LG308 is already set to connect to [[TTN V3 network >>path:https://www.thethingsnetwork.org/]]. So what we need to now is only configure the TTN V3:
172 )))
173
174 (((
175 **Step 1**: Create a device in TTN V3 with the OTAA keys from RS485-LN.
176 )))
177
178 (((
179 Each RS485-LN is shipped with a sticker with unique device EUI:
180 )))
181 )))
182
183 [[image:1652953462722-299.png]]
184
185 (((
186 (((
187 User can enter this key in their LoRaWAN Server portal. Below is TTN V3 screen shot:
188 )))
189
190 (((
191 Add APP EUI in the application.
192 )))
193 )))
194
195 [[image:image-20220519174512-1.png]]
196
197 [[image:image-20220519174512-2.png||height="323" width="720"]]
198
199 [[image:image-20220519174512-3.png||height="556" width="724"]]
200
201 [[image:image-20220519174512-4.png]]
202
203 You can also choose to create the device manually.
204
205 [[image:1652953542269-423.png||height="710" width="723"]]
206
207 Add APP KEY and DEV EUI
208
209 [[image:1652953553383-907.png||height="514" width="724"]]
210
211
212 (((
213 **Step 2**: Power on RS485-LN and it will auto join to the TTN V3 network. After join success, it will start to upload message to TTN V3 and user can see in the panel.
214 )))
215
216 [[image:1652953568895-172.png||height="232" width="724"]]
217
218
219 == 3.3 Configure Commands to read data ==
220
221 (((
222 (((
223 There are plenty of RS485 devices in the market and each device has different command to read the valid data. To support these devices in flexible, RS485-LN supports flexible command set. User can use [[AT Commands>>||anchor="H3.5ConfigureRS485-BLviaATorDownlink"]] or LoRaWAN Downlink Command to configure what commands RS485-LN should send for each sampling and how to handle the return from RS485 devices.
224 )))
225
226 (((
227 (% style="color:red" %)Note: below description and commands are for firmware version >v1.1, if you have firmware version v1.0. Please check the [[user manual v1.0>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/&file=RS485-LN_UserManual_v1.0.1.pdf]] or upgrade the firmware to v1.1
228
229
230 )))
231 )))
232
233 === 3.3.1 onfigure UART settings for RS485 or TTL communication ===
234
235 To use RS485-LN to read data from RS485 sensors, connect the RS485-LN A/B traces to the sensors. And user need to make sure RS485-LN use the match UART setting to access the sensors. The related commands for UART settings are:
236
237 (% border="1" style="background-color:#ffffcc; color:green; width:782px" %)
238 |(% style="width:128px" %)(((
239 **AT Commands**
240 )))|(% style="width:305px" %)(((
241 **Description**
242 )))|(% style="width:346px" %)(((
243 **Example**
244 )))
245 |(% style="width:128px" %)(((
246 AT+BAUDR
247 )))|(% style="width:305px" %)(((
248 Set the baud rate (for RS485 connection). Default Value is: 9600.
249 )))|(% style="width:346px" %)(((
250 (((
251 AT+BAUDR=9600
252 )))
253
254 (((
255 Options: (1200,2400,4800,14400,19200,115200)
256 )))
257 )))
258 |(% style="width:128px" %)(((
259 AT+PARITY
260 )))|(% style="width:305px" %)(((
261 Set UART parity (for RS485 connection)
262 )))|(% style="width:346px" %)(((
263 (((
264 AT+PARITY=0
265 )))
266
267 (((
268 Option: 0: no parity, 1: odd parity, 2: even parity
269 )))
270 )))
271 |(% style="width:128px" %)(((
272 AT+STOPBIT
273 )))|(% style="width:305px" %)(((
274 (((
275 Set serial stopbit (for RS485 connection)
276 )))
277
278 (((
279
280 )))
281 )))|(% style="width:346px" %)(((
282 (((
283 AT+STOPBIT=0 for 1bit
284 )))
285
286 (((
287 AT+STOPBIT=1 for 1.5 bit
288 )))
289
290 (((
291 AT+STOPBIT=2 for 2 bits
292 )))
293 )))
294
295
296
297 === 3.3.2 Configure sensors ===
298
299 (((
300 (((
301 Some sensors might need to configure before normal operation. User can configure such sensor via PC and RS485 adapter or through RS485-LN AT Commands (% style="color:#4f81bd" %)**AT+CFGDEV**(%%). Each (% style="color:#4f81bd" %)**AT+CFGDEV **(%%)equals to send a RS485 command to sensors. This command will only run when user input it and won’t run during each sampling.
302 )))
303 )))
304
305 (% border="1" style="background-color:#ffffcc; color:green; width:806px" %)
306 |**AT Commands**|(% style="width:418px" %)**Description**|(% style="width:256px" %)**Example**
307 |AT+CFGDEV|(% style="width:418px" %)(((
308 This command is used to configure the RS485/TTL devices; they won’t be used during sampling.
309
310 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,
311
312 mm: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command
313 )))|(% style="width:256px" %)AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
314
315 === 3.3.3 Configure read commands for each sampling ===
316
317 (((
318 During each sampling, we need confirm what commands we need to send to the RS485 sensors to read data. After the RS485 sensors send back the value, it normally include some bytes and we only need a few from them for a shorten payload.
319
320 To save the LoRaWAN network bandwidth, we might need to read data from different sensors and combine their valid value into a short payload.
321
322 This section describes how to achieve above goals.
323
324 During each sampling, the RS485-LN can support 15 commands to read sensors. And combine the return to one or several uplink payloads.
325
326
327 **Each RS485 commands include two parts:**
328
329 ~1. What commands RS485-LN will send to the RS485 sensors. There are total 15 commands from **AT+COMMAD1**, **ATCOMMAND2**,…, to **AT+COMMANDF**. All commands are of same grammar.
330
331 2. How to get wanted value the from RS485 sensors returns from by 1). There are total 15 AT Commands to handle the return, commands are **AT+DATACUT1**,**AT+DATACUT2**,…, **AT+DATACUTF** corresponding to the commands from 1). All commands are of same grammar.
332
333 3. Some RS485 device might has longer delay on reply, so user can use AT+CMDDL to set the timeout for getting reply after the RS485 command is sent. For example **AT+CMDDL1=1000** to send the open time to 1000ms
334
335
336 After we got the valid value from each RS485 commands, we need to combine them together with the command **AT+DATAUP**.
337
338
339 Below are examples for the how above AT Commands works.
340
341
342 **AT+COMMANDx : **This command will be sent to RS485 devices during each sampling, Max command length is 14 bytes. The grammar is:
343
344 (% border="1" style="background-color:#4bacc6; color:white; width:499px" %)
345 |(% style="width:496px" %)(((
346 **AT+COMMANDx=xx xx xx xx xx xx xx xx xx xx xx xx,m**
347
348 **xx xx xx xx xx xx xx xx xx xx xx xx: The RS485 command to be sent**
349
350 **m: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command**
351 )))
352
353 For example, if we have a RS485 sensor. The command to get sensor value is: 01 03 0B B8 00 02 46 0A. Where 01 03 0B B8 00 02 is the Modbus command to read the register 0B B8 where stored the sensor value. The 46 0A is the CRC-16/MODBUS which calculate manually.
354
355 In the RS485-LN, we should use this command AT+COMMAND1=01 03 0B B8 00 02,1 for the same.
356
357
358 **AT+DATACUTx : **This command defines how to handle the return from AT+COMMANDx, max return length is 45 bytes.
359
360 (% border="1" style="background-color:#4bacc6; color:white; width:725px" %)
361 |(% style="width:722px" %)(((
362 **AT+DATACUTx=a,b,c**
363
364 * **a: length for the return of AT+COMMAND**
365 * **b:1: grab valid value by byte, max 6 bytes. 2: grab valid value by bytes section, max 3 sections.**
366 * **c: define the position for valid value.  **
367 )))
368
369 **Examples:**
370
371 * Grab bytes:
372
373 [[image:image-20220602153621-1.png]]
374
375
376 * Grab a section.
377
378 [[image:image-20220602153621-2.png]]
379
380
381 * Grab different sections.
382
383 [[image:image-20220602153621-3.png]]
384
385
386 )))
387
388 === 3.3.4 Compose the uplink payload ===
389
390 (((
391 Through AT+COMMANDx and AT+DATACUTx we got valid value from each RS485 commands, Assume these valid value are RETURN1, RETURN2, .., to RETURNx. The next step is how to compose the LoRa Uplink Payload by these RETURNs. The command is **AT+DATAUP.**
392
393
394 )))
395
396 (((
397 (% style="color:#037691" %)**Examples: AT+DATAUP=0**
398
399
400 )))
401
402 (((
403 Compose the uplink payload with value returns in sequence and send with (% style="color:red" %)**A SIGNLE UPLINK**.
404 )))
405
406 (((
407 Final Payload is
408 )))
409
410 (((
411 (% style="color:#4f81bd" %)**Battery Info+PAYVER + VALID Value from RETURN1 + Valid Value from RETURN2 + … + RETURNx**
412 )))
413
414 (((
415 Where PAYVER is defined by AT+PAYVER, below is an example screen shot.
416 )))
417
418 [[image:1653269759169-150.png||height="513" width="716"]]
419
420
421 (% style="color:#037691" %)**Examples: AT+DATAUP=1**
422
423
424 Compose the uplink payload with value returns in sequence and send with (% style="color:red" %)**Multiply UPLINKs**.
425
426 Final Payload is
427
428 (% style="color:#4f81bd" %)**Battery Info+PAYVER + PAYLOAD COUNT + PAYLOAD# + DATA**
429
430 1. PAYVER: Defined by AT+PAYVER
431 1. PAYLOAD COUNT: Total how many uplinks of this sampling.
432 1. PAYLOAD#: Number of this uplink. (from 0,1,2,3…,to PAYLOAD COUNT)
433 1. DATA: Valid value: max 8 bytes for each uplink so each uplink <= 11 bytes. For the last uplink, DATA will might less than 8 bytes
434
435 [[image:image-20220602155039-4.png]]
436
437
438 So totally there will be 3 uplinks for this sampling, each uplink include 8 bytes DATA
439
440 DATA1=RETURN1 Valid Value + the first two of Valid value of RETURN10= **20 20 0a 33 90 41 02 aa**
441
442 DATA2=3^^rd^^ ~~ 10^^th^^ byte of Valid value of RETURN10= **05 81 0a 20 20 20 20 2d**
443
444 DATA3=the rest of Valid value of RETURN10= **30**
445
446
447 (% style="color:red" %)Notice: In firmware v1.3, the Max bytes has been changed according to the max bytes in different Frequency Bands for lowest SF. As below:
448
449 ~* For AU915/AS923 bands, if UplinkDwell time=0, max 51 bytes for each uplink.
450
451 * For AU915/AS923 bands, if UplinkDwell time=0, max 11 bytes for each uplink.
452
453 * For US915 band, max 11 bytes for each uplink.
454
455 ~* For all other bands: max 51 bytes for each uplink.
456
457
458 Below are the uplink payloads:
459
460 [[image:1654157178836-407.png]]
461
462
463 === 3.3.5 Uplink on demand ===
464
465 Except uplink periodically, RS485-LN is able to uplink on demand. The server send downlink command to RS485-LN and RS485 will uplink data base on the command.
466
467 Downlink control command:
468
469 **0x08 command**: Poll an uplink with current command set in RS485-LN.
470
471 **0xA8 command**: Send a command to RS485-LN and uplink the output from sensors.
472
473
474
475 === 3.3.6 Uplink on Interrupt ===
476
477 RS485-LN support external Interrupt uplink since hardware v1.2 release.
478
479 [[image:1654157342174-798.png]]
480
481 Connect the Interrupt pin to RS485-LN INT port and connect the GND pin to V- port. When there is a high voltage (Max 24v) on INT pin. Device will send an uplink packet.
482
483
484 == 3.4 Uplink Payload ==
485
486 (% border="1" style="background-color:#4bacc6; color:white; width:734px" %)
487 |**Size(bytes)**|(% style="width:120px" %)**2**|(% style="width:116px" %)**1**|(% style="width:386px" %)**Length depends on the return from the commands**
488 |Value|(% style="width:120px" %)(((
489 Battery(mV)
490
491 &
492
493 Interrupt _Flag
494 )))|(% style="width:116px" %)(((
495 PAYLOAD_VER
496
497
498 )))|(% style="width:386px" %)If the valid payload is too long and exceed the maximum support payload length in server, server will show payload not provided in the LoRaWAN server.
499
500 Below is the decoder for the first 3 bytes. The rest bytes are dynamic depends on different RS485 sensors.
501
502
503 == 3.5 Configure RS485-BL via AT or Downlink ==
504
505 User can configure RS485-LN via AT Commands or LoRaWAN Downlink Commands
506
507 There are two kinds of Commands:
508
509 * (% style="color:#4f81bd" %)**Common Commands**(%%): They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
510
511 * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for RS485-LN.  User can see these commands below:
512
513 === 3.5.1 Common Commands ===
514
515 They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
516
517
518 === 3.5.2 Sensor related commands ===
519
520 Response feature is added to the server's downlink, a special package with a FPort of 200 will be uploaded immediately after receiving the data sent by the server.
521
522 [[image:image-20220602163333-5.png||height="263" width="1160"]]
523
524 The first byte of this package represents whether the configuration is successful, 00 represents failure, 01 represents success. Except for the first byte, the other is the previous downlink. (All commands except A8 type commands are applicable)
525
526
527 === 3.5.3 Sensor related commands ===
528
529
530
531 ==== **RS485 Debug Command** ====
532
533 This command is used to configure the RS485 devices; they won’t be used during sampling.
534
535 * **AT Command**
536
537 (% class="box infomessage" %)
538 (((
539 **AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m**
540 )))
541
542 m: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command
543
544 * **Downlink Payload**
545
546 Format: A8 MM NN XX XX XX XX YY
547
548 Where:
549
550 * MM: 1: add CRC-16/MODBUS ; 0: no CRC
551 * NN: The length of RS485 command
552 * XX XX XX XX: RS485 command total NN bytes
553 * YY: How many bytes will be uplink from the return of this RS485 command,
554 ** if YY=0, RS485-LN will execute the downlink command without uplink;
555 ** if YY>0, RS485-LN will uplink total YY bytes from the output of this RS485 command; Fport=200
556 ** if YY=FF, RS485-LN will uplink RS485 output with the downlink command content; Fport=200.
557
558 **Example 1** ~-~-> Configure without ask for uplink (YY=0)
559
560 To connect a Modbus Alarm with below commands.
561
562 * The command to active alarm is: 0A 05 00 04 00 01 4C B0. Where 0A 05 00 04 00 01 is the Modbus command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which calculate manually.
563
564 * The command to deactivate alarm is: 0A 05 00 04 00 00 8D 70. Where 0A 05 00 04 00 00 is the Modbus command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which calculate manually.
565
566 So if user want to use downlink command to control to RS485 Alarm, he can use:
567
568 (% style="color:#4f81bd" %)**A8 01 06 0A 05 00 04 00 01 00**(%%): to activate the RS485 Alarm
569
570 (% style="color:#4f81bd" %)**A8 01 06 0A 05 00 04 00 00 00**(%%): to deactivate the RS485 Alarm
571
572 A8 is type code and 01 means add CRC-16/MODBUS at the end, the 3^^rd^^ byte is 06, means the next 6 bytes are the command to be sent to the RS485 network, the final byte 00 means this command don’t need to acquire output.
573
574
575 **Example 2** ~-~-> Configure with requesting uplink and original downlink command (**YY=FF**)
576
577 User in IoT server send a downlink command: (% style="color:#4f81bd" %)**A8 01 06 0A 08 00 04 00 01 YY**
578
579
580 RS485-LN got this downlink command and send (% style="color:#4f81bd" %)**0A 08 00 04 00 01 **(%%)to Modbus network. One of the RS485 sensor in the network send back Modbus reply **0A 08 00 04 00 00**. RS485-LN get this reply and combine with the original downlink command and uplink. The uplink message is:
581
582 **A8** (% style="color:#4f81bd" %)**0A 08 00 04 00  **(% style="color:red" %)**01 06** ** **(% style="color:green" %)**0A 08 00 04 00 00**
583
584 [[image:1654159460680-153.png]]
585
586
587
588 ==== **Set Payload version** ====
589
590 This is the first byte of the uplink payload. RS485-BL can connect to different sensors. User can set the PAYVER field to tell server how to decode the current payload.
591
592 * **AT Command:**
593
594 (% class="box infomessage" %)
595 (((
596 **AT+PAYVER: Set PAYVER field = 1**
597 )))
598
599 * **Downlink Payload:**
600
601 **0xAE 01**  ~-~-> Set PAYVER field =  0x01
602
603 **0xAE 0F**   ~-~-> Set PAYVER field =  0x0F
604
605
606
607 ==== **Set RS485 Sampling Commands** ====
608
609 AT+COMMANDx or AT+DATACUTx
610
611 These three commands are used to configure how the RS485-LN polling data from Modbus device. Detail of usage please see : [[polling RS485 device>>||anchor="H3.3.3Configurereadcommandsforeachsampling"]].
612
613
614 * **AT Command:**
615
616 (% class="box infomessage" %)
617 (((
618 **AT+COMMANDx: Configure RS485 read command to sensor.**
619 )))
620
621 (% class="box infomessage" %)
622 (((
623 **AT+DATACUTx: Configure how to handle return from RS485 devices.**
624 )))
625
626
627 * **Downlink Payload:**
628
629 **0xAF** downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
630
631 (% style="color:red" %)**Note**(%%): if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
632
633 Format: AF MM NN LL XX XX XX XX YY
634
635 Where:
636
637 * MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
638 * NN:  0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
639 * LL:  The length of AT+COMMAND or AT+DATACUT command
640 * XX XX XX XX: AT+COMMAND or AT+DATACUT command
641 * YY:  If YY=0, RS485-BL will execute the downlink command without uplink; if YY=1, RS485-LN will execute an uplink after got this command.
642
643 **Example:**
644
645 (% style="color:#037691" %)**AF 03 01 06 0A 05 00 04 00 01 00**(%%): Same as AT+COMMAND3=0A 05 00 04 00 01,1
646
647 (% style="color:#037691" %)**AF 03 02 06**(% style="color:orange" %)** 10 **(% style="color:red" %)**01 **(% style="color:green" %)**05 06 09 0A**(% style="color:#037691" %)** 00**(%%): Same as AT+DATACUT3=(% style="color:orange" %)**16**(%%),(% style="color:red" %)**1**(%%),(% style="color:green" %)**5+6+9+10**
648
649 (% style="color:#037691" %)**AF 03 02 06 **(% style="color:orange" %)**0B**(% style="color:red" %)** 02 **(% style="color:green" %)**05 07 08 0A **(% style="color:#037691" %)**00**(%%): Same as AT+DATACUT3=(% style="color:orange" %)**11**(%%),(% style="color:red" %)**2**(%%),(% style="color:green" %)**5~~7+8~~10**
650
651
652
653 ==== **Fast command to handle MODBUS device** ====
654
655 AT+MBFUN is valid since v1.3 firmware version. The command is for fast configure to read Modbus devices. It is only valid for the devices which follow the [[MODBUS-RTU protocol>>url:https://www.modbustools.com/modbus.html]].
656
657 This command is valid since v1.3 firmware version
658
659 AT+MBFUN can auto read the Modbus function code: 01, 02, 03 or 04. AT+MBFUN has lower priority vs AT+DATACUT command. If AT+DATACUT command is configured, AT+MBFUN will be ignore.
660
661
662 **Example:**
663
664 * AT+MBFUN=1 and AT+DATACUT1/AT+DATACUT2 are not configure (0,0,0). So RS485-LN.
665 * AT+COMMAND1= 01 03 00 10 00 08,1 ~-~-> read slave address 01 , function code 03, start address 00 01, quantity of registers 00 08.
666 * AT+COMMAND2= 01 02 00 40 00 10,1 ~-~-> read slave address 01 , function code 02, start address 00 40, quantity of inputs 00 10.
667
668 [[image:image-20220602165351-6.png]]
669
670 [[image:image-20220602165351-7.png]]
671
672
673
674 ==== **RS485 command timeout** ====
675
676 Some Modbus device has slow action to send replies. This command is used to configure the RS485-LN to use longer time to wait for their action.
677
678 Default value: 0, range:  0 ~~ 65 seconds
679
680 * **AT Command:**
681
682 (% class="box infomessage" %)
683 (((
684 **AT+CMDDLaa=hex(bb cc)*1000**
685 )))
686
687 **Example:**
688
689 **AT+CMDDL1=1000** to send the open time to 1000ms
690
691
692 * **Downlink Payload:**
693
694 **0x AA aa bb cc**
695
696 Same as: AT+CMDDLaa=hex(bb cc)*1000
697
698 **Example:**
699
700 0xAA 01 00 01  ~-~-> Same as **AT+CMDDL1=1000 ms**
701
702
703
704 ==== **Uplink payload mode** ====
705
706 Define to use one uplink or multiple uplinks for the sampling.
707
708 The use of this command please see: [[Compose Uplink payload>>||anchor="H3.3.4Composetheuplinkpayload"]]
709
710 * **AT Command:**
711
712 (% class="box infomessage" %)
713 (((
714 **AT+DATAUP=0**
715 )))
716
717 (% class="box infomessage" %)
718 (((
719 **AT+DATAUP=1**
720 )))
721
722
723 * **Downlink Payload:**
724
725 **0xAD 00**  **~-~->** Same as AT+DATAUP=0
726
727 **0xAD 01**  **~-~->** Same as AT+DATAUP=1
728
729
730
731 ==== **Manually trigger an Uplink** ====
732
733 Ask device to send an uplink immediately.
734
735 * **AT Command:**
736
737 No AT Command for this, user can press the [[ACT button>>path:#Button]] for 1 second for the same.
738
739
740 * **Downlink Payload:**
741
742 **0x08 FF**, RS485-LN will immediately send an uplink.
743
744
745
746 ==== **Clear RS485 Command** ====
747
748 The AT+COMMANDx and AT+DATACUTx settings are stored in special location, user can use below command to clear them.
749
750 * **AT Command:**
751
752 **AT+CMDEAR=mm,nn**   mm: start position of erase ,nn: stop position of erase
753
754 Etc. AT+CMDEAR=1,10 means erase AT+COMMAND1/AT+DATACUT1 to AT+COMMAND10/AT+DATACUT10
755
756 Example screen shot after clear all RS485 commands. 
757
758
759 The uplink screen shot is:
760
761 [[image:1654160691922-496.png]][[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image001.png]]
762
763
764 * **Downlink Payload:**
765
766 **0x09 aa bb** same as AT+CMDEAR=aa,bb
767
768
769
770 ==== **Set Serial Communication Parameters** ====
771
772 Set the Rs485 serial communication parameters:
773
774 * **AT Command:**
775
776 Set Baud Rate:
777
778 (% class="box infomessage" %)
779 (((
780 **AT+BAUDR=9600**    ~/~/ Options: (1200,2400,4800,14400,19200,115200)
781 )))
782
783 Set UART Parity
784
785 (% class="box infomessage" %)
786 (((
787 **AT+PARITY=0**    ~/~/ Option: 0: no parity, 1: odd parity, 2: even parity
788 )))
789
790 Set STOPBIT
791
792 (% class="box infomessage" %)
793 (((
794 **AT+STOPBIT=0**    ~/~/ Option: 0 for 1bit; 1 for 1.5 bit ; 2 for 2 bits
795 )))
796
797
798 * **Downlink Payload:**
799
800 **A7 01 aa bb**: Same  AT+BAUDR=hex(aa bb)*100
801
802 **Example:**
803
804 * A7 01 00 60   same as AT+BAUDR=9600
805 * A7 01 04 80  same as AT+BAUDR=115200
806
807 A7 02 aa: Same as  AT+PARITY=aa  (aa value: 00 , 01 or 02)
808
809 A7 03 aa: Same as  AT+STOPBIT=aa  (aa value: 00 , 01 or 02)
810
811
812 == 3.6 Listening mode for RS485 network ==
813
814 This feature support since firmware v1.4
815
816 RS485-LN supports listening mode, it can listen the RS485 network packets and send them via LoRaWAN uplink. Below is the structure. The blue arrow shows the RS485 network packets to RS485-LN.
817
818 [[image:image-20220602171200-8.png||height="567" width="1007"]]
819
820 To enable the listening mode, use can run the command AT+RXMODE.
821
822
823 (% border="1" style="background-color:#ffffcc; width:500px" %)
824 |=(% style="width: 161px;" %)**Command example:**|=(% style="width: 337px;" %)**Function**
825 |(% style="width:161px" %)AT+RXMODE=1,10 |(% style="width:337px" %)Enable listening mode 1, if RS485-LN has received more than 10 RS485 commands from the network. RS485-LN will send these commands via LoRaWAN uplinks.
826 |(% style="width:161px" %)AT+RXMODE=2,500|(% style="width:337px" %)Enable listening mode 2, RS485-LN will capture and send a 500ms content once from the first detect of character. Max value is 65535 ms
827 |(% style="width:161px" %)AT+RXMODE=0,0|(% style="width:337px" %)Disable listening mode. This is the default settings.
828 |(% style="width:161px" %) |(% style="width:337px" %)A6 aa bb cc  same as AT+RXMODE=aa,(bb<<8 ~| cc)
829
830 **Downlink Command:**
831
832 **0xA6 aa bb cc ** same as AT+RXMODE=aa,(bb<<8 | cc)
833
834
835 **Example**:
836
837 The RS485-LN is set to AT+RXMODE=2,1000
838
839 There is a two Modbus commands in the RS485 network as below:
840
841 The Modbus master send a command: (% style="background-color:#ffc000" %)01 03 00 00 00 02 c4 0b
842
843 And Modbus slave reply with: (% style="background-color:green" %)01 03 04 00 00 00 00 fa 33
844
845 RS485-LN will capture both and send the uplink: (% style="background-color:#ffc000" %)01 03 00 00 00 02 c4 0b  (% style="background-color:green" %)01 03 04 00 00 00 00 fa 33
846
847 [[image:image-20220602171200-9.png]]
848
849
850 (% style="color:red" %)Notice: Listening mode can work with the default polling mode of RS485-LN. When RS485-LN is in to send the RS485 commands (from AT+COMMANDx), the listening mode will be interrupt for a while.
851
852
853 == 3.7 Buttons ==
854
855
856 (% border="1" style="background-color:#f7faff; width:500px" %)
857 |=**Button**|=(% style="width: 1420px;" %)**Feature**
858 |**ACT**|(% style="width:1420px" %)If RS485 joined in network, press this button for more than 1 second, RS485 will upload a packet, and the SYS LED will give a (% style="color:blue" %)**Blue blink**
859 |**RST**|(% style="width:1420px" %)Reboot RS485
860 |**PRO**|(% style="width:1420px" %)Use for upload image, see [[How to Update Image>>path:#upgrade_image]]
861
862
863 == 3.8 LEDs ==
864
865 (% border="1" style="background-color:#f7faff; width:500px" %)
866 |=**LEDs**|=**Feature**
867 |**PWR**|Always on if there is power
868 |**SYS**|After device is powered on, the SYS will (% style="color:green" %)**fast blink in GREEN** (%%)for 5 times, means RS485-LN start to join LoRaWAN network. If join success, SYS will be (% style="color:green" %)**on GREEN for 5 seconds**(%%)**. **SYS will (% style="color:green" %)**blink Blue**(%%) on every upload and (% style="color:green" %)**blink Green**(%%) once receive a downlink message.
869
870
871 = 4. Case Study =
872
873 User can check this URL for some case studies: [[APP RS485 COMMUNICATE WITH SENSORS>>doc:Main.Application Note \: Communicate with Different Sensors ----- RS485-LN RS485-BL.WebHome]]
874
875
876 = 5. Use AT Command =
877
878 == 5.1 Access AT Command ==
879
880 RS485-BL supports AT Command set. User can use a USB to TTL adapter plus the 3.5mm Program Cable to connect to RS485-BL to use AT command, as below.
881
882 [[image:1654162355560-817.png]]
883
884
885 In PC, User needs to set (% style="color:blue" %)**serial tool**(%%)(such as [[putty>>url:https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to (% style="color:green" %)**9600**(%%) to access to access serial console of RS485-BL. The default password is 123456. Below is the output for reference:
886
887 [[image:1654162368066-342.png]]
888
889
890 More detail AT Command manual can be found at [[AT Command Manual>>||anchor="3.5ConfigureRS485-BLviaATorDownlink"]]
891
892
893 == 5.2 Common AT Command Sequence ==
894
895 === 5.2.1 Multi-channel ABP mode (Use with SX1301/LG308) ===
896
897 If device has not joined network yet:
898
899 (% class="box infomessage" %)
900 (((
901 **AT+FDR**
902 )))
903
904 (% class="box infomessage" %)
905 (((
906 **AT+NJM=0**
907 )))
908
909 (% class="box infomessage" %)
910 (((
911 **ATZ**
912 )))
913
914
915 If device already joined network:
916
917 (% class="box infomessage" %)
918 (((
919 **AT+NJM=0**
920 )))
921
922 (% class="box infomessage" %)
923 (((
924 **ATZ**
925 )))
926
927
928 === 5.5.2 Single-channel ABP mode (Use with LG01/LG02) ===
929
930
931 (% style="background-color:#dcdcdc" %)**AT+FDR** (%%) Reset Parameters to Factory Default, Keys Reserve
932
933 (% style="background-color:#dcdcdc" %)**AT+NJM=0 **(%%)Set to ABP mode
934
935 (% style="background-color:#dcdcdc" %)**AT+ADR=0** (%%)Set the Adaptive Data Rate Off
936
937 (% style="background-color:#dcdcdc" %)**AT+DR=5**   (%%)Set Data Rate
938
939 (% style="background-color:#dcdcdc" %)**AT+TDC=60000** (%%) Set transmit interval to 60 seconds
940
941 (% style="background-color:#dcdcdc" %)**AT+CHS=868400000**(%%) Set transmit frequency to 868.4Mhz
942
943 (% style="background-color:#dcdcdc" %)**AT+RX2FQ=868400000** (%%) Set RX2Frequency to 868.4Mhz (according to the result from server)
944
945 (% style="background-color:#dcdcdc" %)**AT+RX2DR=5**  (%%) Set RX2DR to match the downlink DR from server. see below
946
947 (% style="background-color:#dcdcdc" %)**AT+DADDR=26** (%%) 01 1A F1 Set Device Address to 26 01 1A F1, this ID can be found in the LoRa Server portal.
948
949 (% style="background-color:#dcdcdc" %)**ATZ**       (%%) Reset MCU
950
951
952 (% style="color:red" %)**Note:**
953
954 (% style="color:red" %)1. Make sure the device is set to ABP mode in the IoT Server.
955 2. Make sure the LG01/02 gateway RX frequency is exactly the same as AT+CHS setting.
956 3. Make sure SF / bandwidth setting in LG01/LG02 match the settings of AT+DR. refer [[this link>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_Gateway/&file=LoRaWAN%201.0.3%20Regional%20Parameters.xlsx]] to see what DR means.
957 4. The command AT+RX2FQ and AT+RX2DR is to let downlink work. to set the correct parameters, user can check the actually downlink parameters to be used. As below. Which shows the RX2FQ should use 868400000 and RX2DR should be 5
958
959 [[image:1654162478620-421.png]]
960
961
962 = 6. FAQ =
963
964 == 6.1 How to upgrade the image? ==
965
966 The RS485-LN LoRaWAN Controller is shipped with a 3.5mm cable, the cable is used to upload image to RS485-LN to:
967
968 * Support new features
969 * For bug fix
970 * Change LoRaWAN bands.
971
972 Below shows the hardware connection for how to upload an image to RS485-LN:
973
974 [[image:1654162535040-878.png]]
975
976 **Step1:** Download [[flash loader>>url:https://www.st.com/content/st_com/en/products/development-tools/software-development-tools/stm32-software-development-tools/stm32-programmers/flasher-stm32.html]].
977
978 **Step2**: Download the [[LT Image files>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/image/]].
979
980 **Step3: **Open flashloader; choose the correct COM port to update.
981
982 (% style="color:blue" %) Hold down the PRO button and then momentarily press the RST reset button and the SYS led will change from OFF to ON, While SYS LED is RED ON, it means the RS485-LN is ready to be program.
983
984
985 [[image:image-20220602175818-12.png]]
986
987
988 [[image:image-20220602175848-13.png]]
989
990
991 [[image:image-20220602175912-14.png]]
992
993
994 **Notice**: In case user has lost the program cable. User can hand made one from a 3.5mm cable. The pin mapping is:
995
996 [[image:image-20220602175638-10.png]]
997
998
999 == 6.2 How to change the LoRa Frequency Bands/Region? ==
1000
1001 User can follow the introduction for [[how to upgrade image>>||anchor="H6.1Howtoupgradetheimage3F"]]. When download the images, choose the required image file for download.
1002
1003
1004 == 6.3 How many RS485-Slave can RS485-BL connects? ==
1005
1006 The RS485-BL can support max 32 RS485 devices. Each uplink command of RS485-BL can support max 16 different RS485 command. So RS485-BL can support max 16 RS485 devices pre-program in the device for uplink. For other devices no pre-program, user can use the [[downlink message (type code 0xA8) to poll their info>>||anchor="H3.3.3Configurereadcommandsforeachsampling"]].
1007
1008
1009 == 6.4 Compatible question to ChirpStack and TTI LoRaWAN server ? ==
1010
1011 When user need to use with ChirpStack or TTI. Please set AT+RPL=4.
1012
1013 Detail info check this link: [[Set Packet Receiving Response Level>>doc:Main.End Device AT Commands and Downlink Command.WebHome||anchor="H7.23SetPacketReceivingResponseLevel"]]
1014
1015
1016 = 7. Trouble Shooting =
1017
1018 == 7.1 Downlink doesn’t work, how to solve it? ==
1019
1020 Please see this link for debug: [[LoRaWAN Communication Debug>>doc:Main.LoRaWAN Communication Debug.WebHome]]
1021
1022
1023 == 7.2 Why I can’t join TTN V3 in US915 /AU915 bands? ==
1024
1025 It might about the channels mapping. Please see for detail: [[Notice of Frequency band>>doc:Main.LoRaWAN Communication Debug.WebHome||anchor="H2.NoticeofUS9152FCN4702FAU915Frequencyband"]]
1026
1027
1028 = 8. Order Info =
1029
1030 (% style="color:blue" %)**Part Number: RS485-LN-XXX**
1031
1032 (% style="color:blue" %)**XXX:**
1033
1034 * (% style="color:blue" %)**EU433**(%%): frequency bands EU433
1035 * (% style="color:blue" %)**EU868**(%%): frequency bands EU868
1036 * (% style="color:blue" %)**KR920**(%%): frequency bands KR920
1037 * (% style="color:blue" %)**CN470**(%%): frequency bands CN470
1038 * (% style="color:blue" %)**AS923**(%%): frequency bands AS923
1039 * (% style="color:blue" %)**AU915**(%%): frequency bands AU915
1040 * (% style="color:blue" %)**US915**(%%): frequency bands US915
1041 * (% style="color:blue" %)**IN865**(%%): frequency bands IN865
1042 * (% style="color:blue" %)**RU864**(%%): frequency bands RU864
1043 * (% style="color:blue" %)**KZ865**(%%): frequency bands KZ865
1044
1045
1046 = 9.Packing Info =
1047
1048
1049 **Package Includes**:
1050
1051 * RS485-LN x 1
1052 * Stick Antenna for LoRa RF part x 1
1053 * Program cable x 1
1054
1055 **Dimension and weight**:
1056
1057 * Device Size: 13.5 x 7 x 3 cm
1058 * Device Weight: 105g
1059 * Package Size / pcs : 14.5 x 8 x 5 cm
1060 * Weight / pcs : 170g
1061
1062
1063 = 10. FCC Caution for RS485LN-US915 =
1064
1065 Any Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
1066
1067 This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
1068
1069
1070 **IMPORTANT NOTE:**
1071
1072 **Note: **This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1073
1074 —Reorient or relocate the receiving antenna.
1075
1076 —Increase the separation between the equipment and receiver.
1077
1078 —Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
1079
1080 —Consult the dealer or an experienced radio/TV technician for help.
1081
1082
1083 **FCC Radiation Exposure Statement:**
1084
1085 This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment.This equipment should be installed and operated with minimum distance 20cm between the radiator& your body.
1086
1087
1088 = 11. Support =
1089