1678 1678  == 6.7 How to judge whether there is a problem with the set COMMAND ==
1679 1679  
1680 -=== Introduce: ===
1680 +=== 6.7.1 Introduce: ===
1681 1681  
1682 1682  
1683 1683  Users can use below the structure to fast debug the communication between RS485BL and RS485-LN. The principle is to put the PC in the RS485 network and sniff the packet between Modbus MTU and RS485-BL/LN. We can use this way to:
... ... @@ -1695,16 +1695,14 @@
1695 1695  [[image:image-20221130104310-2.png]]
1696 1696  
1697 1697  
1698 -=== Set up PC to monitor RS485 network ===
1698 +=== 6.7.2 Set up PC to monitor RS485 network With Serial tool ===
1699 1699  
1700 -=== With Serial tool ===
1701 -
1702 1702  Note: Receive and send set to hex mode
1703 1703  
1704 1704  [[image:image-20221130104310-3.png||height="616" width="714"]]
1705 1705  
1706 1706  
1707 -=== With ModRSsim2: ===
1705 +=== 6.7.3 With ModRSsim2: ===
1708 1708  
1709 1709  (1)Select serial port MODBUS RS-232
1710 1710  
... ... @@ -1724,10 +1724,12 @@
1724 1724  
1725 1725  [[image:image-20221130104310-7.png||height="376" width="835"]]
1726 1726  
1727 -=== Run RS485-LN/BL command and monitor if it is correct. ===
1725 +(% class="wikigeneratedid" id="HRunRS485-LN2FBLcommandandmonitorifitiscorrect." %)
1726 +Run RS485-LN/BL command and monitor if it is correct.
1728 1728  
1729 -=== Example – Test the CFGDEV command ===
1730 1730  
1729 +=== 6.7.4 Example – Test the CFGDEV command ===
1730 +
1731 1731  RS485-LN sent below command:
1732 1732  
1733 1733  AT+CFGDEV=01 03 20 00 01 85 c0,1 to RS485 network, and PC is able to get this command and return commands from MTU to show in the serial tool.
... ... @@ -1743,7 +1743,7 @@
1743 1743  
1744 1744  
1745 1745  
1746 -=== Example – Test CMD command sets. ===
1746 +=== 6.7.5 Example – Test CMD command sets. ===
1747 1747  
1748 1748  Run AT+SENSORVALUE=1 to test the CMD commands set in RS485-LN.
1749 1749  
... ... @@ -1758,7 +1758,7 @@
1758 1758  
1759 1759  
1760 1760  
1761 -=== Test with PC ===
1761 +=== 6.7.6 Test with PC ===
1762 1762  
1763 1763  If there is still have problem to set up correctly the commands between RS485-LN and MTU. User can test the correct RS485 command set in PC and compare with the RS485 command sent out via RS485-LN. as long as both commands are the same, the MTU should return correct result.
1764 1764  
... ... @@ -1775,6 +1775,7 @@
1775 1775  
1776 1776  [[image:image-20221130104310-14.png||height="371" width="823"]]
1777 1777  
1778 +
1778 1778  = 7. Trouble Shooting =