1287 1287  Measure the corresponding current of the sensor when the liquid depth is 2.04m and 0.51m.
1288 1288  
1289 -Calculate scale factor
1289 +Calculate scale factor:
1290 1290  Use these two data to calculate the current and depth scaling factors:(7.888-5.035)/(2.04-0.51)=1.86470588235294
1291 1291  
1292 -Calculation formula
1292 +Calculation formula:
1293 1293  
1294 1294  Use the calibration formula:(Current current - Minimum calibration current)/Scale factor + Minimum actual calibration height
1295 1295  
1296 -Actual calculations
1296 +Actual calculations:
1297 1297  
1298 1298  Use this formula to calculate the value corresponding to the current at a depth of 1.5 meters: (6.918-5.035)/1.86470588235294+0.51=1.519810726
1299 1299  
1300 -Error
1300 +Error:
1301 1301  
1302 1302  0.009810726
1303 1303  