From version < 82.24 >
edited by Xiaoling
on 2022/06/20 11:59
To version < 82.3 >
edited by Xiaoling
on 2022/06/20 11:17
>
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -181,7 +181,6 @@
181 181  * Firmware upgradable via program port
182 182  * Counting
183 183  
184 -
185 185  == 1.4  Applications ==
186 186  
187 187  * Smart Buildings & Home Automation
... ... @@ -191,7 +191,6 @@
191 191  * Smart Cities
192 192  * Smart Factory
193 193  
194 -
195 195  == 1.5 Hardware Variants ==
196 196  
197 197  (% border="1" style="background-color:#f7faff; width:500px" %)
... ... @@ -205,9 +205,6 @@
205 205  * 1 x Counting Port
206 206  )))
207 207  
208 -
209 -
210 -
211 211  = 2. Power ON Device =
212 212  
213 213  The LT controller can be powered by 7 ~~ 24V DC power source. Connect VIN to Power Input V+ and GND to power input V- to power the LT controller.
... ... @@ -288,7 +288,6 @@
288 288  * **MOD5**: Single DI Counting + 2 x AVI + 1 x ACI + DO + RO
289 289  * **ADDMOD6**: Trigger Mode, Optional, used together with MOD1 ~~ MOD5
290 290  
291 -
292 292  === 3.3.1 AT+MOD~=1, 2ACI+2AVI ===
293 293  
294 294  The uplink payload includes totally 9 bytes. Uplink packets use FPORT=2 and every 10 minutes send one uplink by default.
... ... @@ -342,7 +342,6 @@
342 342  ** DO1 is high in case there is load between DO1 and V+.
343 343  ** DO1 LED is off in both case
344 344  
345 -
346 346  === 3.3.2 AT+MOD~=2, (Double DI Counting) ===
347 347  
348 348  
... ... @@ -379,7 +379,12 @@
379 379  (((
380 380  (((
381 381  **AT+MOD=2**
375 +)))
376 +)))
382 382  
378 +(% class="box infomessage" %)
379 +(((
380 +(((
383 383  **ATZ**
384 384  )))
385 385  )))
... ... @@ -397,16 +397,41 @@
397 397  (% class="box infomessage" %)
398 398  (((
399 399  (((
400 -**AT+TRIG1=0,100  (set DI1 port to trigger on low level, valid signal is 100ms) **
398 +**AT+TRIG1=0,100 (set DI1 port to trigger on low level, valid signal is 100ms) **
399 +)))
400 +)))
401 401  
402 -**AT+TRIG1=1,100  (set DI1 port to trigger on high level, valid signal is 100ms ) **
402 +(% class="box infomessage" %)
403 +(((
404 +(((
405 +**AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms ) **
406 +)))
407 +)))
403 403  
404 -**AT+TRIG2=0,100  (set DI2 port to trigger on low level, valid signal is 100ms) **
409 +(% class="box infomessage" %)
410 +(((
411 +(((
412 +**AT+TRIG2=0,100 (set DI2 port to trigger on low level, valid signal is 100ms) **
413 +)))
414 +)))
405 405  
406 -**AT+TRIG2=1,100  (set DI2 port to trigger on high level, valid signal is 100ms ) **
416 +(% class="box infomessage" %)
417 +(((
418 +(((
419 +**AT+TRIG2=1,100 (set DI2 port to trigger on high level, valid signal is 100ms ) **
420 +)))
421 +)))
407 407  
423 +(% class="box infomessage" %)
424 +(((
425 +(((
408 408  **AT+SETCNT=1,60   (Set COUNT1 value to 60)**
427 +)))
428 +)))
409 409  
430 +(% class="box infomessage" %)
431 +(((
432 +(((
410 410  **AT+SETCNT=2,60   (Set COUNT2 value to 60)**
411 411  )))
412 412  )))
... ... @@ -441,7 +441,12 @@
441 441  (((
442 442  (((
443 443  **AT+MOD=3**
467 +)))
468 +)))
444 444  
470 +(% class="box infomessage" %)
471 +(((
472 +(((
445 445  **ATZ**
446 446  )))
447 447  )))
... ... @@ -486,13 +486,20 @@
486 486  (((
487 487  (((
488 488  **AT+MOD=4**
517 +)))
518 +)))
489 489  
520 +(% class="box infomessage" %)
521 +(((
522 +(((
490 490  **ATZ**
491 491  )))
492 492  )))
493 493  
527 +(((
528 +
529 +)))
494 494  
495 -
496 496  (((
497 497  Other AT Commands for counting are similar to [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]].
498 498  )))
... ... @@ -506,17 +506,33 @@
506 506  (% class="box infomessage" %)
507 507  (((
508 508  (((
509 -(% style="color:blue" %)**AT+SETCNT=3,60**(%%)**  (set AVI Count to 60)**
544 +**AT+SETCNT=3,60   (set AVI Count to 60)**
545 +)))
546 +)))
510 510  
511 -(% style="color:blue" %)**AT+VOLMAX=20000**(%%)**  (If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1)**
548 +(% class="box infomessage" %)
549 +(((
550 +(((
551 +**AT+VOLMAX=20000   (If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1)**
552 +)))
553 +)))
512 512  
513 -(% style="color:blue" %)**AT+VOLMAX=20000,0**(%%)**  (If AVI1 voltage lower than VOLMAX (20000mV =20v), counter increase 1)**
555 +(% class="box infomessage" %)
556 +(((
557 +(((
558 +**AT+VOLMAX=20000,0   (If AVI1 voltage lower than VOLMAX (20000mV =20v), counter increase 1)**
559 +)))
560 +)))
514 514  
515 -(% style="color:blue" %)**AT+VOLMAX=20000,1**(%%)**  (If AVI1 voltage higer than VOLMAX (20000mV =20v), counter increase 1)**
562 +(% class="box infomessage" %)
563 +(((
564 +(((
565 +**AT+VOLMAX=20000,1   (If AVI1 voltage higer than VOLMAX (20000mV =20v), counter increase 1)**
516 516  )))
517 517  )))
518 518  
519 519  
570 +
520 520  === 3.3.5 AT+MOD~=5, Single DI Counting + 2 x AVI + 1 x ACI ===
521 521  
522 522  
... ... @@ -550,7 +550,12 @@
550 550  (((
551 551  (((
552 552  **AT+MOD=5**
604 +)))
605 +)))
553 553  
607 +(% class="box infomessage" %)
608 +(((
609 +(((
554 554  **ATZ**
555 555  )))
556 556  )))
... ... @@ -576,9 +576,8 @@
576 576  1. Periodically uplink (Base on TDC time). Payload is same as the normal MOD (MOD 1 for above command). This uplink uses LoRaWAN (% style="color:#4f81bd" %)**unconfirmed**(%%) data type
577 577  1. Trigger uplink when meet the trigger condition. LT will sent two packets in this case, the first uplink use payload specify in this mod (mod=6), the second packets use the normal mod payload(MOD=1 for above settings). Both Uplinks use LoRaWAN (% style="color:#4f81bd" %)**CONFIRMED data type.**
578 578  
635 +**AT Command to set Trigger Condition**:
579 579  
580 -(% style="color:#037691" %)**AT Command to set Trigger Condition**:
581 -
582 582  (% style="color:#4f81bd" %)**Trigger base on voltage**:
583 583  
584 584  Format: AT+AVLIM=<AV1_LIMIT_LOW>,< AV1_LIMIT_HIGH>,<AV2_LIMIT_LOW>,< AV2_LIMIT_HIGH>
... ... @@ -613,7 +613,7 @@
613 613  AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
614 614  
615 615  
616 -(% style="color:#037691" %)**Downlink Command to set Trigger Condition:**
671 +**Downlink Command to set Trigger Condition:**
617 617  
618 618  Type Code: 0xAA. Downlink command same as AT Command **AT+AVLIM, AT+ACLIM**
619 619  
... ... @@ -718,7 +718,6 @@
718 718  
719 719  * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for LT-22222-L.  User can see these commands below:
720 720  
721 -
722 722  === 3.4.1 Common Commands ===
723 723  
724 724  They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
... ... @@ -731,7 +731,7 @@
731 731  
732 732  Set device uplink interval.
733 733  
734 -* (% style="color:#037691" %)**AT Command:**
788 +* AT Command:
735 735  
736 736  (% class="box infomessage" %)
737 737  (((
... ... @@ -741,7 +741,7 @@
741 741  **Example: **AT+TDC=30000. Means set interval to 30 seconds
742 742  
743 743  
744 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x01):**
798 +* Downlink Payload (prefix 0x01):
745 745  
746 746  (% class="box infomessage" %)
747 747  (((
... ... @@ -754,7 +754,7 @@
754 754  
755 755  Set work mode.
756 756  
757 -* (% style="color:#037691" %)**AT Command:**
811 +* AT Command:
758 758  
759 759  (% class="box infomessage" %)
760 760  (((
... ... @@ -764,7 +764,7 @@
764 764  **Example**: AT+MOD=2. Set work mode to Double DI counting mode
765 765  
766 766  
767 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x0A):**
821 +* Downlink Payload (prefix 0x0A):
768 768  
769 769  (% class="box infomessage" %)
770 770  (((
... ... @@ -775,12 +775,12 @@
775 775  
776 776  ==== 3.4.2.3 Poll an uplink ====
777 777  
778 -* (% style="color:#037691" %)AT Command:
832 +* AT Command:
779 779  
780 780  There is no AT Command to poll uplink
781 781  
782 782  
783 -* (% style="color:#037691" %)Downlink Payload (prefix 0x08):
837 +* Downlink Payload (prefix 0x08):
784 784  
785 785  (% class="box infomessage" %)
786 786  (((
... ... @@ -795,7 +795,7 @@
795 795  
796 796  Use of trigger mode, please check [[ADDMOD6>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
797 797  
798 -* (% style="color:#037691" %)AT Command:
852 +* AT Command:
799 799  
800 800  (% class="box infomessage" %)
801 801  (((
... ... @@ -807,7 +807,7 @@
807 807  0: Disable Trigger Mode
808 808  
809 809  
810 -* (% style="color:#037691" %)Downlink Payload (prefix 0x0A 06):
864 +* Downlink Payload (prefix 0x0A 06):
811 811  
812 812  (% class="box infomessage" %)
813 813  (((
... ... @@ -820,12 +820,12 @@
820 820  
821 821  Poll trigger settings,
822 822  
823 -* (% style="color:#037691" %)AT Command:
877 +* AT Command:
824 824  
825 825  There is no AT Command for this feature.
826 826  
827 827  
828 -* (% style="color:#037691" %)Downlink Payload (prefix 0x AB 06):
882 +* Downlink Payload (prefix 0x AB 06):
829 829  
830 830  (% class="box infomessage" %)
831 831  (((
... ... @@ -838,9 +838,12 @@
838 838  
839 839  Enable Disable DI1/DI2/DI2 as trigger,
840 840  
841 -* (% style="color:#037691" %)AT Command:
895 +* AT Command:
842 842  
897 +(% class="box infomessage" %)
898 +(((
843 843  **Format: AT+DTRI=<DI1_TIRGGER_FlAG>,< DI2_TIRGGER_FlAG >**
900 +)))
844 844  
845 845  
846 846  **Example:**
... ... @@ -847,20 +847,25 @@
847 847  
848 848  AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
849 849  
850 -* (% style="color:#037691" %)Downlink Payload (prefix 0xAA 02):
907 +* Downlink Payload (prefix 0xAA 02):
851 851  
852 -**0xAA 02 aa bb        **~/~/ Same as AT+DTRI=aa,bb
909 +(% class="box infomessage" %)
910 +(((
911 +**0xAA 02 aa bb  ~/~/ Same as AT+DTRI=aa,bb**
912 +)))
853 853  
854 854  
855 855  
856 -
857 857  ==== 3.4.2.7 Trigger1 – Set DI1 or DI3 as trigger ====
858 858  
859 859  Set DI1 or DI3(for LT-33222-L) trigger.
860 860  
861 -* (% style="color:#037691" %)AT Command:
920 +* AT Command:
862 862  
922 +(% class="box infomessage" %)
923 +(((
863 863  **AT+TRIG1=a,b**
925 +)))
864 864  
865 865  a : Interrupt mode. 0: falling edge; 1: rising edge, 2: falling and raising edge(for MOD=1).
866 866  
... ... @@ -872,20 +872,26 @@
872 872  AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms )
873 873  
874 874  
875 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x09 01 ):**
876 -* **0x09 01 aa bb cc    ** ~/~/ same as AT+TRIG1=aa,0x(bb cc)
937 +* Downlink Payload (prefix 0x09 01 ):
877 877  
939 +(% class="box infomessage" %)
940 +(((
941 +**0x09 01 aa bb cc ~/~/ same as AT+TRIG1=aa,0x(bb cc)**
942 +)))
878 878  
879 879  
945 +
880 880  ==== 3.4.2.8 Trigger2 – Set DI2 as trigger ====
881 881  
882 882  Set DI2 trigger.
883 883  
884 -* (% style="color:#037691" %)**AT Command:**
950 +* AT Command:
885 885  
952 +(% class="box infomessage" %)
953 +(((
886 886  **AT+TRIG2=a,b**
955 +)))
887 887  
888 -
889 889  a : Interrupt mode. 0: falling edge; 1: rising edge, 2: falling and raising edge(for MOD=1).
890 890  
891 891  b : delay timing.
... ... @@ -896,72 +896,93 @@
896 896  AT+TRIG2=0,100(set DI1 port to trigger on low level, valid signal is 100ms )
897 897  
898 898  
899 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x09 02 ):**
967 +* Downlink Payload (prefix 0x09 02 ):
900 900  
901 -**0x09 02 aa bb cc           **~/~/ same as AT+TRIG1=aa,0x(bb cc)
969 +(% class="box infomessage" %)
970 +(((
971 +**0x09 02 aa bb cc ~/~/ same as AT+TRIG1=aa,0x(bb cc)**
972 +)))
902 902  
903 903  
904 904  
905 -
906 906  ==== 3.4.2.9 Trigger – Set AC (current) as trigger ====
907 907  
908 908  Set current trigger , base on AC port. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
909 909  
910 -* (% style="color:#037691" %)**AT Command**
980 +* AT Command:
911 911  
912 -**AT+ACLIM**
982 +(% class="box infomessage" %)
983 +(((
984 +**AT+ACLIM. **
985 +)))
913 913  
914 914  
915 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xAA 01 )**
988 +* Downlink Payload (prefix 0xAA 01 ):
916 916  
917 -**0x AA 01 aa bb cc dd ee ff gg hh        ** ~/~/ same as AT+ACLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
990 +(% class="box infomessage" %)
991 +(((
992 +**0x AA 01 aa bb cc dd ee ff gg hh ~/~/ same as AT+ACLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
993 +)))
918 918  
919 919  
920 920  
921 -
922 922  ==== 3.4.2.10 Trigger – Set AV (voltage) as trigger ====
923 923  
924 924  Set current trigger , base on AV port. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
925 925  
926 -* (% style="color:#037691" %)**AT Command**
1001 +* AT Command:
927 927  
928 -**AT+AVLIM  See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
1003 +(% class="box infomessage" %)
1004 +(((
1005 +**AT+AVLIM. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
1006 +)))
929 929  
930 930  
931 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xAA 00 )**
1009 +* Downlink Payload (prefix 0xAA 00 ):
932 932  
933 -**0x AA 00 aa bb cc dd ee ff gg hh    ** ~/~/ same as AT+AVLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1011 +(% class="box infomessage" %)
1012 +(((
1013 +**0x AA 00 aa bb cc dd ee ff gg hh ~/~/ same as AT+AVLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]] **
1014 +)))
934 934  
935 935  
936 936  
937 -
938 938  ==== 3.4.2.11 Trigger – Set minimum interval ====
939 939  
940 940  Set AV and AC trigger minimum interval, system won’t response to the second trigger within this set time after the first trigger.
941 941  
942 -* (% style="color:#037691" %)**AT Command**
1022 +* AT Command:
943 943  
1024 +(% class="box infomessage" %)
1025 +(((
944 944  **AT+ATDC=5. Device won’t response the second trigger within 5 minute after the first trigger.**
1027 +)))
945 945  
946 946  
947 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xAC )**
1030 +* Downlink Payload (prefix 0xAC ):
948 948  
949 -**0x AC aa bb   ** ~/~/ same as AT+ATDC=0x(aa bb)   . Unit (min)
1032 +(% class="box infomessage" %)
1033 +(((
1034 +**0x AC aa bb ~/~/ same as AT+ATDC=0x(aa bb)   . Unit (min)**
1035 +)))
950 950  
951 951  
952 952  
953 -
954 954  ==== 3.4.2.12 DO ~-~- Control Digital Output DO1/DO2/DO3 ====
955 955  
956 -* (% style="color:#037691" %)**AT Command**
1041 +* AT Command:
957 957  
958 958  There is no AT Command to control Digital Output
959 959  
960 960  
961 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x02)**
962 -* **0x02 aa bb cc     **~/~/ Set DO1/DO2/DO3 output
1046 +* Downlink Payload (prefix 0x02):
963 963  
1048 +(% class="box infomessage" %)
964 964  (((
1050 +**0x02 aa bb cc     ~/~/ Set DO1/DO2/DO3 output**
1051 +)))
1052 +
1053 +(((
965 965  If payload = 0x02010001, while there is load between V+ and DOx, it means set DO1 to low, DO2 to high and DO3 to low.
966 966  )))
967 967  
... ... @@ -981,19 +981,22 @@
981 981  
982 982  
983 983  
984 -
985 985  ==== 3.4.2.13 DO ~-~- Control Digital Output DO1/DO2/DO3 with time control ====
986 986  
987 -* (% style="color:#037691" %)**AT Command**
1075 +* AT Command:
988 988  
989 989  There is no AT Command to control Digital Output
990 990  
991 991  
992 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xA9)**
1080 +* Downlink Payload (prefix 0xA9):
993 993  
994 -**0xA9 aa bb cc     **~/~/ Set DO1/DO2/DO3 output with time control
1082 +(% class="box infomessage" %)
1083 +(((
1084 +(((
1085 +**0xA9 aa bb cc     ~/~/ Set DO1/DO2/DO3 output with time control**
1086 +)))
1087 +)))
995 995  
996 -
997 997  This is to control the digital output time of DO pin. Include four bytes:
998 998  
999 999  (% style="color:#4f81bd" %)**First Byte**(%%)**:** Type code (0xA9)
... ... @@ -1047,19 +1047,20 @@
1047 1047  
1048 1048  
1049 1049  
1050 -
1051 1051  ==== 3.4.2.14 Relay ~-~- Control Relay Output RO1/RO2 ====
1052 1052  
1053 -* (% style="color:#037691" %)**AT Command:**
1144 +* AT Command:
1054 1054  
1055 1055  There is no AT Command to control Relay Output
1056 1056  
1057 1057  
1058 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x03):**
1149 +* Downlink Payload (prefix 0x03):
1059 1059  
1060 -**0x03 aa bb     **~/~/ Set RO1/RO2 output
1151 +(% class="box infomessage" %)
1152 +(((
1153 +**0x03 aa bb     ~/~/ Set RO1/RO2 output**
1154 +)))
1061 1061  
1062 -
1063 1063  (((
1064 1064  If payload = 0x030100, it means set RO1 to close and RO2 to open.
1065 1065  )))
... ... @@ -1076,19 +1076,20 @@
1076 1076  
1077 1077  
1078 1078  
1079 -
1080 1080  ==== 3.4.2.15 Relay ~-~- Control Relay Output RO1/RO2 with time control ====
1081 1081  
1082 -* (% style="color:#037691" %)**AT Command:**
1174 +* AT Command:
1083 1083  
1084 1084  There is no AT Command to control Relay Output
1085 1085  
1086 1086  
1087 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x05):**
1179 +* Downlink Payload (prefix 0x05):
1088 1088  
1089 -**0x05 aa bb cc dd     **~/~/ Set RO1/RO2 relay with time control
1181 +(% class="box infomessage" %)
1182 +(((
1183 +**0x05 aa bb cc dd     ~/~/ Set RO1/RO2 relay with time control:**
1184 +)))
1090 1090  
1091 -
1092 1092  This is to control the relay output time of relay. Include four bytes:
1093 1093  
1094 1094  (% style="color:#4f81bd" %)**First Byte **(%%)**:** Type code (0x05)
... ... @@ -1130,28 +1130,35 @@
1130 1130  
1131 1131  
1132 1132  
1133 -
1134 1134  ==== 3.4.2.16 Counting ~-~- Voltage threshold counting ====
1135 1135  
1136 1136  When voltage exceed the threshold, count. Feature see [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]
1137 1137  
1138 -* (% style="color:#037691" %)**AT Command:**
1231 +* AT Command:
1139 1139  
1140 -(% style="color:#037691" %)**​​​​​​​**(%%)**AT+VOLMAX   ** ~/~/ See [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]
1233 +(% class="box infomessage" %)
1234 +(((
1235 +**AT+VOLMAX    ~/~/ See [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]**
1236 +)))
1141 1141  
1142 1142  
1143 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xA5):**
1239 +* Downlink Payload (prefix 0xA5):
1144 1144  
1145 -**0xA5 aa bb cc   **~/~/ Same as AT+VOLMAX=(aa bb),cc
1241 +(% class="box infomessage" %)
1242 +(((
1243 +**0xA5 aa bb cc   ~/~/ Same as AT+VOLMAX=(aa bb),cc**
1244 +)))
1146 1146  
1147 1147  
1148 1148  
1149 -
1150 1150  ==== 3.4.2.17 Counting ~-~- Pre-configure the Count Number ====
1151 1151  
1152 -* (% style="color:#037691" %)**AT Command:**
1250 +* AT Command:
1153 1153  
1154 -(% style="color:#037691" %)**​​​​​​​​​​​​​​**(%%)**AT+SETCNT=aa,(bb cc dd ee) **
1252 +(% class="box infomessage" %)
1253 +(((
1254 +**AT+SETCNT=aa,(bb cc dd ee) **
1255 +)))
1155 1155  
1156 1156  aa: 1: Set count1,
1157 1157  
... ... @@ -1162,40 +1162,51 @@
1162 1162  Bb cc dd ee: number to be set
1163 1163  
1164 1164  
1165 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xA8):**
1266 +* Downlink Payload (prefix 0xA8):
1166 1166  
1167 -**0x A8 aa bb cc dd ee     **~/~/ same as AT+SETCNT=aa,(bb cc dd ee)
1268 +(% class="box infomessage" %)
1269 +(((
1270 +**0x A8 aa bb cc dd ee     ~/~/ same as AT+SETCNT=aa,(bb cc dd ee)**
1271 +)))
1168 1168  
1169 1169  
1170 1170  
1171 -
1172 1172  ==== 3.4.2.18 Counting ~-~- Clear Counting ====
1173 1173  
1174 1174  Clear counting for counting mode
1175 1175  
1176 -* (% style="color:#037691" %)**AT Command:**
1279 +* AT Command:
1177 1177  
1178 -(% style="color:#037691" %)​​​​​​​​​​​​​​(%%)**AT+CLRCOUNT ** ~/~/ clear all counting
1281 +(% class="box infomessage" %)
1282 +(((
1283 +**AT+CLRCOUNT ~/~/ clear all counting**
1284 +)))
1179 1179  
1286 +* Downlink Payload (prefix 0xA6):
1180 1180  
1181 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xA6):**
1288 +(% class="box infomessage" %)
1289 +(((
1290 +**0x A6 01     ~/~/ clear all counting,**
1291 +)))
1182 1182  
1183 -**0x A6 01    ** ~/~/ clear all counting
1184 1184  
1185 1185  
1186 -
1187 -
1188 1188  ==== 3.4.2.19 Counting ~-~- Change counting mode save time ====
1189 1189  
1190 -* (% style="color:#037691" %)**AT Command:**
1297 +* AT Command:
1191 1191  
1192 -**AT+COUTIME=60  **~/~/ Set save time to 60 seconds. Device will save the counting result in internal flash every 60 seconds. (min value: 30)
1299 +(% class="box infomessage" %)
1300 +(((
1301 +**AT+COUTIME=60  ~/~/ Set save time to 60 seconds. Device will save the counting result in internal flash every 60 seconds. (min value: 30)**
1302 +)))
1193 1193  
1304 +* Downlink Payload (prefix 0xA7):
1194 1194  
1195 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xA7):**
1306 +(% class="box infomessage" %)
1307 +(((
1308 +**0x A7 aa bb cc     ~/~/ same as AT+COUTIME =aa bb cc,**
1309 +)))
1196 1196  
1197 -**0x A7 aa bb cc     **~/~/ same as AT+COUTIME =aa bb cc,
1198 -
1199 1199  (((
1200 1200  range: aa bb cc:0 to 16777215,  (unit:second)
1201 1201  
... ... @@ -1203,7 +1203,6 @@
1203 1203  )))
1204 1204  
1205 1205  
1206 -
1207 1207  == 3.5 Integrate with Mydevice ==
1208 1208  
1209 1209  Mydevices provides a human friendly interface to show the sensor data, once we have data in TTN, we can use Mydevices to connect to TTN and see the data in Mydevices. Below are the steps:
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0