... ... @@ -679,7 +679,6 @@
679 679  )))|(% style="width:86px" %)Unix Time Stamp
680 680  
681 681  
682 -
683 683  IN1_pin_level & IN2_pin_level & Exti_pin_level & Exti_status:
684 684  
685 685  [[image:image-20250117104847-4.png]]
... ... @@ -853,6 +853,7 @@
853 853  
854 854  ==== 2.8.2.1 Wave alarm mode ====
855 855  
855 +
856 856  Feature: By setting the detection period and a change value, the IDC/VDC variable is monitored whether it exceeds the set change value. If this change value is exceeded, the ROC uplink is sent and the comparison value is flushed.
857 857  
858 858  * Change value: The amount by which the next detection value increases/decreases relative to the previous detection value.
... ... @@ -869,21 +869,21 @@
869 869  |(% colspan="1" rowspan="4" style="width:143px" %)(((
870 870  AT+ROC=a,b,c,d
871 871  )))|(% style="width:154px" %)(((
872 -a: Enable or disable the ROC
872 +**a:** Enable or disable the ROC
873 873  )))|(% style="width:197px" %)(((
874 -0: off
875 -1: Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value.
876 -2: Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value. In addition, the comparison value is refreshed when the device sends packets ([[TDC>>||anchor="H3.3.1SetTransmitIntervalTime"]] or [[ACT>>||anchor="H1.7Button26LEDs"]]).
874 +**0:** off
875 +**1:** Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value.
876 +**2:** Turn on the wave alarm mode, send the ROC uplink when the increment exceeds the set parameter and refresh the comparison value. In addition, the comparison value is refreshed when the device sends packets ([[TDC>>||anchor="H3.3.1SetTransmitIntervalTime"]] or [[ACT>>||anchor="H1.7Button26LEDs"]]).
877 877  )))
878 -|(% style="width:154px" %)b: Set the detection interval|(% style="width:197px" %)(((
878 +|(% style="width:154px" %)**b:** Set the detection interval|(% style="width:197px" %)(((
879 879  Range:  0~~65535s
880 880  )))
881 -|(% style="width:154px" %)c: Setting the IDC change value|(% style="width:197px" %)Unit: uA
882 -|(% style="width:154px" %)d: Setting the VDC change value|(% style="width:197px" %)Unit: mV
881 +|(% style="width:154px" %)**c:** Setting the IDC change value|(% style="width:197px" %)Unit: uA
882 +|(% style="width:154px" %)**d:** Setting the VDC change value|(% style="width:197px" %)Unit: mV
883 883  
884 884  Example:
885 885  
886 -* AT+ROC=0,0,0,0  ~/~/The ROC function is not used.
886 +* AT+ROC=0,0,0,0  ~/~/ The ROC function is not used.
887 887  * AT+ROC=1,60,3000, 500  ~/~/ Check value every 60 seconds. lf there is change in IDC (>3mA) or VDC (>500mV), sends an ROC uplink, and the comparison value is refreshed.
888 888  * AT+ROC=1,60,3000,0  ~/~/ Check value every 60 seconds. lf there is change in IDC (>3mA), send an ROC uplink and the comparison value of IDC is refreshed. dd=0 Means doesn't monitor Voltage.
889 889  * AT+ROC=2,60,3000,0  ~/~/ Check value every 60 seconds. lf there is change in IDC (>3mA), send an ROC uplink and the comparison value of IDC is refreshed. dd=0 Means doesn't monitor Voltage. In addition, if the change in the IDC does not exceed 3mA, then the ROC uplink is not sent, and the comparison value is not refreshed by the ROC uplink packet. However, if the device TDC time arrives, or if the user manually sends packets, then the IDC comparison value is also refreshed.
... ... @@ -902,9 +902,9 @@
902 902  
903 903  Example:
904 904  
905 -* Downlink Payload: 09 01 00 3C 0B B8 01 F4  ~/~/Equal to AT+ROC=1,60,3000, 500
906 -* Downlink Payload: 09 01 00 3C 0B B8 00 00  ~/~/Equal to AT+ROC=1,60,3000,0
907 -* Downlink Payload: 09 02 00 3C 0B B8 00 00  ~/~/Equal to AT+ROC=2,60,3000,0
905 +* Downlink Payload: 09 01 00 3C 0B B8 01 F4  ~/~/ Equal to AT+ROC=1,60,3000, 500
906 +* Downlink Payload: 09 01 00 3C 0B B8 00 00  ~/~/ Equal to AT+ROC=1,60,3000,0
907 +* Downlink Payload: 09 02 00 3C 0B B8 00 00  ~/~/ Equal to AT+ROC=2,60,3000,0
908 908  
909 909  Screenshot of parsing example in TTN:
910 910  
... ... @@ -915,6 +915,7 @@
915 915  
916 916  ==== 2.8.2.2 Over-threshold alarm mode ====
917 917  
918 +
918 918  Feature: Monitors whether the IDC/VDC exceeds the threshold by setting the detection period and threshold. Alarm if the threshold is exceeded.
919 919  
920 920  AT Command: AT+ROC=3,a,b,c,d,e
... ... @@ -922,57 +922,36 @@
922 922  (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:510px" %)
923 923  |=(% style="width: 163px; background-color: rgb(79, 129, 189); color: white;" %)Command Example|=(% style="width: 160px; background-color: rgb(79, 129, 189); color: white;" %)Parameters|=(% style="width: 185px; background-color: rgb(79, 129, 189); color: white;" %)Response/Explanation
924 924  |(% style="width:143px" %)AT+ROC=?|(% style="width:160px" %)Show current ROC setting|(% style="width:185px" %)(((
925 -
926 -
927 927  0,0,0,0(default)
928 928  OK
929 929  )))
930 930  |(% colspan="1" rowspan="5" style="width:143px" %)(((
931 -
932 -
933 -
934 -
935 -
936 936  AT+ROC=3,a,b,c,d,e
937 937  )))|(% style="width:160px" %)(((
938 -
939 -
940 -a: Set the detection interval
932 +**a:** Set the detection interval
941 941  )))|(% style="width:185px" %)(((
942 -
943 -
944 944  Range:  0~~65535s
945 945  )))
946 -|(% style="width:160px" %)b: Set the IDC alarm trigger condition|(% style="width:185px" %)(((
947 -
948 -
949 -0: Less than the set IDC threshold, Alarm
950 -
951 -1: Greater than the set IDC threshold, Alarm
936 +|(% style="width:160px" %)**b:** Set the IDC alarm trigger condition|(% style="width:185px" %)(((
937 +**0:** Less than the set IDC threshold, Alarm
938 +**1:** Greater than the set IDC threshold, Alarm
952 952  )))
953 953  |(% style="width:160px" %)(((
954 -
955 -
956 -c:  IDC alarm threshold
941 +**c: ** IDC alarm threshold
957 957  )))|(% style="width:185px" %)(((
958 -
959 -
960 960  Unit: uA
961 961  )))
962 -|(% style="width:160px" %)d: Set the VDC alarm trigger condition|(% style="width:185px" %)(((
963 -
964 -
965 -0: Less than the set VDC threshold, Alarm
966 -
967 -1: Greater than the set VDC threshold, Alarm
945 +|(% style="width:160px" %)**d:** Set the VDC alarm trigger condition|(% style="width:185px" %)(((
946 +**0:** Less than the set VDC threshold, Alarm
947 +**1:** Greater than the set VDC threshold, Alarm
968 968  )))
969 -|(% style="width:160px" %)e: VDC alarm threshold|(% style="width:185px" %)Unit: mV
949 +|(% style="width:160px" %)**e:** VDC alarm threshold|(% style="width:185px" %)Unit: mV
970 970  
971 971  Example:
972 972  
973 -* AT+ROC=3,60,0,3000,0,5000  ~/~/The data is checked every 60 seconds. If the IDC is less than 3mA or the VDC is less than 5000mV, an alarm is generated.
974 -* AT+ROC=3,180,1,3000,1,5000  ~/~/The data is checked every 180 seconds. If the IDC is greater than 3mA or the VDC is greater than 5000mV, an alarm is generated.
975 -* AT+ROC=3,300,0,3000,1,5000  ~/~/The data is checked every 300 seconds. If the IDC is less than 3mA or the VDC is greater than 5000mV, an alarm is generated.
953 +* AT+ROC=3,60,0,3000,0,5000  ~/~/ The data is checked every 60 seconds. If the IDC is less than 3mA or the VDC is less than 5000mV, an alarm is generated.
954 +* AT+ROC=3,180,1,3000,1,5000  ~/~/ The data is checked every 180 seconds. If the IDC is greater than 3mA or the VDC is greater than 5000mV, an alarm is generated.
955 +* AT+ROC=3,300,0,3000,1,5000  ~/~/ The data is checked every 300 seconds. If the IDC is less than 3mA or the VDC is greater than 5000mV, an alarm is generated.
976 976  
977 977  Downlink Command: 0x09 03 aa bb cc dd ee
978 978  
... ... @@ -991,9 +991,9 @@
991 991  
992 992  Example:
993 993  
994 -* Downlink Payload: 09 03 00 3C 00 0B B8 00 13 38 ~/~/Equal to AT+ROC=3,60,0,3000,0,5000
995 -* Downlink Payload: 09 03 00 b4 01 0B B8 01 13 38  ~/~/Equal to AT+ROC=3,60,1,3000,1,5000
996 -* Downlink Payload: 09 03 01 2C 00 0B B8 01 13 38  ~/~/Equal to AT+ROC=3,60,0,3000,1,5000
974 +* Downlink Payload: 09 03 00 3C 00 0B B8 00 13 38 ~/~/ Equal to AT+ROC=3,60,0,3000,0,5000
975 +* Downlink Payload: 09 03 00 b4 01 0B B8 01 13 38  ~/~/ Equal to AT+ROC=3,60,1,3000,1,5000
976 +* Downlink Payload: 09 03 01 2C 00 0B B8 01 13 38  ~/~/ Equal to AT+ROC=3,60,0,3000,1,5000
997 997  