Version 35.4 by Xiaoling on 2022/06/02 15:46

Show last authors
1 (% style="text-align:center" %)
2 [[image:1653266934636-343.png||height="385" width="385"]]
3
4
5
6 **RS485-LN – RS485 to LoRaWAN Converter User Manual**
7
8
9 **Table of Contents:**
10
11
12
13
14
15 = 1.Introduction =
16
17 == 1.1 What is RS485-LN RS485 to LoRaWAN Converter ==
18
19 (((
20 (((
21 The Dragino RS485-LN is a (% style="color:blue" %)**RS485 to LoRaWAN Converter**(%%). It converts the RS485 signal into LoRaWAN wireless signal which simplify the IoT installation and reduce the installation/maintaining cost.
22 )))
23
24 (((
25 RS485-LN allows user to (% style="color:blue" %)**monitor / control RS485 devices**(%%) and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, smartphone detection, building automation, and so on.
26 )))
27
28 (((
29 (% style="color:blue" %)**For data uplink**(%%), RS485-LN sends user-defined commands to RS485 devices and gets the return from the RS485 devices. RS485-LN will process these returns according to user-define rules to get the final payload and upload to LoRaWAN server.
30 )))
31
32 (((
33 (% style="color:blue" %)**For data downlink**(%%), RS485-LN runs in LoRaWAN Class C. When there downlink commands from LoRaWAN server, RS485-LN will forward the commands from LoRaWAN server to RS485 devices.
34
35 (% style="color:blue" %)**Demo Dashboard for RS485-LN**(%%) connect to two energy meters: [[https:~~/~~/app.datacake.de/dashboard/d/58844a26-378d-4c5a-aaf5-b5b5b153447a>>url:https://app.datacake.de/dashboard/d/58844a26-378d-4c5a-aaf5-b5b5b153447a]]
36 )))
37 )))
38
39 [[image:1653267211009-519.png||height="419" width="724"]]
40
41
42 == 1.2 Specifications ==
43
44
45 **Hardware System:**
46
47 * STM32L072CZT6 MCU
48 * SX1276/78 Wireless Chip 
49 * Power Consumption (exclude RS485 device):
50 ** Idle: 32mA@12v
51 ** 20dB Transmit: 65mA@12v
52
53 **Interface for Model:**
54
55 * RS485
56 * Power Input 7~~ 24V DC. 
57
58 **LoRa Spec:**
59
60 * Frequency Range:
61 ** Band 1 (HF): 862 ~~ 1020 Mhz
62 ** Band 2 (LF): 410 ~~ 528 Mhz
63 * 168 dB maximum link budget.
64 * +20 dBm - 100 mW constant RF output vs.
65 * +14 dBm high efficiency PA.
66 * Programmable bit rate up to 300 kbps.
67 * High sensitivity: down to -148 dBm.
68 * Bullet-proof front end: IIP3 = -12.5 dBm.
69 * Excellent blocking immunity.
70 * Low RX current of 10.3 mA, 200 nA register retention.
71 * Fully integrated synthesizer with a resolution of 61 Hz.
72 * FSK, GFSK, MSK, GMSK, LoRaTM and OOK modulation.
73 * Built-in bit synchronizer for clock recovery.
74 * Preamble detection.
75 * 127 dB Dynamic Range RSSI.
76 * Automatic RF Sense and CAD with ultra-fast AFC.
77 * Packet engine up to 256 bytes with CRC.
78
79
80
81 == 1.3 Features ==
82
83 * LoRaWAN Class A & Class C protocol (default Class C)
84 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915/IN865/RU864
85 * AT Commands to change parameters
86 * Remote configure parameters via LoRa Downlink
87 * Firmware upgradable via program port
88 * Support multiply RS485 devices by flexible rules
89 * Support Modbus protocol
90 * Support Interrupt uplink (Since hardware version v1.2)
91
92
93
94 == 1.4 Applications ==
95
96 * Smart Buildings & Home Automation
97 * Logistics and Supply Chain Management
98 * Smart Metering
99 * Smart Agriculture
100 * Smart Cities
101 * Smart Factory
102
103
104
105 == 1.5 Firmware Change log ==
106
107 [[RS485-LN Image files – Download link and Change log>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/]]
108
109
110 == 1.6 Hardware Change log ==
111
112 (((
113 (((
114 v1.2: Add External Interrupt Pin.
115
116 v1.0: Release
117
118
119 )))
120 )))
121
122 = 2. Power ON Device =
123
124 (((
125 The RS485-LN can be powered by 7 ~~ 24V DC power source. Connection as below
126
127 * Power Source VIN to RS485-LN VIN+
128 * Power Source GND to RS485-LN VIN-
129
130 (((
131 Once there is power, the RS485-LN will be on.
132 )))
133
134 [[image:1653268091319-405.png]]
135
136
137 )))
138
139 = 3. Operation Mode =
140
141 == 3.1 How it works? ==
142
143 (((
144 The RS485-LN is configured as LoRaWAN OTAA Class C mode by default. It has OTAA keys to join network. To connect a local LoRaWAN network, user just need to input the OTAA keys in the network server and power on the RS485-LN. It will auto join the network via OTAA.
145
146
147 )))
148
149 == 3.2 Example to join LoRaWAN network ==
150
151 Here shows an example for how to join the TTN V3 Network. Below is the network structure, we use [[LG308>>url:http://www.dragino.com/products/lora-lorawan-gateway/item/140-lg308.html]] as LoRaWAN gateway here. 
152
153 [[image:1653268155545-638.png||height="334" width="724"]]
154
155
156 (((
157 (((
158 The RS485-LN in this example connected to two RS485 devices for demonstration, user can connect to other RS485 devices via the same method. The connection is as below:
159 )))
160
161 (((
162 485A+ and 485B- of the sensor are connected to RS485A and RA485B of RS485-LN respectively.
163 )))
164
165 [[image:1653268227651-549.png||height="592" width="720"]]
166
167 (((
168 The LG308 is already set to connect to [[TTN V3 network >>path:eu1.cloud.thethings.network/]]. So what we need to now is only configure the TTN V3:
169 )))
170
171 (((
172 **Step 1**: Create a device in TTN V3 with the OTAA keys from RS485-LN.
173 )))
174
175 (((
176 Each RS485-LN is shipped with a sticker with unique device EUI:
177 )))
178 )))
179
180 [[image:1652953462722-299.png]]
181
182 (((
183 (((
184 User can enter this key in their LoRaWAN Server portal. Below is TTN V3 screen shot:
185 )))
186
187 (((
188 Add APP EUI in the application.
189 )))
190 )))
191
192 [[image:image-20220519174512-1.png]]
193
194 [[image:image-20220519174512-2.png||height="323" width="720"]]
195
196 [[image:image-20220519174512-3.png||height="556" width="724"]]
197
198 [[image:image-20220519174512-4.png]]
199
200 You can also choose to create the device manually.
201
202 [[image:1652953542269-423.png||height="710" width="723"]]
203
204 Add APP KEY and DEV EUI
205
206 [[image:1652953553383-907.png||height="514" width="724"]]
207
208
209 (((
210 **Step 2**: Power on RS485-LN and it will auto join to the TTN V3 network. After join success, it will start to upload message to TTN V3 and user can see in the panel.
211 )))
212
213 [[image:1652953568895-172.png||height="232" width="724"]]
214
215
216 == 3.3 Configure Commands to read data ==
217
218 (((
219 (((
220 There are plenty of RS485 devices in the market and each device has different command to read the valid data. To support these devices in flexible, RS485-LN supports flexible command set. User can use [[AT Commands>>path:#AT_COMMAND]] or LoRaWAN Downlink Command to configure what commands RS485-LN should send for each sampling and how to handle the return from RS485 devices.
221 )))
222
223 (((
224 (% style="color:red" %)Note: below description and commands are for firmware version >v1.1, if you have firmware version v1.0. Please check the [[user manual v1.0>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/&file=RS485-LN_UserManual_v1.0.1.pdf]] or upgrade the firmware to v1.1
225
226
227 )))
228 )))
229
230 === 3.3.1 onfigure UART settings for RS485 or TTL communication ===
231
232 To use RS485-LN to read data from RS485 sensors, connect the RS485-LN A/B traces to the sensors. And user need to make sure RS485-LN use the match UART setting to access the sensors. The related commands for UART settings are:
233
234 (% border="1" style="background-color:#ffffcc; color:green; width:782px" %)
235 |(% style="width:128px" %)(((
236 **AT Commands**
237 )))|(% style="width:305px" %)(((
238 **Description**
239 )))|(% style="width:346px" %)(((
240 **Example**
241 )))
242 |(% style="width:128px" %)(((
243 AT+BAUDR
244 )))|(% style="width:305px" %)(((
245 Set the baud rate (for RS485 connection). Default Value is: 9600.
246 )))|(% style="width:346px" %)(((
247 (((
248 AT+BAUDR=9600
249 )))
250
251 (((
252 Options: (1200,2400,4800,14400,19200,115200)
253 )))
254 )))
255 |(% style="width:128px" %)(((
256 AT+PARITY
257 )))|(% style="width:305px" %)(((
258 Set UART parity (for RS485 connection)
259 )))|(% style="width:346px" %)(((
260 (((
261 AT+PARITY=0
262 )))
263
264 (((
265 Option: 0: no parity, 1: odd parity, 2: even parity
266 )))
267 )))
268 |(% style="width:128px" %)(((
269 AT+STOPBIT
270 )))|(% style="width:305px" %)(((
271 (((
272 Set serial stopbit (for RS485 connection)
273 )))
274
275 (((
276
277 )))
278 )))|(% style="width:346px" %)(((
279 (((
280 AT+STOPBIT=0 for 1bit
281 )))
282
283 (((
284 AT+STOPBIT=1 for 1.5 bit
285 )))
286
287 (((
288 AT+STOPBIT=2 for 2 bits
289 )))
290 )))
291
292
293
294 === 3.3.2 Configure sensors ===
295
296 (((
297 (((
298 Some sensors might need to configure before normal operation. User can configure such sensor via PC and RS485 adapter or through RS485-LN AT Commands (% style="color:#4f81bd" %)**AT+CFGDEV**(%%). Each (% style="color:#4f81bd" %)**AT+CFGDEV **(%%)equals to send a RS485 command to sensors. This command will only run when user input it and won’t run during each sampling.
299 )))
300 )))
301
302 (% border="1" style="background-color:#ffffcc; color:green; width:806px" %)
303 |**AT Commands**|(% style="width:418px" %)**Description**|(% style="width:256px" %)**Example**
304 |AT+CFGDEV|(% style="width:418px" %)(((
305 This command is used to configure the RS485/TTL devices; they won’t be used during sampling.
306
307 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,
308
309 mm: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command
310 )))|(% style="width:256px" %)AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
311
312
313
314 === 3.3.3 Configure read commands for each sampling ===
315
316 (((
317 During each sampling, we need confirm what commands we need to send to the RS485 sensors to read data. After the RS485 sensors send back the value, it normally include some bytes and we only need a few from them for a shorten payload.
318
319 To save the LoRaWAN network bandwidth, we might need to read data from different sensors and combine their valid value into a short payload.
320
321 This section describes how to achieve above goals.
322
323 During each sampling, the RS485-LN can support 15 commands to read sensors. And combine the return to one or several uplink payloads.
324
325
326 **Each RS485 commands include two parts:**
327
328 ~1. What commands RS485-LN will send to the RS485 sensors. There are total 15 commands from **AT+COMMAD1**, **ATCOMMAND2**,…, to **AT+COMMANDF**. All commands are of same grammar.
329
330 2. How to get wanted value the from RS485 sensors returns from by 1). There are total 15 AT Commands to handle the return, commands are **AT+DATACUT1**,**AT+DATACUT2**,…, **AT+DATACUTF** corresponding to the commands from 1). All commands are of same grammar.
331
332 3. Some RS485 device might has longer delay on reply, so user can use AT+CMDDL to set the timeout for getting reply after the RS485 command is sent. For example **AT+CMDDL1=1000** to send the open time to 1000ms
333
334
335 After we got the valid value from each RS485 commands, we need to combine them together with the command **AT+DATAUP**.
336
337
338 Below are examples for the how above AT Commands works.
339
340
341 **AT+COMMANDx : **This command will be sent to RS485 devices during each sampling, Max command length is 14 bytes. The grammar is:
342
343 (% border="1" style="background-color:#4bacc6; color:white; width:499px" %)
344 |(% style="width:496px" %)(((
345 **AT+COMMANDx=xx xx xx xx xx xx xx xx xx xx xx xx,m**
346
347 **xx xx xx xx xx xx xx xx xx xx xx xx: The RS485 command to be sent**
348
349 **m: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command**
350 )))
351
352 For example, if we have a RS485 sensor. The command to get sensor value is: 01 03 0B B8 00 02 46 0A. Where 01 03 0B B8 00 02 is the Modbus command to read the register 0B B8 where stored the sensor value. The 46 0A is the CRC-16/MODBUS which calculate manually.
353
354 In the RS485-LN, we should use this command AT+COMMAND1=01 03 0B B8 00 02,1 for the same.
355
356
357 **AT+DATACUTx : **This command defines how to handle the return from AT+COMMANDx, max return length is 45 bytes.
358
359 (% border="1" style="background-color:#4bacc6; color:white; width:725px" %)
360 |(% style="width:722px" %)(((
361 **AT+DATACUTx=a,b,c**
362
363 * **a: length for the return of AT+COMMAND**
364 * **b:1: grab valid value by byte, max 6 bytes. 2: grab valid value by bytes section, max 3 sections.**
365 * **c: define the position for valid value. **
366 )))
367
368
369 **Examples:**
370
371 * Grab bytes:
372
373 [[image:image-20220602153621-1.png]]
374
375
376 * Grab a section.
377
378 [[image:image-20220602153621-2.png]]
379
380
381 * Grab different sections.
382
383 [[image:image-20220602153621-3.png]]
384
385
386 )))
387
388 === 3.3.4 Compose the uplink payload ===
389
390 (((
391 Through AT+COMMANDx and AT+DATACUTx we got valid value from each RS485 commands, Assume these valid value are RETURN1, RETURN2, .., to RETURNx. The next step is how to compose the LoRa Uplink Payload by these RETURNs. The command is **AT+DATAUP.**
392 )))
393
394 (((
395 (% style="color:#4f81bd" %)**Examples: AT+DATAUP=0**
396 )))
397
398 (((
399 Compose the uplink payload with value returns in sequence and send with (% style="color:red" %)**A SIGNLE UPLINK**.
400 )))
401
402 (((
403 Final Payload is
404 )))
405
406 (((
407 (% style="color:#4f81bd" %)**Battery Info+PAYVER + VALID Value from RETURN1 + Valid Value from RETURN2 + … + RETURNx**
408 )))
409
410 (((
411 Where PAYVER is defined by AT+PAYVER, below is an example screen shot.
412 )))
413
414 [[image:1653269759169-150.png||height="513" width="716"]]
415
416 (% style="color:#4f81bd" %)**Examples: AT+DATAUP=1**
417
418 Compose the uplink payload with value returns in sequence and send with (% style="color:red" %)**Multiply UPLINKs**.
419
420 Final Payload is
421
422 (% style="color:#4f81bd" %)**Battery Info+PAYVER + PAYLOAD COUNT + PAYLOAD# + DATA**
423
424 1. Battery Info (2 bytes): Battery voltage
425 1. PAYVER (1 byte): Defined by AT+PAYVER
426 1. PAYLOAD COUNT (1 byte): Total how many uplinks of this sampling.
427 1. PAYLOAD# (1 byte): Number of this uplink. (from 0,1,2,3…,to PAYLOAD COUNT)
428 1. DATA: Valid value: max 6 bytes(US915 version here, Notice*!) for each uplink so each uplink <= 11 bytes. For the last uplink, DATA will might less than 6 bytes
429
430 [[image:1653269916228-732.png||height="433" width="711"]]
431
432
433 So totally there will be 3 uplinks for this sampling, each uplink includes 6 bytes DATA
434
435 DATA1=RETURN1 Valid Value = (% style="background-color:green; color:white" %)20 20 0a 33 90 41
436
437 DATA2=1^^st^^ ~~ 6^^th^^ byte of Valid value of RETURN10=(% style="background-color:green; color:white" %) 02 aa 05 81 0a 20
438
439 DATA3=7^^th^^ ~~ 11^^th^^ bytes of Valid value of RETURN10 = (% style="background-color:green; color:white" %)20 20 20 2d 30
440
441 Below are the uplink payloads:
442
443 [[image:1653270130359-810.png]]
444
445
446 (% style="color:red" %)**Notice: the Max bytes is according to the max support bytes in different Frequency Bands for lowest SF. As below:**
447
448 ~* For AU915/AS923 bands, if UplinkDwell time=0, max 51 bytes for each uplink ( so 51 -5 = 46 max valid date)
449
450 * For AU915/AS923 bands, if UplinkDwell time=1, max 11 bytes for each uplink ( so 11 -5 = 6 max valid date).
451
452 * For US915 band, max 11 bytes for each uplink ( so 11 -5 = 6 max valid date).
453
454 ~* For all other bands: max 51 bytes for each uplink  ( so 51 -5 = 46 max valid date).
455
456 === 3.3.5 Uplink on demand ===
457
458 Except uplink periodically, RS485-BL is able to uplink on demand. The server sends downlink command to RS485-BL and RS485 will uplink data base on the command.
459
460 Downlink control command:
461
462 [[0x08 command>>path:#downlink_08]]: Poll an uplink with current command set in RS485-BL.
463
464 [[0xA8 command>>path:#downlink_A8]]: Send a command to RS485-BL and uplink the output from sensors.
465
466
467
468 1.
469 11.
470 111. Uplink on Interrupt
471
472 Put the interrupt sensor between 3.3v_out and GPIO ext.[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image022.png]]
473
474 AT+INTMOD=0  Disable Interrupt
475
476 AT+INTMOD=1  Interrupt trigger by rising or falling edge.
477
478 AT+INTMOD=2  Interrupt trigger by falling edge. ( Default Value)
479
480 AT+INTMOD=3  Interrupt trigger by rising edge.
481
482
483 1.
484 11. Uplink Payload
485
486 |**Size(bytes)**|**2**|**1**|**Length depends on the return from the commands**
487 |Value|(((
488 Battery(mV)
489
490 &
491
492 Interrupt _Flag
493 )))|(((
494 PAYLOAD_VER
495
496
497 )))|If the valid payload is too long and exceed the maximum support payload length in server, server will show payload not provided in the LoRaWAN server.
498
499 Below is the decoder for the first 3 bytes. The rest bytes are dynamic depends on different RS485 sensors.
500
501
502 function Decoder(bytes, port) {
503
504 ~/~/Payload Formats of RS485-BL Deceive
505
506 return {
507
508 ~/~/Battery,units:V
509
510 BatV:((bytes[0]<<8 | bytes[1])&0x7fff)/1000,
511
512 ~/~/GPIO_EXTI 
513
514 EXTI_Trigger:(bytes[0] & 0x80)? "TRUE":"FALSE",
515
516 ~/~/payload of version
517
518 Pay_ver:bytes[2],
519
520 };
521
522 }
523
524
525
526
527
528
529
530 TTN V3 uplink screen shot.
531
532 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
533
534 1.
535 11. Configure RS485-BL via AT or Downlink
536
537 User can configure RS485-BL via [[AT Commands >>path:#_​Using_the_AT]]or LoRaWAN Downlink Commands
538
539 There are two kinds of Commands:
540
541 * **Common Commands**: They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: http:~/~/wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands
542
543 * **Sensor Related Commands**: These commands are special designed for RS485-BL.  User can see these commands below:
544
545 1.
546 11.
547 111. Common Commands:
548
549 They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[http:~~/~~/wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands>>url:http://wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands]]
550
551
552 1.
553 11.
554 111. Sensor related commands:
555
556 ==== Choose Device Type (RS485 or TTL) ====
557
558 RS485-BL can connect to either RS485 sensors or TTL sensor. User need to specify what type of sensor need to connect.
559
560 * AT Command
561
562 **AT+MOD=1** ~/~/ Set to support RS485-MODBUS type sensors. User can connect multiply RS485 , Modbus sensors to the A / B pins.
563
564 **AT+MOD=2** ~/~/ Set to support TTL Level sensors, User can connect one TTL Sensor to the TXD/RXD/GND pins.
565
566
567 * Downlink Payload
568
569 **0A aa**     à same as AT+MOD=aa
570
571
572
573 ==== [[RS485 Debug Command>>path:#downlink_A8]] (AT+CFGDEV) ====
574
575 This command is used to configure the RS485 or TTL sensors; they won’t be used during sampling.
576
577 * AT Command
578
579 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
580
581 m: 0: no CRC; 1: add CRC-16/MODBUS in the end of this command.
582
583
584
585 * Downlink Payload
586
587 Format: A8 MM NN XX XX XX XX YY
588
589 Where:
590
591 * MM: 1: add CRC-16/MODBUS ; 0: no CRC
592 * NN: The length of RS485 command
593 * XX XX XX XX: RS485 command total NN bytes
594 * YY: How many bytes will be uplink from the return of this RS485 command, if YY=0, RS485-BL will execute the downlink command without uplink; if YY>0, RS485-BL will uplink total YY bytes from the output of this RS485 command
595
596 **Example 1:**
597
598 To connect a Modbus Alarm with below commands.
599
600 * The command to active alarm is: 0A 05 00 04 00 01 4C B0. Where 0A 05 00 04 00 01 is the Modbus command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which calculate manually.
601
602 * The command to deactivate alarm is: 0A 05 00 04 00 00 8D 70. Where 0A 05 00 04 00 00 is the Modbus command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which calculate manually.
603
604 So if user want to use downlink command to control to RS485 Alarm, he can use:
605
606 **A8 01 06 0A 05 00 04 00 01 00**: to activate the RS485 Alarm
607
608 **A8 01 06 0A 05 00 04 00 00 00**: to deactivate the RS485 Alarm
609
610 A8 is type code and 01 means add CRC-16/MODBUS at the end, the 3^^rd^^ byte is 06, means the next 6 bytes are the command to be sent to the RS485 network, the final byte 00 means this command don’t need to acquire output.
611
612
613 **Example 2:**
614
615 Check TTL Sensor return:
616
617 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image024.png]]
618
619
620
621
622 ==== Set Payload version ====
623
624 This is the first byte of the uplink payload. RS485-BL can connect to different sensors. User can set the PAYVER field to tell server how to decode the current payload.
625
626 * AT Command:
627
628 AT+PAYVER: Set PAYVER field = 1
629
630
631 * Downlink Payload:
632
633 0xAE 01   à Set PAYVER field =  0x01
634
635 0xAE 0F   à Set PAYVER field =  0x0F
636
637
638 ==== Set RS485 Sampling Commands ====
639
640 AT+COMMANDx, AT+DATACUTx and AT+SEARCHx
641
642 These three commands are used to configure how the RS485-BL polling data from Modbus device. Detail of usage please see : [[polling RS485 device>>path:#polling_485]].
643
644
645 * AT Command:
646
647 AT+COMMANDx: Configure RS485 read command to sensor.
648
649 AT+DATACUTx: Configure how to handle return from RS485 devices.
650
651 AT+SEARCHx: Configure search command
652
653
654 * Downlink Payload:
655
656 0xAF downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
657
658 Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
659
660 Format: AF MM NN LL XX XX XX XX YY
661
662 Where:
663
664 * MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
665 * NN: 0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
666 * LL: The length of AT+COMMAND or AT+DATACUT command
667 * XX XX XX XX: AT+COMMAND or AT+DATACUT command
668 * YY: If YY=0, RS485-BL will execute the downlink command without uplink; if YY=1, RS485-BL will execute an uplink after got this command.
669
670 Example:
671
672 **AF 03 01 06 0A 05 00 04 00 01 00**: Same as AT+COMMAND3=0A 05 00 04 00 01,1
673
674 **AF 03 02 06 10 01 05 06 09 0A 00**: Same as AT+DATACUT3=**16**,**1**,**5+6+9+10**
675
676 **AF 03 02 06 0B 02 05 07 08 0A 00**: Same as AT+DATACUT3=**11**,**2**,**5~~7+8~~10**
677
678
679 0xAB downlink command can be used for set AT+SEARCHx
680
681 Example: **AB aa 01 03 xx xx xx** (03 here means there are total 3 bytes after 03) So
682
683 * AB aa 01 03 xx xx xx  same as AT+SEARCHaa=1,xx xx xx
684 * AB aa 02 03 xx xx xx 02 yy yy(03 means there are 3 bytes after 03, they are xx xx xx;02 means there are 2 bytes after 02, they are yy yy) so the commands
685
686 **AB aa 02 03 xx xx xx 02 yy yy**  same as **AT+SEARCHaa=2,xx xx xx+yy yy**
687
688
689 ==== Fast command to handle MODBUS device ====
690
691 AT+MBFUN is valid since v1.3 firmware version. The command is for fast configure to read Modbus devices. It is only valid for the devices which follow the [[MODBUS-RTU protocol>>url:https://www.modbustools.com/modbus.html]].
692
693 This command is valid since v1.3 firmware version
694
695
696 AT+MBFUN has only two value:
697
698 * AT+MBFUN=1: Enable Modbus reading. And get response base on the MODBUS return
699
700 AT+MBFUN=1, device can auto read the Modbus function code: 01, 02, 03 or 04. AT+MBFUN has lower priority vs AT+DATACUT command. If AT+DATACUT command is configured, AT+MBFUN will be ignore.
701
702 * AT+MBFUN=0: Disable Modbus fast reading.
703
704 Example:
705
706 * AT+MBFUN=1 and AT+DATACUT1/AT+DATACUT2 are not configure (0,0,0).
707 * AT+COMMAND1= 01 03 00 10 00 08,1 ~-~-> read slave address 01 , function code 03, start address 00 01, quantity of registers 00 08.
708 * AT+COMMAND2= 01 02 00 40 00 10,1 ~-~-> read slave address 01 , function code 02, start address 00 40, quantity of inputs 00 10.
709
710 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image025.png]]
711
712
713 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image026.png]]
714
715
716 * Downlink Commands:
717
718 A9 aa -à Same as AT+MBFUN=aa
719
720
721 ==== RS485 command timeout ====
722
723 Some Modbus device has slow action to send replies. This command is used to configure the RS485-BL to use longer time to wait for their action.
724
725 Default value: 0, range:  0 ~~ 5 seconds
726
727
728 * AT Command:
729
730 AT+CMDDLaa=hex(bb cc)
731
732 Example:
733
734 **AT+CMDDL1=1000** to send the open time to 1000ms
735
736
737 * Downlink Payload:
738
739 0x AA aa bb cc
740
741 Same as: AT+CMDDLaa=hex(bb cc)
742
743 Example:
744
745 0xAA 01 03 E8  à Same as **AT+CMDDL1=1000 ms**
746
747
748 ==== [[Uplink>>path:#downlink_A8]] payload mode ====
749
750 Define to use one uplink or multiple uplinks for the sampling.
751
752 The use of this command please see: [[Compose Uplink payload>>path:#DataUP]]
753
754 * AT Command:
755
756 AT+DATAUP=0
757
758 AT+DATAUP=1
759
760
761 * Downlink Payload:
762
763 0xAD 00   à Same as AT+DATAUP=0
764
765 0xAD 01   à Same as AT+DATAUP=1
766
767
768 ==== Manually trigger an Uplink ====
769
770 Ask device to send an uplink immediately.
771
772 * Downlink Payload:
773
774 0x08 FF, RS485-BL will immediately send an uplink.
775
776
777 ==== Clear RS485 Command ====
778
779 The AT+COMMANDx and AT+DATACUTx settings are stored in special location, user can use below command to clear them.
780
781
782 * AT Command:
783
784 **AT+CMDEAR=mm,nn**   mm: start position of erase ,nn: stop position of erase
785
786 Etc. AT+CMDEAR=1,10 means erase AT+COMMAND1/AT+DATACUT1 to AT+COMMAND10/AT+DATACUT10
787
788 Example screen shot after clear all RS485 commands. 
789
790
791
792 The uplink screen shot is:
793
794 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
795
796
797 * Downlink Payload:
798
799 0x09 aa bb same as AT+CMDEAR=aa,bb
800
801
802 ==== Set Serial Communication Parameters ====
803
804 Set the Rs485 serial communication parameters:
805
806 * AT Command:
807
808 Set Baud Rate:
809
810 AT+BAUDR=9600    ~/~/ Options: (1200,2400,4800,14400,19200,115200)
811
812
813 Set UART parity
814
815 AT+PARITY=0    ~/~/ Option: 0: no parity, 1: odd parity, 2: even parity
816
817
818 Set STOPBIT
819
820 AT+STOPBIT=0    ~/~/ Option: 0 for 1bit; 1 for 1.5 bit ; 2 for 2 bits
821
822
823 * Downlink Payload:
824
825 A7 01 aa bb: Same  AT+BAUDR=hex(aa bb)*100
826
827 Example:
828
829 * A7 01 00 60   same as AT+BAUDR=9600
830 * A7 01 04 80  same as AT+BAUDR=115200
831
832 A7 02 aa: Same as  AT+PARITY=aa  (aa value: 00 , 01 or 02)
833
834 A7 03 aa: Same as  AT+STOPBIT=aa  (aa value: 00 , 01 or 02)
835
836
837 ==== Control output power duration ====
838
839 User can set the output power duration before each sampling.
840
841 * AT Command:
842
843 Example:
844
845 AT+3V3T=1000 ~/~/ 3V3 output power will open 1s before each sampling.
846
847 AT+5VT=1000 ~/~/ +5V output power will open 1s before each sampling.
848
849
850 * LoRaWAN Downlink Command:
851
852 07 01 aa bb  Same as AT+5VT=(aa bb)
853
854 07 02 aa bb  Same as AT+3V3T=(aa bb)
855
856
857
858
859 1.
860 11. Buttons
861
862 |**Button**|**Feature**
863 |**RST**|Reboot RS485-BL
864
865 1.
866 11. +3V3 Output
867
868 RS485-BL has a Controllable +3V3 output, user can use this output to power external sensor.
869
870 The +3V3 output will be valid for every sampling. RS485-BL will enable +3V3 output before all sampling and disable the +3V3 after all sampling. 
871
872
873 The +3V3 output time can be controlled by AT Command.
874
875 **AT+3V3T=1000**
876
877 Means set +3v3 valid time to have 1000ms. So, the real +3v3 output will actually have 1000ms + sampling time for other sensors.
878
879
880 By default, the AT+3V3T=0. This is a special case, means the +3V3 output is always on at any time
881
882
883 1.
884 11. +5V Output
885
886 RS485-BL has a Controllable +5V output, user can use this output to power external sensor.
887
888 The +5V output will be valid for every sampling. RS485-BL will enable +5V output before all sampling and disable the +5v after all sampling. 
889
890
891 The 5V output time can be controlled by AT Command.
892
893 **AT+5VT=1000**
894
895 Means set 5V valid time to have 1000ms. So, the real 5V output will actually have 1000ms + sampling time for other sensors.
896
897
898 By default, the AT+5VT=0. If the external sensor which require 5v and require more time to get stable state, user can use this command to increase the power ON duration for this sensor.
899
900
901
902
903 1.
904 11. LEDs
905
906 |**LEDs**|**Feature**
907 |**LED1**|Blink when device transmit a packet.
908
909 1.
910 11. Switch Jumper
911
912 |**Switch Jumper**|**Feature**
913 |**SW1**|(((
914 ISP position: Upgrade firmware via UART
915
916 Flash position: Configure device, check running status.
917 )))
918 |**SW2**|(((
919 5V position: set to compatible with 5v I/O.
920
921 3.3v position: set to compatible with 3.3v I/O.,
922 )))
923
924 +3.3V: is always ON
925
926 +5V: Only open before every sampling. The time is by default, it is AT+5VT=0.  Max open time. 5000 ms.
927
928 1. Case Study
929
930 User can check this URL for some case studies.
931
932 [[http:~~/~~/wiki.dragino.com/index.php?title=APP_RS485_COMMUNICATE_WITH_SENSORS>>url:http://wiki.dragino.com/index.php?title=APP_RS485_COMMUNICATE_WITH_SENSORS]]
933
934
935
936
937 1. Use AT Command
938 11. Access AT Command
939
940 RS485-BL supports AT Command set. User can use a USB to TTL adapter plus the 3.5mm Program Cable to connect to RS485-BL to use AT command, as below.
941
942 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image027.png]]
943
944
945 In PC, User needs to set **serial tool**(such as [[putty>>url:https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to **9600** to access to access serial console of RS485-BL. The default password is 123456. Below is the output for reference:
946
947 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image028.png]]
948
949
950
951 More detail AT Command manual can be found at [[AT Command Manual>>path:#AT_COMMAND]]
952
953
954
955 1.
956 11. Common AT Command Sequence
957 111. Multi-channel ABP mode (Use with SX1301/LG308)
958
959 If device has not joined network yet:
960
961 AT+FDR
962
963 AT+NJM=0
964
965 ATZ
966
967
968 If device already joined network:
969
970 AT+NJM=0
971
972 ATZ
973
974 1.
975 11.
976 111. Single-channel ABP mode (Use with LG01/LG02)
977
978 AT+FDR   Reset Parameters to Factory Default, Keys Reserve
979
980 AT+NJM=0 Set to ABP mode
981
982 AT+ADR=0 Set the Adaptive Data Rate Off
983
984 AT+DR=5  Set Data Rate
985
986 AT+TDC=60000  Set transmit interval to 60 seconds
987
988 AT+CHS=868400000 Set transmit frequency to 868.4Mhz
989
990 AT+RX2FQ=868400000 Set RX2Frequency to 868.4Mhz (according to the result from server)
991
992 AT+RX2DR=5  Set RX2DR to match the downlink DR from server. see below
993
994 AT+DADDR=26 01 1A F1 Set Device Address to 26 01 1A F1, this ID can be found in the LoRa Server portal.
995
996 ATZ          Reset MCU
997
998 **Note:**
999
1000 1. Make sure the device is set to ABP mode in the IoT Server.
1001 1. Make sure the LG01/02 gateway RX frequency is exactly the same as AT+CHS setting.
1002 1. Make sure SF / bandwidth setting in LG01/LG02 match the settings of AT+DR. refer [[this link>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_Gateway/&file=LoRaWAN%201.0.3%20Regional%20Parameters.xlsx]] to see what DR means.
1003 1. The command AT+RX2FQ and AT+RX2DR is to let downlink work. to set the correct parameters, user can check the actually downlink parameters to be used. As below. Which shows the RX2FQ should use 868400000 and RX2DR should be 5
1004
1005 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image029.png]]
1006
1007
1008 1. FAQ
1009 11. How to upgrade the image?
1010
1011 The RS485-BL LoRaWAN Controller is shipped with a 3.5mm cable, the cable is used to upload image to RS485-BL to:
1012
1013 * Support new features
1014 * For bug fix
1015 * Change LoRaWAN bands.
1016
1017 Below shows the hardware connection for how to upload an image to RS485-BL:
1018
1019 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image030.png]]
1020
1021 **Step1:** Download [[flash loader>>url:https://www.st.com/content/st_com/en/products/development-tools/software-development-tools/stm32-software-development-tools/stm32-programmers/flasher-stm32.html]].
1022
1023 **Step2**: Download the [[LT Image files>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/image/]].
1024
1025 **Step3: **Open flashloader; choose the correct COM port to update.
1026
1027
1028 |(((
1029 HOLD PRO then press the RST button, SYS will be ON, then click next
1030 )))
1031
1032 |(((
1033 Board detected
1034 )))
1035
1036 |(((
1037
1038 )))
1039
1040 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image031.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image032.png]]
1041
1042
1043
1044 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image033.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image034.png]]
1045
1046
1047 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image035.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image036.png]]
1048
1049
1050 1.
1051 11. How to change the LoRa Frequency Bands/Region?
1052
1053 User can follow the introduction for [[how to upgrade image>>path:#upgrade_image]]. When download the images, choose the required image file for download.
1054
1055
1056
1057 1.
1058 11. How many RS485-Slave can RS485-BL connects?
1059
1060 The RS485-BL can support max 32 RS485 devices. Each uplink command of RS485-BL can support max 16 different RS485 command. So RS485-BL can support max 16 RS485 devices pre-program in the device for uplink. For other devices no pre-program, user can use the [[downlink message (type code 0xA8) to poll their info>>path:#downlink_A8]].
1061
1062
1063
1064
1065 1. Trouble Shooting     
1066 11. Downlink doesn’t work, how to solve it?
1067
1068 Please see this link for debug:
1069
1070 [[http:~~/~~/wiki.dragino.com/index.php?title=Main_Page#LoRaWAN_Communication_Debug>>url:http://wiki.dragino.com/index.php?title=Main_Page#LoRaWAN_Communication_Debug]] 
1071
1072
1073
1074 1.
1075 11. Why I can’t join TTN V3 in US915 /AU915 bands?
1076
1077 It might about the channels mapping. Please see for detail.
1078
1079 [[http:~~/~~/wiki.dragino.com/index.php?title=LoRaWAN_Communication_Debug#Notice_of_US915.2FCN470.2FAU915_Frequency_band>>url:http://wiki.dragino.com/index.php?title=LoRaWAN_Communication_Debug#Notice_of_US915.2FCN470.2FAU915_Frequency_band]]
1080
1081
1082
1083 1. Order Info
1084
1085 **Part Number: RS485-BL-XXX**
1086
1087 **XXX:**
1088
1089 * **EU433**: frequency bands EU433
1090 * **EU868**: frequency bands EU868
1091 * **KR920**: frequency bands KR920
1092 * **CN470**: frequency bands CN470
1093 * **AS923**: frequency bands AS923
1094 * **AU915**: frequency bands AU915
1095 * **US915**: frequency bands US915
1096 * **IN865**: frequency bands IN865
1097 * **RU864**: frequency bands RU864
1098 * **KZ865: **frequency bands KZ865
1099
1100 1. Packing Info
1101
1102 **Package Includes**:
1103
1104 * RS485-BL x 1
1105 * Stick Antenna for LoRa RF part x 1
1106 * Program cable x 1
1107
1108 **Dimension and weight**:
1109
1110 * Device Size: 13.5 x 7 x 3 cm
1111 * Device Weight: 105g
1112 * Package Size / pcs : 14.5 x 8 x 5 cm
1113 * Weight / pcs : 170g
1114
1115 1. Support
1116
1117 * Support is provided Monday to Friday, from 09:00 to 18:00 GMT+8. Due to different timezones we cannot offer live support. However, your questions will be answered as soon as possible in the before-mentioned schedule.
1118 * Provide as much information as possible regarding your enquiry (product models, accurately describe your problem and steps to replicate it etc) and send a mail to