845 845  Test the current values at the depth of different liquids and convert them to a linear scale.
846 846  Replace its ratio with the ratio of water to current in the decoder.
847 847  
848 -**Example:**
849 849  
850 -Measure the corresponding current of the sensor when the liquid depth is 2.04m and 0.51m.
851 -
852 -**Calculate scale factor:**
853 -Use these two data to calculate the current and depth scaling factors:(7.888-5.035)/(2.04-0.51)=1.86470588235294
854 -
855 -**Calculation formula:**
856 -
857 -Use the calibration formula:(Current current - Minimum calibration current)/Scale factor + Minimum actual calibration height
858 -
859 -**Actual calculations:**
860 -
861 -Use this formula to calculate the value corresponding to the current at a depth of 1.5 meters: (6.918-5.035)/1.86470588235294+0.51=1.519810726
862 -
863 -**Error:**
864 -
865 -0.009810726
866 -
867 -
868 -[[image:image-20240329175044-1.png]]
869 -
870 870  = 7. Troubleshooting =
871 871  
872 872  == 7.1 Water Depth Always shows 0 in payload ==