... ... @@ -273,6 +273,7 @@
273 273  [[image:1653298044601-602.png||height="405" width="709"]]
274 274  
275 275  
276 +
276 276  == 3.3 Uplink Payload ==
277 277  
278 278  There are five working modes + one interrupt mode on LT for different type application:
... ... @@ -284,6 +284,8 @@
284 284  * **MOD5**: Single DI Counting + 2 x AVI + 1 x ACI + DO + RO
285 285  * **ADDMOD6**: Trigger Mode, Optional, used together with MOD1 ~~ MOD5
286 286  
288 +
289 +
287 287  === 3.3.1 AT+MOD~=1, 2ACI+2AVI ===
288 288  
289 289  The uplink payload includes totally 9 bytes. Uplink packets use FPORT=2 and every 10 minutes send one uplink by default.
... ... @@ -319,6 +319,7 @@
319 319  * [1] RO1 relay channel is close and the RO1 LED is ON.
320 320  * [0] RO2 relay channel is open and RO2 LED is OFF;
321 321  
325 +
322 322  **LT22222-L:**
323 323  
324 324  * [1] DI2 channel is high input and DI2 LED is ON;
... ... @@ -334,6 +334,8 @@
334 334  ** DO1 is high in case there is load between DO1 and V+.
335 335  ** DO1 LED is off in both case
336 336  
341 +
342 +
337 337  === 3.3.2 AT+MOD~=2, (Double DI Counting) ===
338 338  
339 339  **For LT-22222-L**: this mode the **DI1 and DI2** are used as counting pins.
... ... @@ -427,6 +427,7 @@
427 427  )))
428 428  
429 429  
436 +
430 430  === 3.3.3 AT+MOD~=3, Single DI Counting + 2 x ACI ===
431 431  
432 432  **LT22222-L**: This mode the DI1 is used as a counting pin.
... ... @@ -471,6 +471,8 @@
471 471  
472 472  )))
473 473  
481 +
482 +
474 474  === 3.3.4 AT+MOD~=4, Single DI Counting + 1 x Voltage Counting ===
475 475  
476 476  **LT22222-L**: This mode the DI1 is used as a counting pin.
... ... @@ -552,6 +552,7 @@
552 552  )))
553 553  
554 554  
564 +
555 555  === 3.3.5 AT+MOD~=5, Single DI Counting + 2 x AVI + 1 x ACI ===
556 556  
557 557  **LT22222-L**: This mode the DI1 is used as a counting pin.
... ... @@ -596,6 +596,8 @@
596 596  
597 597  )))
598 598  
609 +
610 +
599 599  === 3.3.6 AT+ADDMOD~=6. (Trigger Mode, Optional) ===
600 600  
601 601  (% style="color:#4f81bd" %)**This mode is an optional mode for trigger purpose. It can run together with other mode.**
... ... @@ -719,6 +719,7 @@
719 719  When device got this command, it will send the MOD6 payload.
720 720  
721 721  
734 +
722 722  === 3.3.7 Payload Decoder ===
723 723  
724 724  (((
... ... @@ -727,6 +727,8 @@
727 727  
728 728  )))
729 729  
743 +
744 +
730 730  == 3.4 ​Configure LT via AT or Downlink ==
731 731  
732 732  User can configure LT I/O Controller via AT Commands or LoRaWAN Downlink Commands
... ... @@ -739,11 +739,14 @@
739 739  
740 740  * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for LT-22222-L.  User can see these commands below:
741 741  
757 +
758 +
742 742  === 3.4.1 Common Commands ===
743 743  
744 744  They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
745 745  
746 746  
764 +
747 747  === 3.4.2 Sensor related commands ===
748 748  
749 749  ==== 3.4.2.1 Set Transmit Interval ====