14
15 = 1.Introduction =
16
17 == 1.1 What is RS485-LN RS485 to LoRaWAN Converter ==
18
19 (((
20 (((
21 The Dragino RS485-LN is a (% style="color:blue" %)**RS485 to LoRaWAN Converter**(%%). It converts the RS485 signal into LoRaWAN wireless signal which simplify the IoT installation and reduce the installation/maintaining cost.
22 )))
23
24 (((
25 RS485-LN allows user to (% style="color:blue" %)**monitor / control RS485 devices**(%%) and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, smartphone detection, building automation, and so on.
26 )))
27
28 (((
29 (% style="color:blue" %)**For data uplink**(%%), RS485-LN sends user-defined commands to RS485 devices and gets the return from the RS485 devices. RS485-LN will process these returns according to user-define rules to get the final payload and upload to LoRaWAN server.
30 )))
31
32 (((
33 (% style="color:blue" %)**For data downlink**(%%), RS485-LN runs in LoRaWAN Class C. When there downlink commands from LoRaWAN server, RS485-LN will forward the commands from LoRaWAN server to RS485 devices.
34
35 (% style="color:blue" %)**Demo Dashboard for RS485-LN**(%%) connect to two energy meters: [[https:~~/~~/app.datacake.de/dashboard/d/58844a26-378d-4c5a-aaf5-b5b5b153447a>>url:https://app.datacake.de/dashboard/d/58844a26-378d-4c5a-aaf5-b5b5b153447a]]
36 )))
37 )))
38
39 [[image:1653267211009-519.png||height="419" width="724"]]
40
41
42 == 1.2 Specifications ==
43
44
45 **Hardware System:**
46
47 * STM32L072CZT6 MCU
48 * SX1276/78 Wireless Chip 
49 * Power Consumption (exclude RS485 device):
50 ** Idle: 32mA@12v
51 ** 20dB Transmit: 65mA@12v
52
53 **Interface for Model:**
54
55 * RS485
56 * Power Input 7~~ 24V DC. 
57
58 **LoRa Spec:**
59
60 * Frequency Range:
61 ** Band 1 (HF): 862 ~~ 1020 Mhz
62 ** Band 2 (LF): 410 ~~ 528 Mhz
63 * 168 dB maximum link budget.
64 * +20 dBm - 100 mW constant RF output vs.
65 * +14 dBm high efficiency PA.
66 * Programmable bit rate up to 300 kbps.
67 * High sensitivity: down to -148 dBm.
68 * Bullet-proof front end: IIP3 = -12.5 dBm.
69 * Excellent blocking immunity.
70 * Low RX current of 10.3 mA, 200 nA register retention.
71 * Fully integrated synthesizer with a resolution of 61 Hz.
72 * FSK, GFSK, MSK, GMSK, LoRaTM and OOK modulation.
73 * Built-in bit synchronizer for clock recovery.
74 * Preamble detection.
75 * 127 dB Dynamic Range RSSI.
76 * Automatic RF Sense and CAD with ultra-fast AFC.
77 * Packet engine up to 256 bytes with CRC.
78
79 == 1.3 Features ==
80
81 * LoRaWAN Class A & Class C protocol (default Class C)
82 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915/IN865/RU864
83 * AT Commands to change parameters
84 * Remote configure parameters via LoRa Downlink
85 * Firmware upgradable via program port
86 * Support multiply RS485 devices by flexible rules
87 * Support Modbus protocol
88 * Support Interrupt uplink (Since hardware version v1.2)
89
90 == 1.4 Applications ==
91
92 * Smart Buildings & Home Automation
93 * Logistics and Supply Chain Management
94 * Smart Metering
95 * Smart Agriculture
96 * Smart Cities
97 * Smart Factory
98
99 == 1.5 Firmware Change log ==
100
101 [[RS485-LN Image files – Download link and Change log>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/]]
102
103
104 == 1.6 Hardware Change log ==
105
106 (((
107 (((
108 v1.2: Add External Interrupt Pin.
109
110 v1.0: Release
111
112
113 )))
114 )))
115
116 = 2. Power ON Device =
117
118 (((
119 The RS485-LN can be powered by 7 ~~ 24V DC power source. Connection as below
120
121 * Power Source VIN to RS485-LN VIN+
122 * Power Source GND to RS485-LN VIN-
123
124 (((
125 Once there is power, the RS485-LN will be on.
126 )))
127
128 [[image:1653268091319-405.png]]
129
130
131 )))
132
133 = 3. Operation Mode =
134
135 == 3.1 How it works? ==
136
137 (((
138 The RS485-LN is configured as LoRaWAN OTAA Class C mode by default. It has OTAA keys to join network. To connect a local LoRaWAN network, user just need to input the OTAA keys in the network server and power on the RS485-LN. It will auto join the network via OTAA.
139
140
141 )))
142
143 == 3.2 Example to join LoRaWAN network ==
144
145 Here shows an example for how to join the TTN V3 Network. Below is the network structure, we use [[LG308>>url:http://www.dragino.com/products/lora-lorawan-gateway/item/140-lg308.html]] as LoRaWAN gateway here. 
146
147 [[image:1653268155545-638.png||height="334" width="724"]]
148
149
150 (((
151 (((
152 The RS485-LN in this example connected to two RS485 devices for demonstration, user can connect to other RS485 devices via the same method. The connection is as below:
153 )))
154
155 (((
156 485A+ and 485B- of the sensor are connected to RS485A and RA485B of RS485-LN respectively.
157 )))
158
159 [[image:1653268227651-549.png||height="592" width="720"]]
160
161 (((
162 The LG308 is already set to connect to [[TTN V3 network >>path:eu1.cloud.thethings.network/]]. So what we need to now is only configure the TTN V3:
163 )))
164
165 (((
166 **Step 1**: Create a device in TTN V3 with the OTAA keys from RS485-LN.
167 )))
168
169 (((
170 Each RS485-LN is shipped with a sticker with unique device EUI:
171 )))
172 )))
173
174 [[image:1652953462722-299.png]]
175
176 (((
177 (((
178 User can enter this key in their LoRaWAN Server portal. Below is TTN V3 screen shot:
179 )))
180
181 (((
182 Add APP EUI in the application.
183 )))
184 )))
185
186 [[image:image-20220519174512-1.png]]
187
188 [[image:image-20220519174512-2.png||height="323" width="720"]]
189
190 [[image:image-20220519174512-3.png||height="556" width="724"]]
191
192 [[image:image-20220519174512-4.png]]
193
194 You can also choose to create the device manually.
195
196 [[image:1652953542269-423.png||height="710" width="723"]]
197
198 Add APP KEY and DEV EUI
199
200 [[image:1652953553383-907.png||height="514" width="724"]]
201
202
203 (((
204 **Step 2**: Power on RS485-LN and it will auto join to the TTN V3 network. After join success, it will start to upload message to TTN V3 and user can see in the panel.
205 )))
206
207 [[image:1652953568895-172.png||height="232" width="724"]]
208
209
210 == 3.3 Configure Commands to read data ==
211
212 (((
213 (((
214 There are plenty of RS485 devices in the market and each device has different command to read the valid data. To support these devices in flexible, RS485-LN supports flexible command set. User can use [[AT Commands>>path:#AT_COMMAND]] or LoRaWAN Downlink Command to configure what commands RS485-LN should send for each sampling and how to handle the return from RS485 devices.
215 )))
216
217 (((
218 (% style="color:red" %)Note: below description and commands are for firmware version >v1.1, if you have firmware version v1.0. Please check the [[user manual v1.0>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/&file=RS485-LN_UserManual_v1.0.1.pdf]] or upgrade the firmware to v1.1
219
220
221 )))
222 )))
223
224 === 3.3.1 onfigure UART settings for RS485 or TTL communication ===
225
226 To use RS485-LN to read data from RS485 sensors, connect the RS485-LN A/B traces to the sensors. And user need to make sure RS485-LN use the match UART setting to access the sensors. The related commands for UART settings are:
227
228 (% border="1" style="background-color:#ffffcc; color:green; width:782px" %)
229 |(% style="width:128px" %)(((
230 **AT Commands**
231 )))|(% style="width:305px" %)(((
232 **Description**
233 )))|(% style="width:346px" %)(((
234 **Example**
235 )))
236 |(% style="width:128px" %)(((
237 AT+BAUDR
238 )))|(% style="width:305px" %)(((
239 Set the baud rate (for RS485 connection). Default Value is: 9600.
240 )))|(% style="width:346px" %)(((
241 (((
242 AT+BAUDR=9600
243 )))
244
245 (((
246 Options: (1200,2400,4800,14400,19200,115200)
247 )))
248 )))
249 |(% style="width:128px" %)(((
250 AT+PARITY
251 )))|(% style="width:305px" %)(((
252 Set UART parity (for RS485 connection)
253 )))|(% style="width:346px" %)(((
254 (((
255 AT+PARITY=0
256 )))
257
258 (((
259 Option: 0: no parity, 1: odd parity, 2: even parity
260 )))
261 )))
262 |(% style="width:128px" %)(((
263 AT+STOPBIT
264 )))|(% style="width:305px" %)(((
265 (((
266 Set serial stopbit (for RS485 connection)
267 )))
268
269 (((
270
271 )))
272 )))|(% style="width:346px" %)(((
273 (((
274 AT+STOPBIT=0 for 1bit
275 )))
276
277 (((
278 AT+STOPBIT=1 for 1.5 bit
279 )))
280
281 (((
282 AT+STOPBIT=2 for 2 bits
283 )))
284 )))
285
286 === 3.3.2 Configure sensors ===
287
288 (((
289 (((
290 Some sensors might need to configure before normal operation. User can configure such sensor via PC and RS485 adapter or through RS485-LN AT Commands (% style="color:#4f81bd" %)**AT+CFGDEV**(%%). Each (% style="color:#4f81bd" %)**AT+CFGDEV **(%%)equals to send a RS485 command to sensors. This command will only run when user input it and won’t run during each sampling.
291 )))
292 )))
293
294 (% border="1" style="background-color:#ffffcc; color:green; width:806px" %)
295 |**AT Commands**|(% style="width:418px" %)**Description**|(% style="width:256px" %)**Example**
296 |AT+CFGDEV|(% style="width:418px" %)(((
297 This command is used to configure the RS485/TTL devices; they won’t be used during sampling.
298
299 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,
300
301 mm: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command
302 )))|(% style="width:256px" %)AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
303
304 === 3.3.3 Configure read commands for each sampling ===
305
306 (((
307 During each sampling, we need confirm what commands we need to send to the RS485 sensors to read data. After the RS485 sensors send back the value, it normally include some bytes and we only need a few from them for a shorten payload.
308
309 To save the LoRaWAN network bandwidth, we might need to read data from different sensors and combine their valid value into a short payload.
310
311 This section describes how to achieve above goals.
312
313 During each sampling, the RS485-LN can support 15 commands to read sensors. And combine the return to one or several uplink payloads.
314
315
316 **Each RS485 commands include two parts:**
317
318 ~1. What commands RS485-LN will send to the RS485 sensors. There are total 15 commands from **AT+COMMAD1**, **ATCOMMAND2**,…, to **AT+COMMANDF**. All commands are of same grammar.
319
320 2. How to get wanted value the from RS485 sensors returns from by 1). There are total 15 AT Commands to handle the return, commands are **AT+DATACUT1**,**AT+DATACUT2**,…, **AT+DATACUTF** corresponding to the commands from 1). All commands are of same grammar.
321
322 3. Some RS485 device might has longer delay on reply, so user can use AT+CMDDL to set the timeout for getting reply after the RS485 command is sent. For example **AT+CMDDL1=1000** to send the open time to 1000ms
323
324
325 After we got the valid value from each RS485 commands, we need to combine them together with the command **AT+DATAUP**.
326
327
328 Below are examples for the how above AT Commands works.
329
330
331 **AT+COMMANDx : **This command will be sent to RS485 devices during each sampling, Max command length is 14 bytes. The grammar is:
332
333 (% border="1" style="background-color:#4bacc6; color:white; width:499px" %)
334 |(% style="width:496px" %)(((
335 **AT+COMMANDx=xx xx xx xx xx xx xx xx xx xx xx xx,m**
336
337 **xx xx xx xx xx xx xx xx xx xx xx xx: The RS485 command to be sent**
338
339 **m: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command**
340 )))
341
342 For example, if we have a RS485 sensor. The command to get sensor value is: 01 03 0B B8 00 02 46 0A. Where 01 03 0B B8 00 02 is the Modbus command to read the register 0B B8 where stored the sensor value. The 46 0A is the CRC-16/MODBUS which calculate manually.
343
344 In the RS485-LN, we should use this command AT+COMMAND1=01 03 0B B8 00 02,1 for the same.
345
346
347 **AT+DATACUTx : **This command defines how to handle the return from AT+COMMANDx, max return length is 45 bytes.
348
349 (% border="1" style="background-color:#4bacc6; color:white; width:725px" %)
350 |(% style="width:722px" %)(((
351 **AT+DATACUTx=a,b,c**
352
353 * **a: length for the return of AT+COMMAND**
354 * **b:1: grab valid value by byte, max 6 bytes. 2: grab valid value by bytes section, max 3 sections.**
355 * **c: define the position for valid value.  **
356 )))
357
358 **Examples:**
359
360 * Grab bytes:
361
362 [[image:image-20220602153621-1.png]]
363
364
365 * Grab a section.
366
367 [[image:image-20220602153621-2.png]]
368
369
370 * Grab different sections.
371
372 [[image:image-20220602153621-3.png]]
373
374
375 )))
376
377 === 3.3.4 Compose the uplink payload ===
378
379 (((
380 Through AT+COMMANDx and AT+DATACUTx we got valid value from each RS485 commands, Assume these valid value are RETURN1, RETURN2, .., to RETURNx. The next step is how to compose the LoRa Uplink Payload by these RETURNs. The command is **AT+DATAUP.**
381
382
383 )))
384
385 (((
386 (% style="color:#037691" %)**Examples: AT+DATAUP=0**
387
388
389 )))
390
391 (((
392 Compose the uplink payload with value returns in sequence and send with (% style="color:red" %)**A SIGNLE UPLINK**.
393 )))
394
395 (((
396 Final Payload is
397 )))
398
399 (((
400 (% style="color:#4f81bd" %)**Battery Info+PAYVER + VALID Value from RETURN1 + Valid Value from RETURN2 + … + RETURNx**
401 )))
402
403 (((
404 Where PAYVER is defined by AT+PAYVER, below is an example screen shot.
405 )))
406
407 [[image:1653269759169-150.png||height="513" width="716"]]
408
409
410 (% style="color:#037691" %)**Examples: AT+DATAUP=1**
411
412
413 Compose the uplink payload with value returns in sequence and send with (% style="color:red" %)**Multiply UPLINKs**.
414
415 Final Payload is
416
417 (% style="color:#4f81bd" %)**Battery Info+PAYVER + PAYLOAD COUNT + PAYLOAD# + DATA**
418
419 1. Battery Info (2 bytes): Battery voltage
420 1. PAYVER (1 byte): Defined by AT+PAYVER
421 1. PAYLOAD COUNT (1 byte): Total how many uplinks of this sampling.
422 1. PAYLOAD# (1 byte): Number of this uplink. (from 0,1,2,3…,to PAYLOAD COUNT)
423 1. DATA: Valid value: max 6 bytes(US915 version here, Notice*!) for each uplink so each uplink <= 11 bytes. For the last uplink, DATA will might less than 6 bytes
424
425 [[image:1653269916228-732.png||height="433" width="711"]]
426
427
428 So totally there will be 3 uplinks for this sampling, each uplink includes 6 bytes DATA
429
430 DATA1=RETURN1 Valid Value = (% style="background-color:green; color:white" %)20 20 0a 33 90 41
431
432 DATA2=1^^st^^ ~~ 6^^th^^ byte of Valid value of RETURN10=(% style="background-color:green; color:white" %) 02 aa 05 81 0a 20
433
434 DATA3=7^^th^^ ~~ 11^^th^^ bytes of Valid value of RETURN10 = (% style="background-color:green; color:white" %)20 20 20 2d 30
435
436 Below are the uplink payloads:
437
438 [[image:1653270130359-810.png]]
439
440
441 (% style="color:red" %)**Notice: the Max bytes is according to the max support bytes in different Frequency Bands for lowest SF. As below:**
442
443 ~* For AU915/AS923 bands, if UplinkDwell time=0, max 51 bytes for each uplink ( so 51 -5 = 46 max valid date)
444
445 * For AU915/AS923 bands, if UplinkDwell time=1, max 11 bytes for each uplink ( so 11 -5 = 6 max valid date).
446
447 * For US915 band, max 11 bytes for each uplink ( so 11 -5 = 6 max valid date).
448
449 ~* For all other bands: max 51 bytes for each uplink  ( so 51 -5 = 46 max valid date).
450
451 === 3.3.5 Uplink on demand ===
452
453 Except uplink periodically, RS485-BL is able to uplink on demand. The server sends downlink command to RS485-BL and RS485 will uplink data base on the command.
454
455 Downlink control command:
456
457 [[0x08 command>>path:#downlink_08]]: Poll an uplink with current command set in RS485-BL.
458
459 [[0xA8 command>>path:#downlink_A8]]: Send a command to RS485-BL and uplink the output from sensors.
460
461
462
463 1.
464 11.
465 111. Uplink on Interrupt
466
467 Put the interrupt sensor between 3.3v_out and GPIO ext.[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image022.png]]
468
469 AT+INTMOD=0  Disable Interrupt
470
471 AT+INTMOD=1  Interrupt trigger by rising or falling edge.
472
473 AT+INTMOD=2  Interrupt trigger by falling edge. ( Default Value)
474
475 AT+INTMOD=3  Interrupt trigger by rising edge.
476
477
478 1.
479 11. Uplink Payload
480
481 |**Size(bytes)**|**2**|**1**|**Length depends on the return from the commands**
482 |Value|(((
483 Battery(mV)
484
485 &
486
487 Interrupt _Flag
488 )))|(((
489 PAYLOAD_VER
490
491
492 )))|If the valid payload is too long and exceed the maximum support payload length in server, server will show payload not provided in the LoRaWAN server.
493
494 Below is the decoder for the first 3 bytes. The rest bytes are dynamic depends on different RS485 sensors.
495
496
497 function Decoder(bytes, port) {
498
499 ~/~/Payload Formats of RS485-BL Deceive
500
501 return {
502
503 ~/~/Battery,units:V
504
505 BatV:((bytes[0]<<8 | bytes[1])&0x7fff)/1000,
506
507 ~/~/GPIO_EXTI 
508
509 EXTI_Trigger:(bytes[0] & 0x80)? "TRUE":"FALSE",
510
511 ~/~/payload of version
512
513 Pay_ver:bytes[2],
514
515 };
516
517 }
518
519
520
521
522
523
524
525 TTN V3 uplink screen shot.
526
527 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
528
529 1.
530 11. Configure RS485-BL via AT or Downlink
531
532 User can configure RS485-BL via [[AT Commands >>path:#_​Using_the_AT]]or LoRaWAN Downlink Commands
533
534 There are two kinds of Commands:
535
536 * **Common Commands**: They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: http:~/~/wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands
537
538 * **Sensor Related Commands**: These commands are special designed for RS485-BL.  User can see these commands below:
539
540 1.
541 11.
542 111. Common Commands:
543
544 They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[http:~~/~~/wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands>>url:http://wiki.dragino.com/index.php?title=End_Device_AT_Commands_and_Downlink_Commands]]
545
546
547 1.
548 11.
549 111. Sensor related commands:
550
551 ==== Choose Device Type (RS485 or TTL) ====
552
553 RS485-BL can connect to either RS485 sensors or TTL sensor. User need to specify what type of sensor need to connect.
554
555 * AT Command
556
557 **AT+MOD=1** ~/~/ Set to support RS485-MODBUS type sensors. User can connect multiply RS485 , Modbus sensors to the A / B pins.
558
559 **AT+MOD=2** ~/~/ Set to support TTL Level sensors, User can connect one TTL Sensor to the TXD/RXD/GND pins.
560
561
562 * Downlink Payload
563
564 **0A aa**     à same as AT+MOD=aa
565
566
567
568 ==== [[RS485 Debug Command>>path:#downlink_A8]] (AT+CFGDEV) ====
569
570 This command is used to configure the RS485 or TTL sensors; they won’t be used during sampling.
571
572 * AT Command
573
574 AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
575
576 m: 0: no CRC; 1: add CRC-16/MODBUS in the end of this command.
577
578
579
580 * Downlink Payload
581
582 Format: A8 MM NN XX XX XX XX YY
583
584 Where:
585
586 * MM: 1: add CRC-16/MODBUS ; 0: no CRC
587 * NN: The length of RS485 command
588 * XX XX XX XX: RS485 command total NN bytes
589 * YY: How many bytes will be uplink from the return of this RS485 command, if YY=0, RS485-BL will execute the downlink command without uplink; if YY>0, RS485-BL will uplink total YY bytes from the output of this RS485 command
590
591 **Example 1:**
592
593 To connect a Modbus Alarm with below commands.
594
595 * The command to active alarm is: 0A 05 00 04 00 01 4C B0. Where 0A 05 00 04 00 01 is the Modbus command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which calculate manually.
596
597 * The command to deactivate alarm is: 0A 05 00 04 00 00 8D 70. Where 0A 05 00 04 00 00 is the Modbus command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which calculate manually.
598
599 So if user want to use downlink command to control to RS485 Alarm, he can use:
600
601 **A8 01 06 0A 05 00 04 00 01 00**: to activate the RS485 Alarm
602
603 **A8 01 06 0A 05 00 04 00 00 00**: to deactivate the RS485 Alarm
604
605 A8 is type code and 01 means add CRC-16/MODBUS at the end, the 3^^rd^^ byte is 06, means the next 6 bytes are the command to be sent to the RS485 network, the final byte 00 means this command don’t need to acquire output.
606
607
608 **Example 2:**
609
610 Check TTL Sensor return:
611
612 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image024.png]]
613
614
615
616
617 ==== Set Payload version ====
618
619 This is the first byte of the uplink payload. RS485-BL can connect to different sensors. User can set the PAYVER field to tell server how to decode the current payload.
620
621 * AT Command:
622
623 AT+PAYVER: Set PAYVER field = 1
624
625
626 * Downlink Payload:
627
628 0xAE 01   à Set PAYVER field =  0x01
629
630 0xAE 0F   à Set PAYVER field =  0x0F
631
632
633 ==== Set RS485 Sampling Commands ====
634
635 AT+COMMANDx, AT+DATACUTx and AT+SEARCHx
636
637 These three commands are used to configure how the RS485-BL polling data from Modbus device. Detail of usage please see : [[polling RS485 device>>path:#polling_485]].
638
639
640 * AT Command:
641
642 AT+COMMANDx: Configure RS485 read command to sensor.
643
644 AT+DATACUTx: Configure how to handle return from RS485 devices.
645
646 AT+SEARCHx: Configure search command
647
648
649 * Downlink Payload:
650
651 0xAF downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
652
653 Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
654
655 Format: AF MM NN LL XX XX XX XX YY
656
657 Where:
658
659 * MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
660 * NN: 0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
661 * LL: The length of AT+COMMAND or AT+DATACUT command
662 * XX XX XX XX: AT+COMMAND or AT+DATACUT command
663 * YY: If YY=0, RS485-BL will execute the downlink command without uplink; if YY=1, RS485-BL will execute an uplink after got this command.
664
665 Example:
666
667 **AF 03 01 06 0A 05 00 04 00 01 00**: Same as AT+COMMAND3=0A 05 00 04 00 01,1
668
669 **AF 03 02 06 10 01 05 06 09 0A 00**: Same as AT+DATACUT3=**16**,**1**,**5+6+9+10**
670
671 **AF 03 02 06 0B 02 05 07 08 0A 00**: Same as AT+DATACUT3=**11**,**2**,**5~~7+8~~10**
672
673
674 0xAB downlink command can be used for set AT+SEARCHx
675
676 Example: **AB aa 01 03 xx xx xx** (03 here means there are total 3 bytes after 03) So
677
678 * AB aa 01 03 xx xx xx  same as AT+SEARCHaa=1,xx xx xx
679 * AB aa 02 03 xx xx xx 02 yy yy(03 means there are 3 bytes after 03, they are xx xx xx;02 means there are 2 bytes after 02, they are yy yy) so the commands
680
681 **AB aa 02 03 xx xx xx 02 yy yy**  same as **AT+SEARCHaa=2,xx xx xx+yy yy**
682
683
684 ==== Fast command to handle MODBUS device ====
685
686 AT+MBFUN is valid since v1.3 firmware version. The command is for fast configure to read Modbus devices. It is only valid for the devices which follow the [[MODBUS-RTU protocol>>url:https://www.modbustools.com/modbus.html]].
687
688 This command is valid since v1.3 firmware version
689
690
691 AT+MBFUN has only two value:
692
693 * AT+MBFUN=1: Enable Modbus reading. And get response base on the MODBUS return
694
695 AT+MBFUN=1, device can auto read the Modbus function code: 01, 02, 03 or 04. AT+MBFUN has lower priority vs AT+DATACUT command. If AT+DATACUT command is configured, AT+MBFUN will be ignore.
696
697 * AT+MBFUN=0: Disable Modbus fast reading.
698
699 Example:
700
701 * AT+MBFUN=1 and AT+DATACUT1/AT+DATACUT2 are not configure (0,0,0).
702 * AT+COMMAND1= 01 03 00 10 00 08,1 ~-~-> read slave address 01 , function code 03, start address 00 01, quantity of registers 00 08.
703 * AT+COMMAND2= 01 02 00 40 00 10,1 ~-~-> read slave address 01 , function code 02, start address 00 40, quantity of inputs 00 10.
704
705 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image025.png]]
706
707
708 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image026.png]]
709
710
711 * Downlink Commands:
712
713 A9 aa -à Same as AT+MBFUN=aa
714
715
716 ==== RS485 command timeout ====
717
718 Some Modbus device has slow action to send replies. This command is used to configure the RS485-BL to use longer time to wait for their action.
719
720 Default value: 0, range:  0 ~~ 5 seconds
721
722
723 * AT Command:
724
725 AT+CMDDLaa=hex(bb cc)
726
727 Example:
728
729 **AT+CMDDL1=1000** to send the open time to 1000ms
730
731
732 * Downlink Payload:
733
734 0x AA aa bb cc
735
736 Same as: AT+CMDDLaa=hex(bb cc)
737
738 Example:
739
740 0xAA 01 03 E8  à Same as **AT+CMDDL1=1000 ms**
741
742
743 ==== [[Uplink>>path:#downlink_A8]] payload mode ====
744
745 Define to use one uplink or multiple uplinks for the sampling.
746
747 The use of this command please see: [[Compose Uplink payload>>path:#DataUP]]
748
749 * AT Command:
750
751 AT+DATAUP=0
752
753 AT+DATAUP=1
754
755
756 * Downlink Payload:
757
758 0xAD 00   à Same as AT+DATAUP=0
759
760 0xAD 01   à Same as AT+DATAUP=1
761
762
763 ==== Manually trigger an Uplink ====
764
765 Ask device to send an uplink immediately.
766
767 * Downlink Payload:
768
769 0x08 FF, RS485-BL will immediately send an uplink.
770
771
772 ==== Clear RS485 Command ====
773
774 The AT+COMMANDx and AT+DATACUTx settings are stored in special location, user can use below command to clear them.
775
776
777 * AT Command:
778
779 **AT+CMDEAR=mm,nn**   mm: start position of erase ,nn: stop position of erase
780
781 Etc. AT+CMDEAR=1,10 means erase AT+COMMAND1/AT+DATACUT1 to AT+COMMAND10/AT+DATACUT10
782
783 Example screen shot after clear all RS485 commands. 
784
785
786
787 The uplink screen shot is:
788
789 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
790
791
792 * Downlink Payload:
793
794 0x09 aa bb same as AT+CMDEAR=aa,bb
795
796
797 ==== Set Serial Communication Parameters ====
798
799 Set the Rs485 serial communication parameters:
800
801 * AT Command:
802
803 Set Baud Rate:
804
805 AT+BAUDR=9600    ~/~/ Options: (1200,2400,4800,14400,19200,115200)
806
807
808 Set UART parity
809
810 AT+PARITY=0    ~/~/ Option: 0: no parity, 1: odd parity, 2: even parity
811
812
813 Set STOPBIT
814
815 AT+STOPBIT=0    ~/~/ Option: 0 for 1bit; 1 for 1.5 bit ; 2 for 2 bits
816
817
818 * Downlink Payload:
819
820 A7 01 aa bb: Same  AT+BAUDR=hex(aa bb)*100
821
822 Example:
823
824 * A7 01 00 60   same as AT+BAUDR=9600
825 * A7 01 04 80  same as AT+BAUDR=115200
826
827 A7 02 aa: Same as  AT+PARITY=aa  (aa value: 00 , 01 or 02)
828
829 A7 03 aa: Same as  AT+STOPBIT=aa  (aa value: 00 , 01 or 02)
830
831
832 ==== Control output power duration ====
833
834 User can set the output power duration before each sampling.
835
836 * AT Command:
837
838 Example:
839
840 AT+3V3T=1000 ~/~/ 3V3 output power will open 1s before each sampling.
841
842 AT+5VT=1000 ~/~/ +5V output power will open 1s before each sampling.
843
844
845 * LoRaWAN Downlink Command:
846
847 07 01 aa bb  Same as AT+5VT=(aa bb)
848
849 07 02 aa bb  Same as AT+3V3T=(aa bb)
850
851
852
853
854 1.
855 11. Buttons
856
857 |**Button**|**Feature**
858 |**RST**|Reboot RS485-BL
859
860 1.
861 11. +3V3 Output
862
863 RS485-BL has a Controllable +3V3 output, user can use this output to power external sensor.
864
865 The +3V3 output will be valid for every sampling. RS485-BL will enable +3V3 output before all sampling and disable the +3V3 after all sampling. 
866
867
868 The +3V3 output time can be controlled by AT Command.
869
870 **AT+3V3T=1000**
871
872 Means set +3v3 valid time to have 1000ms. So, the real +3v3 output will actually have 1000ms + sampling time for other sensors.
873
874
875 By default, the AT+3V3T=0. This is a special case, means the +3V3 output is always on at any time
876
877
878 1.
879 11. +5V Output
880
881 RS485-BL has a Controllable +5V output, user can use this output to power external sensor.
882
883 The +5V output will be valid for every sampling. RS485-BL will enable +5V output before all sampling and disable the +5v after all sampling. 
884
885
886 The 5V output time can be controlled by AT Command.
887
888 **AT+5VT=1000**
889
890 Means set 5V valid time to have 1000ms. So, the real 5V output will actually have 1000ms + sampling time for other sensors.
891
892
893 By default, the AT+5VT=0. If the external sensor which require 5v and require more time to get stable state, user can use this command to increase the power ON duration for this sensor.
894
895
896
897
898 1.
899 11. LEDs
900
901 |**LEDs**|**Feature**
902 |**LED1**|Blink when device transmit a packet.
903
904 1.
905 11. Switch Jumper
906
907 |**Switch Jumper**|**Feature**
908 |**SW1**|(((
909 ISP position: Upgrade firmware via UART
910
911 Flash position: Configure device, check running status.
912 )))
913 |**SW2**|(((
914 5V position: set to compatible with 5v I/O.
915
916 3.3v position: set to compatible with 3.3v I/O.,
917 )))
918
919 +3.3V: is always ON
920
921 +5V: Only open before every sampling. The time is by default, it is AT+5VT=0.  Max open time. 5000 ms.
922
923 1. Case Study
924
925 User can check this URL for some case studies.
926
927 [[http:~~/~~/wiki.dragino.com/index.php?title=APP_RS485_COMMUNICATE_WITH_SENSORS>>url:http://wiki.dragino.com/index.php?title=APP_RS485_COMMUNICATE_WITH_SENSORS]]
928
929
930
931
932 1. Use AT Command
933 11. Access AT Command
934
935 RS485-BL supports AT Command set. User can use a USB to TTL adapter plus the 3.5mm Program Cable to connect to RS485-BL to use AT command, as below.
936
937 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image027.png]]
938
939
940 In PC, User needs to set **serial tool**(such as [[putty>>url:https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to **9600** to access to access serial console of RS485-BL. The default password is 123456. Below is the output for reference:
941
942 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image028.png]]
943
944
945
946 More detail AT Command manual can be found at [[AT Command Manual>>path:#AT_COMMAND]]
947
948
949
950 1.
951 11. Common AT Command Sequence
952 111. Multi-channel ABP mode (Use with SX1301/LG308)
953
954 If device has not joined network yet:
955
956 AT+FDR
957
958 AT+NJM=0
959
960 ATZ
961
962
963 If device already joined network:
964
965 AT+NJM=0
966
967 ATZ
968
969 1.
970 11.
971 111. Single-channel ABP mode (Use with LG01/LG02)
972
973 AT+FDR   Reset Parameters to Factory Default, Keys Reserve
974
975 AT+NJM=0 Set to ABP mode
976
977 AT+ADR=0 Set the Adaptive Data Rate Off
978
979 AT+DR=5  Set Data Rate
980
981 AT+TDC=60000  Set transmit interval to 60 seconds
982
983 AT+CHS=868400000 Set transmit frequency to 868.4Mhz
984
985 AT+RX2FQ=868400000 Set RX2Frequency to 868.4Mhz (according to the result from server)
986
987 AT+RX2DR=5  Set RX2DR to match the downlink DR from server. see below
988
989 AT+DADDR=26 01 1A F1 Set Device Address to 26 01 1A F1, this ID can be found in the LoRa Server portal.
990
991 ATZ          Reset MCU
992
993 **Note:**
994
995 1. Make sure the device is set to ABP mode in the IoT Server.
996 1. Make sure the LG01/02 gateway RX frequency is exactly the same as AT+CHS setting.
997 1. Make sure SF / bandwidth setting in LG01/LG02 match the settings of AT+DR. refer [[this link>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_Gateway/&file=LoRaWAN%201.0.3%20Regional%20Parameters.xlsx]] to see what DR means.
998 1. The command AT+RX2FQ and AT+RX2DR is to let downlink work. to set the correct parameters, user can check the actually downlink parameters to be used. As below. Which shows the RX2FQ should use 868400000 and RX2DR should be 5
999
1000 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image029.png]]
1001
1002
1003 1. FAQ
1004 11. How to upgrade the image?
1005
1006 The RS485-BL LoRaWAN Controller is shipped with a 3.5mm cable, the cable is used to upload image to RS485-BL to:
1007
1008 * Support new features
1009 * For bug fix
1010 * Change LoRaWAN bands.
1011
1012 Below shows the hardware connection for how to upload an image to RS485-BL:
1013
1014 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image030.png]]
1015
1016 **Step1:** Download [[flash loader>>url:https://www.st.com/content/st_com/en/products/development-tools/software-development-tools/stm32-software-development-tools/stm32-programmers/flasher-stm32.html]].
1017
1018 **Step2**: Download the [[LT Image files>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/image/]].
1019
1020 **Step3: **Open flashloader; choose the correct COM port to update.
1021
1022
1023 |(((
1024 HOLD PRO then press the RST button, SYS will be ON, then click next
1025 )))
1026
1027 |(((
1028 Board detected
1029 )))
1030
1031 |(((
1032
1033 )))
1034
1035 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image031.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image032.png]]
1036
1037
1038
1039 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image033.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image034.png]]
1040
1041
1042 [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image035.png]] [[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image036.png]]
1043
1044
1045 1.
1046 11. How to change the LoRa Frequency Bands/Region?
1047
1048 User can follow the introduction for [[how to upgrade image>>path:#upgrade_image]]. When download the images, choose the required image file for download.
1049
1050
1051
1052 1.
1053 11. How many RS485-Slave can RS485-BL connects?
1054
1055 The RS485-BL can support max 32 RS485 devices. Each uplink command of RS485-BL can support max 16 different RS485 command. So RS485-BL can support max 16 RS485 devices pre-program in the device for uplink. For other devices no pre-program, user can use the [[downlink message (type code 0xA8) to poll their info>>path:#downlink_A8]].
1056
1057
1058
1059
1060 1. Trouble Shooting     
1061 11. Downlink doesn’t work, how to solve it?
1062
1063 Please see this link for debug:
1064
1065 [[http:~~/~~/wiki.dragino.com/index.php?title=Main_Page#LoRaWAN_Communication_Debug>>url:http://wiki.dragino.com/index.php?title=Main_Page#LoRaWAN_Communication_Debug]] 
1066
1067
1068
1069 1.
1070 11. Why I can’t join TTN V3 in US915 /AU915 bands?
1071
1072 It might about the channels mapping. Please see for detail.
1073
1074 [[http:~~/~~/wiki.dragino.com/index.php?title=LoRaWAN_Communication_Debug#Notice_of_US915.2FCN470.2FAU915_Frequency_band>>url:http://wiki.dragino.com/index.php?title=LoRaWAN_Communication_Debug#Notice_of_US915.2FCN470.2FAU915_Frequency_band]]
1075
1076
1077
1078 1. Order Info
1079
1080 **Part Number: RS485-BL-XXX**
1081
1082 **XXX:**
1083
1084 * **EU433**: frequency bands EU433
1085 * **EU868**: frequency bands EU868
1086 * **KR920**: frequency bands KR920
1087 * **CN470**: frequency bands CN470
1088 * **AS923**: frequency bands AS923
1089 * **AU915**: frequency bands AU915
1090 * **US915**: frequency bands US915
1091 * **IN865**: frequency bands IN865
1092 * **RU864**: frequency bands RU864
1093 * **KZ865: **frequency bands KZ865
1094
1095 1. Packing Info
1096
1097 **Package Includes**:
1098
1099 * RS485-BL x 1
1100 * Stick Antenna for LoRa RF part x 1
1101 * Program cable x 1
1102
1103 **Dimension and weight**:
1104
1105 * Device Size: 13.5 x 7 x 3 cm
1106 * Device Weight: 105g
1107 * Package Size / pcs : 14.5 x 8 x 5 cm
1108 * Weight / pcs : 170g
1109
1110 1. Support
1111
1112 * Support is provided Monday to Friday, from 09:00 to 18:00 GMT+8. Due to different timezones we cannot offer live support. However, your questions will be answered as soon as possible in the before-mentioned schedule.
1113 * Provide as much information as possible regarding your enquiry (product models, accurately describe your problem and steps to replicate it etc) and send a mail to
1114
1115 [[support@dragino.com>>url:file:///D:/市场资料/说明书/LoRa/LT系列/support@dragino.com]]
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0