Show last authors
1 (% style="text-align:center" %)
2 [[image:1653266934636-343.png||height="385" width="385"]]
3
4
5
6 **RS485-LN – RS485 to LoRaWAN Converter User Manual**
7
8
9 **Table of Contents:**
10
11
12
13
14
15 = 1.Introduction =
16
17 == 1.1 What is RS485-LN RS485 to LoRaWAN Converter ==
18
19 (((
20 (((
21 The Dragino RS485-LN is a RS485 to LoRaWAN Converter. It converts the RS485 signal into LoRaWAN wireless signal which simplify the IoT installation and reduce the installation/maintaining cost.
22 )))
23
24 (((
25 RS485-LN allows user to monitor / control RS485 devices and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, smartphone detection, building automation, and so on.
26 )))
27
28 (((
29 For data uplink, RS485-LN sends user-defined commands to RS485 devices and gets the return from the RS485 devices. RS485-LN will process these returns according to user-define rules to get the final payload and upload to LoRaWAN server.
30 )))
31
32 (((
33 For data downlink, RS485-LN runs in LoRaWAN Class C. When there downlink commands from LoRaWAN server, RS485-LN will forward the commands from LoRaWAN server to RS485 devices.
34 )))
35 )))
36
37 [[image:1653267211009-519.png||height="419" width="724"]]
38
39 == 1.2 Specifications ==
40
41 **Hardware System:**
42
43 * STM32L072CZT6 MCU
44 * SX1276/78 Wireless Chip 
45 * Power Consumption (exclude RS485 device):
46 ** Idle: 32mA@12v
47
48 *
49 ** 20dB Transmit: 65mA@12v
50
51 **Interface for Model:**
52
53 * RS485
54 * Power Input 7~~ 24V DC. 
55
56 **LoRa Spec:**
57
58 * Frequency Range:
59 ** Band 1 (HF): 862 ~~ 1020 Mhz
60 ** Band 2 (LF): 410 ~~ 528 Mhz
61 * 168 dB maximum link budget.
62 * +20 dBm - 100 mW constant RF output vs.
63 * +14 dBm high efficiency PA.
64 * Programmable bit rate up to 300 kbps.
65 * High sensitivity: down to -148 dBm.
66 * Bullet-proof front end: IIP3 = -12.5 dBm.
67 * Excellent blocking immunity.
68 * Low RX current of 10.3 mA, 200 nA register retention.
69 * Fully integrated synthesizer with a resolution of 61 Hz.
70 * FSK, GFSK, MSK, GMSK, LoRaTM and OOK modulation.
71 * Built-in bit synchronizer for clock recovery.
72 * Preamble detection.
73 * 127 dB Dynamic Range RSSI.
74 * Automatic RF Sense and CAD with ultra-fast AFC.
75 * Packet engine up to 256 bytes with CRC.
76
77 == 1.3 Features ==
78
79 * LoRaWAN Class A & Class C protocol (default Class C)
80 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915/IN865/RU864
81 * AT Commands to change parameters
82 * Remote configure parameters via LoRa Downlink
83 * Firmware upgradable via program port
84 * Support multiply RS485 devices by flexible rules
85 * Support Modbus protocol
86 * Support Interrupt uplink (Since hardware version v1.2)
87
88 == 1.4 Applications ==
89
90 * Smart Buildings & Home Automation
91 * Logistics and Supply Chain Management
92 * Smart Metering
93 * Smart Agriculture
94 * Smart Cities
95 * Smart Factory
96
97 == 1.5 Firmware Change log ==
98
99 [[RS485-LN Image files – Download link and Change log>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/]]
100
101 == 1.6 Hardware Change log ==
102
103 (((
104 (((
105 v1.2: Add External Interrupt Pin.
106
107 v1.0: Release
108 )))
109 )))
110
111 = 2. Power ON Device =
112
113 (((
114 The RS485-LN can be powered by 7 ~~ 24V DC power source. Connection as below
115
116 * Power Source VIN to RS485-LN VIN+
117 * Power Source GND to RS485-LN VIN-
118
119 (((
120 Once there is power, the RS485-LN will be on.
121 )))
122
123 [[image:1653268091319-405.png]]
124 )))
125
126 = 3. Operation Mode =
127
128 == 3.1 How it works? ==
129
130 (((
131 The RS485-LN is configured as LoRaWAN OTAA Class C mode by default. It has OTAA keys to join network. To connect a local LoRaWAN network, user just need to input the OTAA keys in the network server and power on the RS485-LN. It will auto join the network via OTAA.
132 )))
133
134 == 3.2 Example to join LoRaWAN network ==
135
136 Here shows an example for how to join the TTN V3 Network. Below is the network structure, we use [[LG308>>url:http://www.dragino.com/products/lora-lorawan-gateway/item/140-lg308.html]] as LoRaWAN gateway here. 
137
138 [[image:1653268155545-638.png||height="334" width="724"]]
139
140 (((
141 The RS485-LN in this example connected to two RS485 devices for demonstration, user can connect to other RS485 devices via the same method. The connection is as below:
142
143 485A+ and 485B- of the sensor are connected to RS485A and RA485B of RS485-LN respectively.
144
145 [[image:1653268227651-549.png||height="592" width="720"]]
146
147 (((
148 The LG308 is already set to connect to [[TTN V3 network >>path:eu1.cloud.thethings.network/]]. So what we need to now is only configure the TTN V3:
149 )))
150
151 (((
152 **Step 1**: Create a device in TTN V3 with the OTAA keys from RS485-LN.
153 )))
154
155 (((
156 Each RS485-LN is shipped with a sticker with unique device EUI:
157 )))
158 )))
159
160 [[image:1652953462722-299.png]]
161
162 (((
163 (((
164 User can enter this key in their LoRaWAN Server portal. Below is TTN V3 screen shot:
165 )))
166
167 (((
168 Add APP EUI in the application.
169 )))
170 )))
171
172 [[image:image-20220519174512-1.png]]
173
174 [[image:image-20220519174512-2.png||height="323" width="720"]]
175
176 [[image:image-20220519174512-3.png||height="556" width="724"]]
177
178 [[image:image-20220519174512-4.png]]
179
180 You can also choose to create the device manually.
181
182 [[image:1652953542269-423.png||height="710" width="723"]]
183
184 Add APP KEY and DEV EUI
185
186 [[image:1652953553383-907.png||height="514" width="724"]]
187
188
189 (((
190 **Step 2**: Power on RS485-LN and it will auto join to the TTN V3 network. After join success, it will start to upload message to TTN V3 and user can see in the panel.
191 )))
192
193 [[image:1652953568895-172.png||height="232" width="724"]]
194
195 == 3.3 Configure Commands to read data ==
196
197 (((
198 (((
199 There are plenty of RS485 devices in the market and each device has different command to read the valid data. To support these devices in flexible, RS485-LN supports flexible command set. User can use [[AT Commands>>path:#AT_COMMAND]] or LoRaWAN Downlink Command to configure what commands RS485-LN should send for each sampling and how to handle the return from RS485 devices.
200 )))
201
202 (((
203 (% style="color:red" %)Note: below description and commands are for firmware version >v1.1, if you have firmware version v1.0. Please check the [[user manual v1.0>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/&file=RS485-LN_UserManual_v1.0.1.pdf]] or upgrade the firmware to v1.1
204 )))
205 )))
206
207 === 3.3.1 onfigure UART settings for RS485 or TTL communication ===
208
209 To use RS485-LN to read data from RS485 sensors, connect the RS485-LN A/B traces to the sensors. And user need to make sure RS485-LN use the match UART setting to access the sensors. The related commands for UART settings are:
210
211 (% border="1" style="background-color:#ffffcc; color:green; width:795px" %)
212 |(((
213 **AT Commands**
214 )))|(% style="width:285px" %)(((
215 **Description**
216 )))|(% style="width:347px" %)(((
217 **Example**
218 )))
219 |(((
220 AT+BAUDR
221 )))|(% style="width:285px" %)(((
222 Set the baud rate (for RS485 connection). Default Value is: 9600.
223 )))|(% style="width:347px" %)(((
224 (((
225 AT+BAUDR=9600
226 )))
227
228 (((
229 Options: (1200,2400,4800,14400,19200,115200)
230 )))
231 )))
232 |(((
233 AT+PARITY
234 )))|(% style="width:285px" %)(((
235 Set UART parity (for RS485 connection)
236 )))|(% style="width:347px" %)(((
237 (((
238 AT+PARITY=0
239 )))
240
241 (((
242 Option: 0: no parity, 1: odd parity, 2: even parity
243 )))
244 )))
245 |(((
246 AT+STOPBIT
247 )))|(% style="width:285px" %)(((
248 (((
249 Set serial stopbit (for RS485 connection)
250 )))
251
252 (((
253
254 )))
255 )))|(% style="width:347px" %)(((
256 (((
257 AT+STOPBIT=0 for 1bit
258 )))
259
260 (((
261 AT+STOPBIT=1 for 1.5 bit
262 )))
263
264 (((
265 AT+STOPBIT=2 for 2 bits
266 )))
267 )))
268
269 === 3.3.2 Configure sensors ===
270
271 (((
272 Some sensors might need to configure before normal operation. User can configure such sensor via PC or through RS485-BL AT Commands (% style="color:#4f81bd" %)**AT+CFGDEV**.
273 )))
274
275 (((
276 When user issue an (% style="color:#4f81bd" %)**AT+CFGDEV**(%%) command, Each (% style="color:#4f81bd" %)**AT+CFGDEV**(%%) equals to send a command to the RS485 or TTL sensors. This command will only run when user input it and won’t run during each sampling.
277 )))
278
279 (% border="1" style="background-color:#ffffcc; color:green; width:806px" %)
280 |**AT Commands**|(% style="width:418px" %)**Description**|(% style="width:256px" %)**Example**
281 |AT+CFGDEV|(% style="width:418px" %)(((
282 This command is used to configure the RS485/TTL devices; they won’t be used during sampling.
283
284 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,
285
286 mm: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command
287 )))|(% style="width:256px" %)AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
288
289 Detail of AT+CFGDEV command see [[AT+CFGDEV detail>>path:#AT_CFGDEV]].
290
291 === 3.3.3 Configure read commands for each sampling ===
292
293 (((
294 RS485-BL is a battery powered device; it will sleep most of time. And wake up on each period and read RS485 / TTL sensor data and uplink.
295 )))
296
297 (((
298 During each sampling, we need to confirm what commands we need to send to the sensors to read data. After the RS485/TTL sensors send back the value, it normally includes some bytes and we only need a few from them for a shorten payload.
299 )))
300
301 (((
302 To save the LoRaWAN network bandwidth, we might need to read data from different sensors and combine their valid value into a short payload.
303 )))
304
305 (((
306 This section describes how to achieve above goals.
307 )))
308
309 (((
310 During each sampling, the RS485-BL can support 15 commands to read sensors. And combine the return to one or several uplink payloads.
311 )))
312
313 (((
314 **Command from RS485-BL to Sensor:**
315 )))
316
317 (((
318 RS485-BL can send out pre-set max 15 strings via **AT+COMMAD1**, **ATCOMMAND2**,…, to **AT+COMMANDF** . All commands are of same grammar.
319 )))
320
321 (((
322 **Handle return from sensors to RS485-BL**:
323 )))
324
325 (((
326 After RS485-BL send out a string to sensor, RS485-BL will wait for the return from RS485 or TTL sensor. And user can specify how to handle the return, by **AT+DATACUT or AT+SEARCH commands**
327 )))
328
329 * (((
330 **AT+DATACUT**
331 )))
332
333 (((
334 When the return value from sensor have fix length and we know which position the valid value we should get, we can use AT+DATACUT command.
335 )))
336
337 * (((
338 **AT+SEARCH**
339 )))
340
341 (((
342 When the return value from sensor is dynamic length and we are not sure which bytes the valid data is, instead, we know what value the valid value following. We can use AT+SEARCH to search the valid value in the return string.
343 )))
344
345 (((
346 **Define wait timeout:**
347 )))
348
349 (((
350 Some RS485 device might has longer delay on reply, so user can use AT+CMDDL to set the timeout for getting reply after the RS485 command is sent. For example, AT+CMDDL1=1000 to send the open time to 1000ms
351 )))
352
353 (((
354 After we got the valid value from each RS485 commands, we need to combine them together with the command **AT+DATAUP**.
355 )))
356
357 **Examples:**
358
359 Below are examples for the how above AT Commands works.
360
361 **AT+COMMANDx : **This command will be sent to RS485/TTL devices during each sampling, Max command length is 14 bytes. The grammar is:
362
363 (% border="1" class="table-bordered" %)
364 |(((
365 **AT+COMMANDx=xx xx xx xx xx xx xx xx xx xx xx xx,m**
366
367 **xx xx xx xx xx xx xx xx xx xx xx xx: The RS485 command to be sent**
368
369 **m: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command**
370 )))
371
372 For example, if we have a RS485 sensor. The command to get sensor value is: 01 03 0B B8 00 02 46 0A. Where 01 03 0B B8 00 02 is the Modbus command to read the register 0B B8 where stored the sensor value. The 46 0A is the CRC-16/MODBUS which calculate manually.
373
374 In the RS485-BL, we should use this command AT+COMMAND1=01 03 0B B8 00 02,1 for the same.
375
376 **AT+SEARCHx**: This command defines how to handle the return from AT+COMMANDx.
377
378 (% border="1" class="table-bordered" %)
379 |(((
380 **AT+SEARCHx=aa,xx xx xx xx xx**
381
382 * **aa: 1: prefix match mode; 2: prefix and suffix match mode**
383 * **xx xx xx xx xx: match string. Max 5 bytes for prefix and 5 bytes for suffix**
384
385
386 )))
387
388 Examples:
389
390 1. For a return string from AT+COMMAND1: 16 0c 1e 56 34 2e 30 58 5f 36 41 30 31 00 49
391
392 If we set AT+SEARCH1=1,1E 56 34.      (max 5 bytes for prefix)
393
394 The valid data will be all bytes after 1E 56 34 , so it is 2e 30 58 5f 36 41 30 31 00 49
395
396 [[image:1652954654347-831.png]]
397
398
399 1. For a return string from AT+COMMAND1:  16 0c 1e 56 34 2e 30 58 5f 36 41 30 31 00 49
400
401 If we set AT+SEARCH1=2, 1E 56 34+31 00 49
402
403 Device will search the bytes between 1E 56 34 and 31 00 49. So it is 2e 30 58 5f 36 41 30
404
405 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image014.png]]
406
407
408 **AT+DATACUTx : **This command defines how to handle the return from AT+COMMANDx, max return length is 45 bytes.
409
410 |(((
411 **AT+DATACUTx=a,b,c**
412
413 * **a: length for the return of AT+COMMAND**
414 * **b:1: grab valid value by byte, max 6 bytes. 2: grab valid value by bytes section, max 3 sections.**
415 * **c: define the position for valid value.  **
416 )))
417
418 Examples:
419
420 * Grab bytes:
421
422 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image015.png]]
423
424 * Grab a section.
425
426 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image016.png]]
427
428 * Grab different sections.
429
430 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image017.png]]
431
432
433 Note:
434
435 AT+SEARCHx and AT+DATACUTx can be used together, if both commands are set, RS485-BL will first process AT+SEARCHx on the return string and get a temporary string, and then process AT+DATACUTx on this temporary string to get the final payload. In this case, AT+DATACUTx need to set to format AT+DATACUTx=0,xx,xx where the return bytes set to 0.
436
437 Example:
438
439 AT+COMMAND1=11 01 1E D0,0
440
441 AT+SEARCH1=1,1E 56 34
442
443 AT+DATACUT1=0,2,1~~5
444
445 Return string from AT+COMMAND1: 16 0c 1e 56 34 2e 30 58 5f 36 41 30 31 00 49
446
447 String after SEARCH command: 2e 30 58 5f 36 41 30 31 00 49
448
449 Valid payload after DataCUT command: 2e 30 58 5f 36
450
451 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image018.png]]
452
453
454
455
456 1.
457 11.
458 111. Compose the uplink payload
459
460 Through AT+COMMANDx and AT+DATACUTx we got valid value from each RS485 commands, Assume these valid value are RETURN1, RETURN2, .., to RETURNx. The next step is how to compose the LoRa Uplink Payload by these RETURNs. The command is **AT+DATAUP.**
461
462
463 **Examples: AT+DATAUP=0**
464
465 Compose the uplink payload with value returns in sequence and send with **A SIGNLE UPLINK**.
466
467 Final Payload is
468
469 Battery Info+PAYVER + VALID Value from RETURN1 + Valid Value from RETURN2 + … + RETURNx
470
471 Where PAYVER is defined by AT+PAYVER, below is an example screen shot.
472
473 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image019.png]]
474
475
476
477 **Examples: AT+DATAUP=1**
478
479 Compose the uplink payload with value returns in sequence and send with **Multiply UPLINKs**.
480
481 Final Payload is
482
483 Battery Info+PAYVER + PAYLOAD COUNT + PAYLOAD# + DATA
484
485 1. Battery Info (2 bytes): Battery voltage
486 1. PAYVER (1 byte): Defined by AT+PAYVER
487 1. PAYLOAD COUNT (1 byte): Total how many uplinks of this sampling.
488 1. PAYLOAD# (1 byte): Number of this uplink. (from 0,1,2,3…,to PAYLOAD COUNT)
489 1. DATA: Valid value: max 6 bytes(US915 version here, [[Notice*!>>path:#max_byte]]) for each uplink so each uplink <= 11 bytes. For the last uplink, DATA will might less than 6 bytes
490
491 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image020.png]]
492
493
494 So totally there will be 3 uplinks for this sampling, each uplink includes 6 bytes DATA
495
496 DATA1=RETURN1 Valid Value = 20 20 0a 33 90 41
497
498 DATA2=1^^st^^ ~~ 6^^th^^ byte of Valid value of RETURN10= 02 aa 05 81 0a 20
499
500 DATA3=7^^th^^ ~~ 11^^th^^ bytes of Valid value of RETURN10 = 20 20 20 2d 30
501
502
503
504 Below are the uplink payloads:
505
506 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image021.png]]
507
508
509 Notice: the Max bytes is according to the max support bytes in different Frequency Bands for lowest SF. As below:
510
511 ~* For AU915/AS923 bands, if UplinkDwell time=0, max 51 bytes for each uplink ( so 51 -5 = 46 max valid date)
512
513 * For AU915/AS923 bands, if UplinkDwell time=1, max 11 bytes for each uplink ( so 11 -5 = 6 max valid date).
514
515 * For US915 band, max 11 bytes for each uplink ( so 11 -5 = 6 max valid date).
516
517 ~* For all other bands: max 51 bytes for each uplink  ( so 51 -5 = 46 max valid date).
518
519
520
521 1.
522 11.
523 111. Uplink on demand
524
525 Except uplink periodically, RS485-BL is able to uplink on demand. The server sends downlink command to RS485-BL and RS485 will uplink data base on the command.
526
527 Downlink control command:
528
529 [[0x08 command>>path:#downlink_08]]: Poll an uplink with current command set in RS485-BL.
530
531 [[0xA8 command>>path:#downlink_A8]]: Send a command to RS485-BL and uplink the output from sensors.
532
533
534
535 1.
536 11.
537 111. Uplink on Interrupt
538
539 Put the interrupt sensor between 3.3v_out and GPIO ext.[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image022.png]]
540
541 AT+INTMOD=0  Disable Interrupt
542
543 AT+INTMOD=1  Interrupt trigger by rising or falling edge.
544
545 AT+INTMOD=2  Interrupt trigger by falling edge. ( Default Value)
546
547 AT+INTMOD=3  Interrupt trigger by rising edge.
548
549
550 1.
551 11. Uplink Payload
552
553 |**Size(bytes)**|**2**|**1**|**Length depends on the return from the commands**
554 |Value|(((
555 Battery(mV)
556
557 &
558
559 Interrupt _Flag
560 )))|(((
561 PAYLOAD_VER
562
563
564 )))|If the valid payload is too long and exceed the maximum support payload length in server, server will show payload not provided in the LoRaWAN server.
565
566 Below is the decoder for the first 3 bytes. The rest bytes are dynamic depends on different RS485 sensors.
567
568
569 function Decoder(bytes, port) {
570
571 ~/~/Payload Formats of RS485-BL Deceive
572
573 return {
574
575 ~/~/Battery,units:V
576
577 BatV:((bytes[0]<<8 | bytes[1])&0x7fff)/1000,
578
579 ~/~/GPIO_EXTI 
580
581 EXTI_Trigger:(bytes[0] & 0x80)? "TRUE":"FALSE",
582
583 ~/~/payload of version
584
585 Pay_ver:bytes[2],
586
587 };
588
589 }
590
591
592
593
594
595
596
597 TTN V3 uplink screen shot.
598
599 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
600
601 1.
602 11. Configure RS485-BL via AT or Downlink
603
604 User can configure RS485-BL via [[AT Commands >>path:#_​Using_the_AT]]or LoRaWAN Downlink Commands
605
606 There are two kinds of Commands:
607
608 * **Common Commands**: They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: http:~/~/wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands
609
610 * **Sensor Related Commands**: These commands are special designed for RS485-BL.  User can see these commands below:
611
612 1.
613 11.
614 111. Common Commands:
615
616 They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[http:~~/~~/wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands>>url:http://wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands]]
617
618
619 1.
620 11.
621 111. Sensor related commands:
622
623 ==== Choose Device Type (RS485 or TTL) ====
624
625 RS485-BL can connect to either RS485 sensors or TTL sensor. User need to specify what type of sensor need to connect.
626
627 * AT Command
628
629 **AT+MOD=1** ~/~/ Set to support RS485-MODBUS type sensors. User can connect multiply RS485 , Modbus sensors to the A / B pins.
630
631 **AT+MOD=2** ~/~/ Set to support TTL Level sensors, User can connect one TTL Sensor to the TXD/RXD/GND pins.
632
633
634 * Downlink Payload
635
636 **0A aa**     à same as AT+MOD=aa
637
638
639
640 ==== [[RS485 Debug Command>>path:#downlink_A8]] (AT+CFGDEV) ====
641
642 This command is used to configure the RS485 or TTL sensors; they won’t be used during sampling.
643
644 * AT Command
645
646 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
647
648 m: 0: no CRC; 1: add CRC-16/MODBUS in the end of this command.
649
650
651
652 * Downlink Payload
653
654 Format: A8 MM NN XX XX XX XX YY
655
656 Where:
657
658 * MM: 1: add CRC-16/MODBUS ; 0: no CRC
659 * NN: The length of RS485 command
660 * XX XX XX XX: RS485 command total NN bytes
661 * YY: How many bytes will be uplink from the return of this RS485 command, if YY=0, RS485-BL will execute the downlink command without uplink; if YY>0, RS485-BL will uplink total YY bytes from the output of this RS485 command
662
663 **Example 1:**
664
665 To connect a Modbus Alarm with below commands.
666
667 * The command to active alarm is: 0A 05 00 04 00 01 4C B0. Where 0A 05 00 04 00 01 is the Modbus command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which calculate manually.
668
669 * The command to deactivate alarm is: 0A 05 00 04 00 00 8D 70. Where 0A 05 00 04 00 00 is the Modbus command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which calculate manually.
670
671 So if user want to use downlink command to control to RS485 Alarm, he can use:
672
673 **A8 01 06 0A 05 00 04 00 01 00**: to activate the RS485 Alarm
674
675 **A8 01 06 0A 05 00 04 00 00 00**: to deactivate the RS485 Alarm
676
677 A8 is type code and 01 means add CRC-16/MODBUS at the end, the 3^^rd^^ byte is 06, means the next 6 bytes are the command to be sent to the RS485 network, the final byte 00 means this command don’t need to acquire output.
678
679
680 **Example 2:**
681
682 Check TTL Sensor return:
683
684 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image024.png]]
685
686
687
688
689 ==== Set Payload version ====
690
691 This is the first byte of the uplink payload. RS485-BL can connect to different sensors. User can set the PAYVER field to tell server how to decode the current payload.
692
693 * AT Command:
694
695 AT+PAYVER: Set PAYVER field = 1
696
697
698 * Downlink Payload:
699
700 0xAE 01   à Set PAYVER field =  0x01
701
702 0xAE 0F   à Set PAYVER field =  0x0F
703
704
705 ==== Set RS485 Sampling Commands ====
706
707 AT+COMMANDx, AT+DATACUTx and AT+SEARCHx
708
709 These three commands are used to configure how the RS485-BL polling data from Modbus device. Detail of usage please see : [[polling RS485 device>>path:#polling_485]].
710
711
712 * AT Command:
713
714 AT+COMMANDx: Configure RS485 read command to sensor.
715
716 AT+DATACUTx: Configure how to handle return from RS485 devices.
717
718 AT+SEARCHx: Configure search command
719
720
721 * Downlink Payload:
722
723 0xAF downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
724
725 Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
726
727 Format: AF MM NN LL XX XX XX XX YY
728
729 Where:
730
731 * MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
732 * NN: 0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
733 * LL: The length of AT+COMMAND or AT+DATACUT command
734 * XX XX XX XX: AT+COMMAND or AT+DATACUT command
735 * YY: If YY=0, RS485-BL will execute the downlink command without uplink; if YY=1, RS485-BL will execute an uplink after got this command.
736
737 Example:
738
739 **AF 03 01 06 0A 05 00 04 00 01 00**: Same as AT+COMMAND3=0A 05 00 04 00 01,1
740
741 **AF 03 02 06 10 01 05 06 09 0A 00**: Same as AT+DATACUT3=**16**,**1**,**5+6+9+10**
742
743 **AF 03 02 06 0B 02 05 07 08 0A 00**: Same as AT+DATACUT3=**11**,**2**,**5~~7+8~~10**
744
745
746 0xAB downlink command can be used for set AT+SEARCHx
747
748 Example: **AB aa 01 03 xx xx xx** (03 here means there are total 3 bytes after 03) So
749
750 * AB aa 01 03 xx xx xx  same as AT+SEARCHaa=1,xx xx xx
751 * AB aa 02 03 xx xx xx 02 yy yy(03 means there are 3 bytes after 03, they are xx xx xx;02 means there are 2 bytes after 02, they are yy yy) so the commands
752
753 **AB aa 02 03 xx xx xx 02 yy yy**  same as **AT+SEARCHaa=2,xx xx xx+yy yy**
754
755
756 ==== Fast command to handle MODBUS device ====
757
758 AT+MBFUN is valid since v1.3 firmware version. The command is for fast configure to read Modbus devices. It is only valid for the devices which follow the [[MODBUS-RTU protocol>>url:https://www.modbustools.com/modbus.html]].
759
760 This command is valid since v1.3 firmware version
761
762
763 AT+MBFUN has only two value:
764
765 * AT+MBFUN=1: Enable Modbus reading. And get response base on the MODBUS return
766
767 AT+MBFUN=1, device can auto read the Modbus function code: 01, 02, 03 or 04. AT+MBFUN has lower priority vs AT+DATACUT command. If AT+DATACUT command is configured, AT+MBFUN will be ignore.
768
769 * AT+MBFUN=0: Disable Modbus fast reading.
770
771 Example:
772
773 * AT+MBFUN=1 and AT+DATACUT1/AT+DATACUT2 are not configure (0,0,0).
774 * AT+COMMAND1= 01 03 00 10 00 08,1 ~-~-> read slave address 01 , function code 03, start address 00 01, quantity of registers 00 08.
775 * AT+COMMAND2= 01 02 00 40 00 10,1 ~-~-> read slave address 01 , function code 02, start address 00 40, quantity of inputs 00 10.
776
777 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image025.png]]
778
779
780 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image026.png]]
781
782
783 * Downlink Commands:
784
785 A9 aa -à Same as AT+MBFUN=aa
786
787
788 ==== RS485 command timeout ====
789
790 Some Modbus device has slow action to send replies. This command is used to configure the RS485-BL to use longer time to wait for their action.
791
792 Default value: 0, range:  0 ~~ 5 seconds
793
794
795 * AT Command:
796
797 AT+CMDDLaa=hex(bb cc)
798
799 Example:
800
801 **AT+CMDDL1=1000** to send the open time to 1000ms
802
803
804 * Downlink Payload:
805
806 0x AA aa bb cc
807
808 Same as: AT+CMDDLaa=hex(bb cc)
809
810 Example:
811
812 0xAA 01 03 E8  à Same as **AT+CMDDL1=1000 ms**
813
814
815 ==== [[Uplink>>path:#downlink_A8]] payload mode ====
816
817 Define to use one uplink or multiple uplinks for the sampling.
818
819 The use of this command please see: [[Compose Uplink payload>>path:#DataUP]]
820
821 * AT Command:
822
823 AT+DATAUP=0
824
825 AT+DATAUP=1
826
827
828 * Downlink Payload:
829
830 0xAD 00   à Same as AT+DATAUP=0
831
832 0xAD 01   à Same as AT+DATAUP=1
833
834
835 ==== Manually trigger an Uplink ====
836
837 Ask device to send an uplink immediately.
838
839 * Downlink Payload:
840
841 0x08 FF, RS485-BL will immediately send an uplink.
842
843
844 ==== Clear RS485 Command ====
845
846 The AT+COMMANDx and AT+DATACUTx settings are stored in special location, user can use below command to clear them.
847
848
849 * AT Command:
850
851 **AT+CMDEAR=mm,nn**   mm: start position of erase ,nn: stop position of erase
852
853 Etc. AT+CMDEAR=1,10 means erase AT+COMMAND1/AT+DATACUT1 to AT+COMMAND10/AT+DATACUT10
854
855 Example screen shot after clear all RS485 commands. 
856
857
858
859 The uplink screen shot is:
860
861 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
862
863
864 * Downlink Payload:
865
866 0x09 aa bb same as AT+CMDEAR=aa,bb
867
868
869 ==== Set Serial Communication Parameters ====
870
871 Set the Rs485 serial communication parameters:
872
873 * AT Command:
874
875 Set Baud Rate:
876
877 AT+BAUDR=9600    ~/~/ Options: (1200,2400,4800,14400,19200,115200)
878
879
880 Set UART parity
881
882 AT+PARITY=0    ~/~/ Option: 0: no parity, 1: odd parity, 2: even parity
883
884
885 Set STOPBIT
886
887 AT+STOPBIT=0    ~/~/ Option: 0 for 1bit; 1 for 1.5 bit ; 2 for 2 bits
888
889
890 * Downlink Payload:
891
892 A7 01 aa bb: Same  AT+BAUDR=hex(aa bb)*100
893
894 Example:
895
896 * A7 01 00 60   same as AT+BAUDR=9600
897 * A7 01 04 80  same as AT+BAUDR=115200
898
899 A7 02 aa: Same as  AT+PARITY=aa  (aa value: 00 , 01 or 02)
900
901 A7 03 aa: Same as  AT+STOPBIT=aa  (aa value: 00 , 01 or 02)
902
903
904 ==== Control output power duration ====
905
906 User can set the output power duration before each sampling.
907
908 * AT Command:
909
910 Example:
911
912 AT+3V3T=1000 ~/~/ 3V3 output power will open 1s before each sampling.
913
914 AT+5VT=1000 ~/~/ +5V output power will open 1s before each sampling.
915
916
917 * LoRaWAN Downlink Command:
918
919 07 01 aa bb  Same as AT+5VT=(aa bb)
920
921 07 02 aa bb  Same as AT+3V3T=(aa bb)
922
923
924
925
926 1.
927 11. Buttons
928
929 |**Button**|**Feature**
930 |**RST**|Reboot RS485-BL
931
932 1.
933 11. +3V3 Output
934
935 RS485-BL has a Controllable +3V3 output, user can use this output to power external sensor.
936
937 The +3V3 output will be valid for every sampling. RS485-BL will enable +3V3 output before all sampling and disable the +3V3 after all sampling. 
938
939
940 The +3V3 output time can be controlled by AT Command.
941
942 **AT+3V3T=1000**
943
944 Means set +3v3 valid time to have 1000ms. So, the real +3v3 output will actually have 1000ms + sampling time for other sensors.
945
946
947 By default, the AT+3V3T=0. This is a special case, means the +3V3 output is always on at any time
948
949
950 1.
951 11. +5V Output
952
953 RS485-BL has a Controllable +5V output, user can use this output to power external sensor.
954
955 The +5V output will be valid for every sampling. RS485-BL will enable +5V output before all sampling and disable the +5v after all sampling. 
956
957
958 The 5V output time can be controlled by AT Command.
959
960 **AT+5VT=1000**
961
962 Means set 5V valid time to have 1000ms. So, the real 5V output will actually have 1000ms + sampling time for other sensors.
963
964
965 By default, the AT+5VT=0. If the external sensor which require 5v and require more time to get stable state, user can use this command to increase the power ON duration for this sensor.
966
967
968
969
970 1.
971 11. LEDs
972
973 |**LEDs**|**Feature**
974 |**LED1**|Blink when device transmit a packet.
975
976 1.
977 11. Switch Jumper
978
979 |**Switch Jumper**|**Feature**
980 |**SW1**|(((
981 ISP position: Upgrade firmware via UART
982
983 Flash position: Configure device, check running status.
984 )))
985 |**SW2**|(((
986 5V position: set to compatible with 5v I/O.
987
988 3.3v position: set to compatible with 3.3v I/O.,
989 )))
990
991 +3.3V: is always ON
992
993 +5V: Only open before every sampling. The time is by default, it is AT+5VT=0.  Max open time. 5000 ms.
994
995 1. Case Study
996
997 User can check this URL for some case studies.
998
999 [[http:~~/~~/wiki.dragino.com/index.php?title=APP_RS485_COMMUNICATE_WITH_SENSORS>>url:http://wiki.dragino.com/index.php?title=APP_RS485_COMMUNICATE_WITH_SENSORS]]
1000
1001
1002
1003
1004 1. Use AT Command
1005 11. Access AT Command
1006
1007 RS485-BL supports AT Command set. User can use a USB to TTL adapter plus the 3.5mm Program Cable to connect to RS485-BL to use AT command, as below.
1008
1009 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image027.png]]
1010
1011
1012 In PC, User needs to set **serial tool**(such as [[putty>>url:https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to **9600** to access to access serial console of RS485-BL. The default password is 123456. Below is the output for reference:
1013
1014 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image028.png]]
1015
1016
1017
1018 More detail AT Command manual can be found at [[AT Command Manual>>path:#AT_COMMAND]]
1019
1020
1021
1022 1.
1023 11. Common AT Command Sequence
1024 111. Multi-channel ABP mode (Use with SX1301/LG308)
1025
1026 If device has not joined network yet:
1027
1028 AT+FDR
1029
1030 AT+NJM=0
1031
1032 ATZ
1033
1034
1035 If device already joined network:
1036
1037 AT+NJM=0
1038
1039 ATZ
1040
1041 1.
1042 11.
1043 111. Single-channel ABP mode (Use with LG01/LG02)
1044
1045 AT+FDR   Reset Parameters to Factory Default, Keys Reserve
1046
1047 AT+NJM=0 Set to ABP mode
1048
1049 AT+ADR=0 Set the Adaptive Data Rate Off
1050
1051 AT+DR=5  Set Data Rate
1052
1053 AT+TDC=60000  Set transmit interval to 60 seconds
1054
1055 AT+CHS=868400000 Set transmit frequency to 868.4Mhz
1056
1057 AT+RX2FQ=868400000 Set RX2Frequency to 868.4Mhz (according to the result from server)
1058
1059 AT+RX2DR=5  Set RX2DR to match the downlink DR from server. see below
1060
1061 AT+DADDR=26 01 1A F1 Set Device Address to 26 01 1A F1, this ID can be found in the LoRa Server portal.
1062
1063 ATZ          Reset MCU
1064
1065 **Note:**
1066
1067 1. Make sure the device is set to ABP mode in the IoT Server.
1068 1. Make sure the LG01/02 gateway RX frequency is exactly the same as AT+CHS setting.
1069 1. Make sure SF / bandwidth setting in LG01/LG02 match the settings of AT+DR. refer [[this link>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_Gateway/&file=LoRaWAN%201.0.3%20Regional%20Parameters.xlsx]] to see what DR means.
1070 1. The command AT+RX2FQ and AT+RX2DR is to let downlink work. to set the correct parameters, user can check the actually downlink parameters to be used. As below. Which shows the RX2FQ should use 868400000 and RX2DR should be 5
1071
1072 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image029.png]]
1073
1074
1075 1. FAQ
1076 11. How to upgrade the image?
1077
1078 The RS485-BL LoRaWAN Controller is shipped with a 3.5mm cable, the cable is used to upload image to RS485-BL to:
1079
1080 * Support new features
1081 * For bug fix
1082 * Change LoRaWAN bands.
1083
1084 Below shows the hardware connection for how to upload an image to RS485-BL:
1085
1086 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image030.png]]
1087
1088 **Step1:** Download [[flash loader>>url:https://www.st.com/content/st_com/en/products/development-tools/software-development-tools/stm32-software-development-tools/stm32-programmers/flasher-stm32.html]].
1089
1090 **Step2**: Download the [[LT Image files>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/image/]].
1091
1092 **Step3: **Open flashloader; choose the correct COM port to update.
1093
1094
1095 |(((
1096 HOLD PRO then press the RST button, SYS will be ON, then click next
1097 )))
1098
1099 |(((
1100 Board detected
1101 )))
1102
1103 |(((
1104
1105 )))
1106
1107 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image031.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image032.png]]
1108
1109
1110
1111 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image033.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image034.png]]
1112
1113
1114 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image035.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image036.png]]
1115
1116
1117 1.
1118 11. How to change the LoRa Frequency Bands/Region?
1119
1120 User can follow the introduction for [[how to upgrade image>>path:#upgrade_image]]. When download the images, choose the required image file for download.
1121
1122
1123
1124 1.
1125 11. How many RS485-Slave can RS485-BL connects?
1126
1127 The RS485-BL can support max 32 RS485 devices. Each uplink command of RS485-BL can support max 16 different RS485 command. So RS485-BL can support max 16 RS485 devices pre-program in the device for uplink. For other devices no pre-program, user can use the [[downlink message (type code 0xA8) to poll their info>>path:#downlink_A8]].
1128
1129
1130
1131
1132 1. Trouble Shooting     
1133 11. Downlink doesn’t work, how to solve it?
1134
1135 Please see this link for debug:
1136
1137 [[http:~~/~~/wiki.dragino.com/index.php?title=Main_Page#LoRaWAN_Communication_Debug>>url:http://wiki.dragino.com/index.php?title=Main_Page#LoRaWAN_Communication_Debug]] 
1138
1139
1140
1141 1.
1142 11. Why I can’t join TTN V3 in US915 /AU915 bands?
1143
1144 It might about the channels mapping. Please see for detail.
1145
1146 [[http:~~/~~/wiki.dragino.com/index.php?title=LoRaWAN_Communication_Debug#Notice_of_US915.2FCN470.2FAU915_Frequency_band>>url:http://wiki.dragino.com/index.php?title=LoRaWAN_Communication_Debug#Notice_of_US915.2FCN470.2FAU915_Frequency_band]]
1147
1148
1149
1150 1. Order Info
1151
1152 **Part Number: RS485-BL-XXX**
1153
1154 **XXX:**
1155
1156 * **EU433**: frequency bands EU433
1157 * **EU868**: frequency bands EU868
1158 * **KR920**: frequency bands KR920
1159 * **CN470**: frequency bands CN470
1160 * **AS923**: frequency bands AS923
1161 * **AU915**: frequency bands AU915
1162 * **US915**: frequency bands US915
1163 * **IN865**: frequency bands IN865
1164 * **RU864**: frequency bands RU864
1165 * **KZ865: **frequency bands KZ865
1166
1167 1. Packing Info
1168
1169 **Package Includes**:
1170
1171 * RS485-BL x 1
1172 * Stick Antenna for LoRa RF part x 1
1173 * Program cable x 1
1174
1175 **Dimension and weight**:
1176
1177 * Device Size: 13.5 x 7 x 3 cm
1178 * Device Weight: 105g
1179 * Package Size / pcs : 14.5 x 8 x 5 cm
1180 * Weight / pcs : 170g
1181
1182 1. Support
1183
1184 * Support is provided Monday to Friday, from 09:00 to 18:00 GMT+8. Due to different timezones we cannot offer live support. However, your questions will be answered as soon as possible in the before-mentioned schedule.
1185 * Provide as much information as possible regarding your enquiry (product models, accurately describe your problem and steps to replicate it etc) and send a mail to
1186
1187 [[support@dragino.com>>url:file:///D:/市场资料/说明书/LoRa/LT系列/support@dragino.com]]
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved