... ... @@ -666,7 +666,6 @@
666 666  
667 667  Same as AT+ DTRI =1,0  (Enable DI1 trigger / disable DI2 trigger)
668 668  
669 -
670 670  (% style="color:#4f81bd" %)**Trigger Settings Payload Explanation:**
671 671  
672 672  MOD6 Payload : total 11 bytes payload
... ... @@ -673,7 +673,6 @@
673 673  
674 674  [[image:image-20220524085923-1.png]]
675 675  
676 -
677 677  (% style="color:#4f81bd" %)**TRI FLAG1**(%%) is a combination to show if trigger is set for this part. Totally 1byte as below
678 678  
679 679  [[image:image-20220524090106-2.png]]
... ... @@ -680,7 +680,6 @@
680 680  
681 681  * Each bits shows if the corresponding trigger has been configured.
682 682  
683 -
684 684  **Example:**
685 685  
686 686  10100000: Means the system has configure to use the trigger: AC1_LOW and AV2_LOW
... ... @@ -692,7 +692,6 @@
692 692  
693 693  * Each bits shows which status has been trigger on this uplink.
694 694  
695 -
696 696  **Example:**
697 697  
698 698  10000000: Means this packet is trigger by AC1_LOW. Means voltage too low.
... ... @@ -743,8 +743,6 @@
743 743  
744 744  * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for LT-22222-L.  User can see these commands below:
745 745  
746 -
747 -
748 748  === 3.4.1 Common Commands ===
749 749  
750 750  They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
... ... @@ -766,7 +766,6 @@
766 766  
767 767  **Example: **AT+TDC=30000. Means set interval to 30 seconds
768 768  
769 -
770 770  * Downlink Payload (prefix 0x01):
771 771  
772 772  (% class="box infomessage" %)
... ... @@ -789,7 +789,6 @@
789 789  
790 790  **Example**: AT+MOD=2. Set work mode to Double DI counting mode
791 791  
792 -
793 793  * Downlink Payload (prefix 0x0A):
794 794  
795 795  (% class="box infomessage" %)
... ... @@ -805,7 +805,6 @@
805 805  
806 806  There is no AT Command to poll uplink
807 807  
808 -
809 809  * Downlink Payload (prefix 0x08):
810 810  
811 811  (% class="box infomessage" %)
... ... @@ -832,7 +832,6 @@
832 832  
833 833  0: Disable Trigger Mode
834 834  
835 -
836 836  * Downlink Payload (prefix 0x0A 06):
837 837  
838 838  (% class="box infomessage" %)
... ... @@ -850,7 +850,6 @@
850 850  
851 851  There is no AT Command for this feature.
852 852  
853 -
854 854  * Downlink Payload (prefix 0x AB 06):
855 855  
856 856  (% class="box infomessage" %)
... ... @@ -871,7 +871,6 @@
871 871  **Format: AT+DTRI=<DI1_TIRGGER_FlAG>,< DI2_TIRGGER_FlAG >**
872 872  )))
873 873  
874 -
875 875  **Example:**
876 876  
877 877  AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
... ... @@ -900,12 +900,10 @@
900 900  
901 901  b : delay timing.
902 902  
903 -
904 904  **Example:**
905 905  
906 906  AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms )
907 907  
908 -
909 909  * Downlink Payload (prefix 0x09 01 ):
910 910  
911 911  (% class="box infomessage" %)
... ... @@ -930,12 +930,10 @@
930 930  
931 931  b : delay timing.
932 932  
933 -
934 934  **Example:**
935 935  
936 936  AT+TRIG2=0,100(set DI1 port to trigger on low level, valid signal is 100ms )
937 937  
938 -
939 939  * Downlink Payload (prefix 0x09 02 ):
940 940  
941 941  (% class="box infomessage" %)
... ... @@ -956,7 +956,6 @@
956 956  **AT+ACLIM. **
957 957  )))
958 958  
959 -
960 960  * Downlink Payload (prefix 0xAA 01 ):
961 961  
962 962  (% class="box infomessage" %)
... ... @@ -977,7 +977,6 @@
977 977  **AT+AVLIM. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
978 978  )))
979 979  
980 -
981 981  * Downlink Payload (prefix 0xAA 00 ):
982 982  
983 983  (% class="box infomessage" %)
... ... @@ -998,7 +998,6 @@
998 998  **AT+ATDC=5. Device won’t response the second trigger within 5 minute after the first trigger.**
999 999  )))
1000 1000  
1001 -
1002 1002  * Downlink Payload (prefix 0xAC ):
1003 1003  
1004 1004  (% class="box infomessage" %)
... ... @@ -1014,7 +1014,6 @@
1014 1014  
1015 1015  There is no AT Command to control Digital Output
1016 1016  
1017 -
1018 1018  * Downlink Payload (prefix 0x02):
1019 1019  
1020 1020  (% class="box infomessage" %)
... ... @@ -1048,7 +1048,6 @@
1048 1048  
1049 1049  There is no AT Command to control Digital Output
1050 1050  
1051 -
1052 1052  * Downlink Payload (prefix 0xA9):
1053 1053  
1054 1054  (% class="box infomessage" %)
... ... @@ -1068,22 +1068,18 @@
1068 1068  
1069 1069  00: DO pins will change to an inverter state after timeout 
1070 1070  
1071 -
1072 1072  (% style="color:#4f81bd" %)**Third Byte**(%%): Control Method and Ports status:
1073 1073  
1074 1074  [[image:image-20220524093238-6.png]]
1075 1075  
1076 -
1077 1077  (% style="color:#4f81bd" %)**Fourth Byte**(%%): Control Method and Ports status:
1078 1078  
1079 1079  [[image:image-20220524093328-7.png]]
1080 1080  
1081 -
1082 1082  (% style="color:#4f81bd" %)**Fifth Byte**(%%): Control Method and Ports status:
1083 1083  
1084 1084  [[image:image-20220524093351-8.png]]
1085 1085  
1086 -
1087 1087  (% style="color:#4f81bd" %)**Sixth and Seventh Byte**:
1088 1088  
1089 1089   Latching time. Unit: ms
... ... @@ -1090,7 +1090,6 @@
1090 1090  
1091 1091  Device will upload a packet if downlink code executes successfully.
1092 1092  
1093 -
1094 1094  **Example payload:**
1095 1095  
1096 1096  **~1. A9 01 01 01 01 07 D0**
... ... @@ -1111,13 +1111,12 @@
1111 1111  
1112 1112  
1113 1113  
1114 -==== 3.4.2.14 Relay ~-~- Control Relay Output RO1/RO2 ====
1088 +=== 3.4.2.14 Relay ~-~- Control Relay Output RO1/RO2 ===
1115 1115  
1116 1116  * AT Command:
1117 1117  
1118 1118  There is no AT Command to control Relay Output
1119 1119  
1120 -
1121 1121  * Downlink Payload (prefix 0x03):
1122 1122  
1123 1123  (% class="box infomessage" %)
... ... @@ -1147,7 +1147,6 @@
1147 1147  
1148 1148  There is no AT Command to control Relay Output
1149 1149  
1150 -
1151 1151  * Downlink Payload (prefix 0x05):
1152 1152  
1153 1153  (% class="box infomessage" %)
... ... @@ -1165,17 +1165,14 @@
1165 1165  
1166 1166  00: Relays will change to an inverter state after timeout
1167 1167  
1168 -
1169 1169  (% style="color:#4f81bd" %)**Third Byte(bb)**(%%): Control Method and Ports status:
1170 1170  
1171 1171  [[image:image-20220524093831-10.png]]
1172 1172  
1173 -
1174 1174  (% style="color:#4f81bd" %)**Fourth/Fifth Bytes(cc)**(%%): Latching time. Unit: ms
1175 1175  
1176 1176  Device will upload a packet if downlink code executes successfully.
1177 1177  
1178 -
1179 1179  **Example payload:**
1180 1180  
1181 1181  **~1. 05 01 11 07 D0**
... ... @@ -1207,7 +1207,6 @@
1207 1207  **AT+VOLMAX    ~/~/ See [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]**
1208 1208  )))
1209 1209  
1210 -
1211 1211  * Downlink Payload (prefix 0xA5):
1212 1212  
1213 1213  (% class="box infomessage" %)
... ... @@ -1234,7 +1234,6 @@
1234 1234  
1235 1235  Bb cc dd ee: number to be set
1236 1236  
1237 -
1238 1238  * Downlink Payload (prefix 0xA8):
1239 1239  
1240 1240  (% class="box infomessage" %)
... ... @@ -1287,16 +1287,17 @@
1287 1287  )))
1288 1288  
1289 1289  
1257 +
1290 1290  == 3.5 Integrate with Mydevice ==
1291 1291  
1292 1292  Mydevices provides a human friendly interface to show the sensor data, once we have data in TTN, we can use Mydevices to connect to TTN and see the data in Mydevices. Below are the steps:
1293 1293  
1294 1294  (((
1295 -(% style="color:blue" %)**Step 1**(%%): Be sure that your device is programmed and properly connected to the network at this time.
1263 +**Step 1**: Be sure that your device is programmed and properly connected to the network at this time.
1296 1296  )))
1297 1297  
1298 1298  (((
1299 -(% style="color:blue" %)**Step 2**(%%): To configure the Application to forward data to Mydevices you will need to add integration. To add the Mydevices integration, perform the following steps:
1267 +**Step 2**: To configure the Application to forward data to Mydevices you will need to add integration. To add the Mydevices integration, perform the following steps:
1300 1300  )))
1301 1301  
1302 1302  [[image:1653356737703-362.png||height="232" width="732"]]
... ... @@ -1303,13 +1303,12 @@
1303 1303  
1304 1304  [[image:image-20220524094641-11.png||height="390" width="723"]]
1305 1305  
1306 -
1307 1307  [[image:image-20220524094641-12.png||height="402" width="718"]]
1308 1308  
1309 1309  
1310 -(% style="color:blue" %)**Step 3**(%%): Create an account or log in Mydevices.
1277 +**Step 3**: Create an account or log in Mydevices.
1311 1311  
1312 -(% style="color:blue" %)**Step 4**(%%): Search LT-22222-L(for both LT-22222-L / LT-33222-L) and add DevEUI.(% style="display:none" %)
1279 +**Step 4**: Search LT-22222-L(for both LT-22222-L / LT-33222-L) and add DevEUI.(% style="display:none" %)
1313 1313  
1314 1314  Search under The things network
1315 1315  