... ... @@ -275,7 +275,6 @@
275 275  * **MOD5**: Single DI Counting + 2 x AVI + 1 x ACI + DO + RO
276 276  * **ADDMOD6**: Trigger Mode, Optional, used together with MOD1 ~~ MOD5
277 277  
278 -
279 279  === 3.3.1 AT+MOD~=1, 2ACI+2AVI ===
280 280  
281 281  The uplink payload includes totally 9 bytes. Uplink packets use FPORT=2 and every 10 minutes send one uplink by default.
... ... @@ -283,8 +283,6 @@
283 283  [[image:image-20220523174024-3.png]]
284 284  
285 285  (((
286 -
287 -
288 288  (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
289 289  )))
290 290  
... ... @@ -298,7 +298,6 @@
298 298  
299 299  For example if payload is: [[image:image-20220523175847-2.png]]
300 300  
301 -
302 302  **The value for the interface is:  **
303 303  
304 304  AVI1 channel voltage is 0x04AB/1000=1195(DEC)/1000=1.195V
... ... @@ -314,8 +314,6 @@
314 314  * [1] RO1 relay channel is close and the RO1 LED is ON.
315 315  * [0] RO2 relay channel is open and RO2 LED is OFF;
316 316  
317 -
318 -
319 319  **LT22222-L:**
320 320  
321 321  * [1] DI2 channel is high input and DI2 LED is ON;
... ... @@ -331,10 +331,8 @@
331 331  ** DO1 is high in case there is load between DO1 and V+.
332 332  ** DO1 LED is off in both case
333 333  
334 -
335 335  === 3.3.2 AT+MOD~=2, (Double DI Counting) ===
336 336  
337 -
338 338  **For LT-22222-L**: this mode the **DI1 and DI2** are used as counting pins.
339 339  
340 340  (((
... ... @@ -343,7 +343,6 @@
343 343  
344 344  [[image:image-20220523180452-3.png]]
345 345  
346 -
347 347  (((
348 348  (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DO3, DO2 and DO1. Totally 1bytes as below
349 349  )))
... ... @@ -359,8 +359,6 @@
359 359  )))
360 360  
361 361  (((
362 -
363 -
364 364  **To use counting mode, please run:**
365 365  )))
366 366  
... ... @@ -379,8 +379,6 @@
379 379  )))
380 380  
381 381  (((
382 -
383 -
384 384  (% style="color:#4f81bd" %)**AT Commands for counting:**
385 385  )))
386 386  
... ... @@ -477,9 +477,9 @@
477 477  )))
478 478  
479 479  
467 +
480 480  === 3.3.4 AT+MOD~=4, Single DI Counting + 1 x Voltage Counting ===
481 481  
482 -
483 483  **LT22222-L**: This mode the DI1 is used as a counting pin.
484 484  
485 485  The AVI1 is also used for counting. AVI1 is used to monitor the voltage. It will check the voltage **every 60s**, if voltage is higher or lower than VOLMAX mV, the AVI1 Counting increase 1, so AVI1 counting can be used to measure a machine working hour.
... ... @@ -486,7 +486,6 @@
486 486  
487 487  [[image:image-20220523181903-8.png]]
488 488  
489 -
490 490  (((
491 491  (% style="color:#4f81bd" %)**DIDORO **(%%)is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
492 492  )))
... ... @@ -567,7 +567,6 @@
567 567  
568 568  === 3.3.5 AT+MOD~=5, Single DI Counting + 2 x AVI + 1 x ACI ===
569 569  
570 -
571 571  **LT22222-L**: This mode the DI1 is used as a counting pin.
572 572  
573 573  [[image:image-20220523182334-9.png]]
... ... @@ -616,7 +616,6 @@
616 616  
617 617  === 3.3.6 AT+ADDMOD~=6. (Trigger Mode, Optional) ===
618 618  
619 -
620 620  (% style="color:#4f81bd" %)**This mode is an optional mode for trigger purpose. It can run together with other mode.**
621 621  
622 622  For example, if user has configured below commands:
... ... @@ -631,7 +631,6 @@
631 631  1. Trigger uplink when meet the trigger condition. LT will sent two packets in this case, the first uplink use payload specify in this mod (mod=6), the second packets use the normal mod payload(MOD=1 for above settings). Both Uplinks use LoRaWAN (% style="color:#4f81bd" %)**CONFIRMED data type.**
632 632  
633 633  
634 -
635 635  **AT Command to set Trigger Condition**:
636 636  
637 637  (% style="color:#4f81bd" %)**Trigger base on voltage**:
... ... @@ -645,7 +645,6 @@
645 645  AT+AVLIM=5000,0,0,0   (If AVI1 voltage lower than 5V , trigger uplink, 0 means ignore)
646 646  
647 647  
648 -
649 649  (% style="color:#4f81bd" %)**Trigger base on current**:
650 650  
651 651  Format: AT+ACLIM=<AC1_LIMIT_LOW>,< AC1_LIMIT_HIGH>,<AC2_LIMIT_LOW>,< AC2_LIMIT_HIGH>
... ... @@ -655,7 +655,6 @@
655 655  AT+ACLIM=10000,15000,0,0   (If ACI1 voltage lower than 10mA or higher than 15mA, trigger an uplink)
656 656  
657 657  
658 -
659 659  (% style="color:#4f81bd" %)**Trigger base on DI status**:
660 660  
661 661  DI status trigger Flag.
... ... @@ -662,13 +662,12 @@
662 662  
663 663  Format: AT+DTRI=<DI1_TIRGGER_FlAG>,< DI2_TIRGGER_FlAG >
664 664  
665 -
666 666  **Example:**
667 667  
668 668  AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
669 669  
670 670  
671 -**Downlink Command to set Trigger Condition:**
651 +**Downlink Command to set Trigger Condition**
672 672  
673 673  Type Code: 0xAA. Downlink command same as AT Command **AT+AVLIM, AT+ACLIM**
674 674  
... ... @@ -697,7 +697,6 @@
697 697  Same as AT+ DTRI =1,0  (Enable DI1 trigger / disable DI2 trigger)
698 698  
699 699  
700 -
701 701  (% style="color:#4f81bd" %)**Trigger Settings Payload Explanation:**
702 702  
703 703  MOD6 Payload : total 11 bytes payload
... ... @@ -712,7 +712,6 @@
712 712  * Each bits shows if the corresponding trigger has been configured.
713 713  
714 714  
715 -
716 716  **Example:**
717 717  
718 718  10100000: Means the system has configure to use the trigger: AC1_LOW and AV2_LOW
... ... @@ -725,7 +725,6 @@
725 725  * Each bits shows which status has been trigger on this uplink.
726 726  
727 727  
728 -
729 729  **Example:**
730 730  
731 731  10000000: Means this packet is trigger by AC1_LOW. Means voltage too low.
... ... @@ -738,7 +738,6 @@
738 738  * Each bits shows which status has been trigger on this uplink.
739 739  
740 740  
741 -
742 742  **Example:**
743 743  
744 744  00000111: Means both DI1 and DI2 trigger are enabled and this packet is trigger by DI1.
... ... @@ -759,8 +759,6 @@
759 759  === 3.3.7 Payload Decoder ===
760 760  
761 761  (((
762 -
763 -
764 764  **Decoder for TTN/loraserver/ChirpStack**: [[http:~~/~~/www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/Payload_decoder/>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/Payload_decoder/]]