... ... @@ -645,8 +645,6 @@
645 645  |=(% colspan="4" style="width: 160px; background-color:#4F81BD;color:white" %)Downlink Command to poll Open/Close status (0x31)
646 646  |(% style="background-color:#f2f2f2; width:67px" %)1byte|(% style="background-color:#f2f2f2; width:145px" %)4bytes|(% style="background-color:#f2f2f2; width:133px" %)4bytes|(% style="background-color:#f2f2f2; width:163px" %)1byte
647 647  |(% style="background-color:#f2f2f2; width:67px" %)31|(% style="background-color:#f2f2f2; width:145px" %)Timestamp start|(% style="background-color:#f2f2f2; width:133px" %)(((
648 -
649 -
650 650  Timestamp end
651 651  )))|(% style="background-color:#f2f2f2; width:163px" %)Uplink Interval
652 652  
... ... @@ -681,7 +681,6 @@
681 681  )))|(% style="width:86px" %)Unix Time Stamp
682 682  
683 683  
684 -
685 685  IN1_pin_level & IN2_pin_level & Exti_pin_level & Exti_status:
686 686  
687 687  [[image:image-20250117104847-4.png]]
... ... @@ -787,13 +787,9 @@
787 787  
788 788  (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:510px" %)
789 789  |(% style="background-color:#4f81bd; color:white; width:97px" %)(((
790 -
791 -
792 792  Size(bytes)
793 793  )))|(% style="background-color:#4f81bd; color:white; width:48px" %)2|(% style="background-color:#4f81bd; color:white; width:71px" %)2|(% style="background-color:#4f81bd; color:white; width:98px" %)2|(% style="background-color:#4f81bd; color:white; width:73px" %)2|(% style="background-color:#4f81bd; color:white; width:122px" %)1
794 -|(% style="width:97px" %)Value|(% style="width:48px" %)[[BAT>>||anchor="H2.3.3BatteryInfo"]]|(% style="width:71px" %)[[Probe Model>>||anchor="H2.3.4ProbeModel"]]|(% style="width:98px" %)[[0 ~~~~ 20mA value>>||anchor="H2.3.507E20mAvalue28IDC_IN29"]]|(% style="width:73px" %)[[0 ~~~~ 30v value>>||anchor="H2.3.607E30Vvalue28pinVDC_IN29"]]|(% style="width:122px" %)(((
795 -
796 -
789 +|(% style="width:98px" %)Value|(% style="width:48px" %)[[BAT>>||anchor="H2.3.3BatteryInfo"]]|(% style="width:71px" %)[[Probe Model>>||anchor="H2.3.4ProbeModel"]]|(% style="width:98px" %)[[0 ~~~~ 20mA value>>||anchor="H2.3.507E20mAvalue28IDC_IN29"]]|(% style="width:73px" %)[[0 ~~~~ 30v value>>||anchor="H2.3.607E30Vvalue28pinVDC_IN29"]]|(% style="width:122px" %)(((
797 797  [[IN1 &IN2 Interrupt  flag>>||anchor="H2.3.7IN126IN226INTpin"]] & ROC_flag
798 798  )))
799 799  
... ... @@ -859,6 +859,7 @@
859 859  
860 860  ==== 2.8.2.1 Wave alarm mode ====
861 861  
855 +
862 862  Feature: By setting the detection period and a change value, the IDC/VDC variable is monitored whether it exceeds the set change value. If this change value is exceeded, the ROC uplink is sent and the comparison value is flushed.
863 863  
864 864  * Change value: The amount by which the next detection value increases/decreases relative to the previous detection value.
... ... @@ -869,46 +869,27 @@
869 869  (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:510px" %)
870 870  |=(% style="width: 163px; background-color: rgb(79, 129, 189); color: white;" %)Command Example|=(% style="width: 154px; background-color: rgb(79, 129, 189); color: white;" %)Parameters|=(% style="width: 197px; background-color: rgb(79, 129, 189); color: white;" %)Response/Explanation
871 871  |(% style="width:143px" %)AT+ROC=?|(% style="width:154px" %)Show current ROC setting|(% style="width:197px" %)(((
872 -
873 -
874 874  0,0,0,0(default)
875 875  OK
876 876  )))
877 877  |(% colspan="1" rowspan="4" style="width:143px" %)(((
878 -
879 -
880 -
881 -
882 -
883 883  AT+ROC=a,b,c,d
884 884  )))|(% style="width:154px" %)(((
885 -
886 -
887 -
888 -
889 -
890 -
891 -
892 -a: Enable or disable the ROC
872 +**a:** Enable or disable the ROC
893 893  )))|(% style="width:197px" %)(((
894 -
895 -
896 -0: off
897 -1: Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value.
898 -
899 -2: Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value. In addition, the comparison value is refreshed when the device sends packets ([[TDC>>||anchor="H3.3.1SetTransmitIntervalTime"]] or [[ACT>>||anchor="H1.7Button26LEDs"]]).
874 +**0:** off
875 +**1:** Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value.
876 +**2:** Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value. In addition, the comparison value is refreshed when the device sends packets ([[TDC>>||anchor="H3.3.1SetTransmitIntervalTime"]] or [[ACT>>||anchor="H1.7Button26LEDs"]]).
900 900  )))
901 -|(% style="width:154px" %)b: Set the detection interval|(% style="width:197px" %)(((
902 -
903 -
878 +|(% style="width:154px" %)**b:** Set the detection interval|(% style="width:197px" %)(((
904 904  Range:  0~~65535s
905 905  )))
906 -|(% style="width:154px" %)c: Setting the IDC change value|(% style="width:197px" %)Unit: uA
907 -|(% style="width:154px" %)d: Setting the VDC change value|(% style="width:197px" %)Unit: mV
881 +|(% style="width:154px" %)**c:** Setting the IDC change value|(% style="width:197px" %)Unit: uA
882 +|(% style="width:154px" %)**d:** Setting the VDC change value|(% style="width:197px" %)Unit: mV
908 908  
909 909  Example:
910 910  
911 -* AT+ROC=0,0,0,0  ~/~/The ROC function is not used.
886 +* AT+ROC=0,0,0,0  ~/~/ The ROC function is not used.
912 912  * AT+ROC=1,60,3000, 500  ~/~/ Check value every 60 seconds. lf there is change in IDC (>3mA) or VDC (>500mV), sends an ROC uplink, and the comparison value is refreshed.
913 913  * AT+ROC=1,60,3000,0  ~/~/ Check value every 60 seconds. lf there is change in IDC (>3mA), send an ROC uplink and the comparison value of IDC is refreshed. dd=0 Means doesn't monitor Voltage.
914 914  * AT+ROC=2,60,3000,0  ~/~/ Check value every 60 seconds. lf there is change in IDC (>3mA), send an ROC uplink and the comparison value of IDC is refreshed. dd=0 Means doesn't monitor Voltage. In addition, if the change in the IDC does not exceed 3mA, then the ROC uplink is not sent, and the comparison value is not refreshed by the ROC uplink packet. However, if the device TDC time arrives, or if the user manually sends packets, then the IDC comparison value is also refreshed.
... ... @@ -927,9 +927,9 @@
927 927  
928 928  Example:
929 929  
930 -* Downlink Payload: 09 01 00 3C 0B B8 01 F4  ~/~/Equal to AT+ROC=1,60,3000, 500
931 -* Downlink Payload: 09 01 00 3C 0B B8 00 00  ~/~/Equal to AT+ROC=1,60,3000,0
932 -* Downlink Payload: 09 02 00 3C 0B B8 00 00  ~/~/Equal to AT+ROC=2,60,3000,0
905 +* Downlink Payload: 09 01 00 3C 0B B8 01 F4  ~/~/ Equal to AT+ROC=1,60,3000, 500
906 +* Downlink Payload: 09 01 00 3C 0B B8 00 00  ~/~/ Equal to AT+ROC=1,60,3000,0
907 +* Downlink Payload: 09 02 00 3C 0B B8 00 00  ~/~/ Equal to AT+ROC=2,60,3000,0
933 933  
934 934  Screenshot of parsing example in TTN:
935 935  
... ... @@ -940,6 +940,7 @@
940 940  
941 941  ==== 2.8.2.2 Over-threshold alarm mode ====
942 942  
918 +
943 943  Feature: Monitors whether the IDC/VDC exceeds the threshold by setting the detection period and threshold. Alarm if the threshold is exceeded.
944 944  
945 945  AT Command: AT+ROC=3,a,b,c,d,e
... ... @@ -947,8 +947,6 @@
947 947  (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:510px" %)
948 948  |=(% style="width: 163px; background-color: rgb(79, 129, 189); color: white;" %)Command Example|=(% style="width: 160px; background-color: rgb(79, 129, 189); color: white;" %)Parameters|=(% style="width: 185px; background-color: rgb(79, 129, 189); color: white;" %)Response/Explanation
949 949  |(% style="width:143px" %)AT+ROC=?|(% style="width:160px" %)Show current ROC setting|(% style="width:185px" %)(((
950 -
951 -
952 952  0,0,0,0(default)
953 953  OK
954 954  )))
... ... @@ -960,44 +960,32 @@
960 960  
961 961  AT+ROC=3,a,b,c,d,e
962 962  )))|(% style="width:160px" %)(((
963 -
964 -
965 -a: Set the detection interval
937 +**a:** Set the detection interval
966 966  )))|(% style="width:185px" %)(((
967 -
968 -
969 969  Range:  0~~65535s
970 970  )))
971 -|(% style="width:160px" %)b: Set the IDC alarm trigger condition|(% style="width:185px" %)(((
972 -
941 +|(% style="width:160px" %)**b:** Set the IDC alarm trigger condition|(% style="width:185px" %)(((
942 +**0:** Less than the set IDC threshold, Alarm
973 973  
974 -0: Less than the set IDC threshold, Alarm
975 -
976 -1: Greater than the set IDC threshold, Alarm
944 +**1:** Greater than the set IDC threshold, Alarm
977 977  )))
978 978  |(% style="width:160px" %)(((
979 -
980 -
981 -c:  IDC alarm threshold
947 +**c: ** IDC alarm threshold
982 982  )))|(% style="width:185px" %)(((
983 -
984 -
985 985  Unit: uA
986 986  )))
987 -|(% style="width:160px" %)d: Set the VDC alarm trigger condition|(% style="width:185px" %)(((
988 -
951 +|(% style="width:160px" %)**d:** Set the VDC alarm trigger condition|(% style="width:185px" %)(((
952 +**0:** Less than the set VDC threshold, Alarm
989 989  
990 -0: Less than the set VDC threshold, Alarm
991 -
992 -1: Greater than the set VDC threshold, Alarm
954 +**1:** Greater than the set VDC threshold, Alarm
993 993  )))
994 -|(% style="width:160px" %)e: VDC alarm threshold|(% style="width:185px" %)Unit: mV
956 +|(% style="width:160px" %)**e:** VDC alarm threshold|(% style="width:185px" %)Unit: mV
995 995  
996 996  Example:
997 997  
998 -* AT+ROC=3,60,0,3000,0,5000  ~/~/The data is checked every 60 seconds. If the IDC is less than 3mA or the VDC is less than 5000mV, an alarm is generated.
999 -* AT+ROC=3,180,1,3000,1,5000  ~/~/The data is checked every 180 seconds. If the IDC is greater than 3mA or the VDC is greater than 5000mV, an alarm is generated.
1000 -* AT+ROC=3,300,0,3000,1,5000  ~/~/The data is checked every 300 seconds. If the IDC is less than 3mA or the VDC is greater than 5000mV, an alarm is generated.
960 +* AT+ROC=3,60,0,3000,0,5000  ~/~/ The data is checked every 60 seconds. If the IDC is less than 3mA or the VDC is less than 5000mV, an alarm is generated.
961 +* AT+ROC=3,180,1,3000,1,5000  ~/~/ The data is checked every 180 seconds. If the IDC is greater than 3mA or the VDC is greater than 5000mV, an alarm is generated.
962 +* AT+ROC=3,300,0,3000,1,5000  ~/~/ The data is checked every 300 seconds. If the IDC is less than 3mA or the VDC is greater than 5000mV, an alarm is generated.
1001 1001  
1002 1002  Downlink Command: 0x09 03 aa bb cc dd ee
1003 1003  
... ... @@ -1016,9 +1016,9 @@
1016 1016  
1017 1017  Example:
1018 1018  
1019 -* Downlink Payload: 09 03 00 3C 00 0B B8 00 13 38 ~/~/Equal to AT+ROC=3,60,0,3000,0,5000
1020 -* Downlink Payload: 09 03 00 b4 01 0B B8 01 13 38  ~/~/Equal to AT+ROC=3,60,1,3000,1,5000
1021 -* Downlink Payload: 09 03 01 2C 00 0B B8 01 13 38  ~/~/Equal to AT+ROC=3,60,0,3000,1,5000
981 +* Downlink Payload: 09 03 00 3C 00 0B B8 00 13 38 ~/~/ Equal to AT+ROC=3,60,0,3000,0,5000
982 +* Downlink Payload: 09 03 00 b4 01 0B B8 01 13 38  ~/~/ Equal to AT+ROC=3,60,1,3000,1,5000
983 +* Downlink Payload: 09 03 01 2C 00 0B B8 01 13 38  ~/~/ Equal to AT+ROC=3,60,0,3000,1,5000
1022 1022  
1023 1023  Screenshot of parsing example in TTN:
1024 1024  
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved