Last modified by Mengting Qiu on 2025/06/04 18:42

From version 77.65
edited by Xiaoling
on 2022/06/10 09:19
Change comment: There is no comment for this version
To version 77.57
edited by Xiaoling
on 2022/06/10 09:09
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -888,12 +888,10 @@
888 888  
889 889  b : delay timing.
890 890  
891 -
892 892  **Example:**
893 893  
894 894  AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms )
895 895  
896 -
897 897  * Downlink Payload (prefix 0x09 01 ):
898 898  
899 899  (% class="box infomessage" %)
... ... @@ -918,12 +918,10 @@
918 918  
919 919  b : delay timing.
920 920  
921 -
922 922  **Example:**
923 923  
924 924  AT+TRIG2=0,100(set DI1 port to trigger on low level, valid signal is 100ms )
925 925  
926 -
927 927  * Downlink Payload (prefix 0x09 02 ):
928 928  
929 929  (% class="box infomessage" %)
... ... @@ -944,7 +944,6 @@
944 944  **AT+ACLIM. **
945 945  )))
946 946  
947 -
948 948  * Downlink Payload (prefix 0xAA 01 ):
949 949  
950 950  (% class="box infomessage" %)
... ... @@ -965,7 +965,6 @@
965 965  **AT+AVLIM. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
966 966  )))
967 967  
968 -
969 969  * Downlink Payload (prefix 0xAA 00 ):
970 970  
971 971  (% class="box infomessage" %)
... ... @@ -986,7 +986,6 @@
986 986  **AT+ATDC=5. Device won’t response the second trigger within 5 minute after the first trigger.**
987 987  )))
988 988  
989 -
990 990  * Downlink Payload (prefix 0xAC ):
991 991  
992 992  (% class="box infomessage" %)
... ... @@ -1002,7 +1002,6 @@
1002 1002  
1003 1003  There is no AT Command to control Digital Output
1004 1004  
1005 -
1006 1006  * Downlink Payload (prefix 0x02):
1007 1007  
1008 1008  (% class="box infomessage" %)
... ... @@ -1036,7 +1036,6 @@
1036 1036  
1037 1037  There is no AT Command to control Digital Output
1038 1038  
1039 -
1040 1040  * Downlink Payload (prefix 0xA9):
1041 1041  
1042 1042  (% class="box infomessage" %)
... ... @@ -1056,22 +1056,18 @@
1056 1056  
1057 1057  00: DO pins will change to an inverter state after timeout 
1058 1058  
1059 -
1060 1060  (% style="color:#4f81bd" %)**Third Byte**(%%): Control Method and Ports status:
1061 1061  
1062 1062  [[image:image-20220524093238-6.png]]
1063 1063  
1064 -
1065 1065  (% style="color:#4f81bd" %)**Fourth Byte**(%%): Control Method and Ports status:
1066 1066  
1067 1067  [[image:image-20220524093328-7.png]]
1068 1068  
1069 -
1070 1070  (% style="color:#4f81bd" %)**Fifth Byte**(%%): Control Method and Ports status:
1071 1071  
1072 1072  [[image:image-20220524093351-8.png]]
1073 1073  
1074 -
1075 1075  (% style="color:#4f81bd" %)**Sixth and Seventh Byte**:
1076 1076  
1077 1077   Latching time. Unit: ms
... ... @@ -1078,7 +1078,6 @@
1078 1078  
1079 1079  Device will upload a packet if downlink code executes successfully.
1080 1080  
1081 -
1082 1082  **Example payload:**
1083 1083  
1084 1084  **~1. A9 01 01 01 01 07 D0**
... ... @@ -1105,7 +1105,6 @@
1105 1105  
1106 1106  There is no AT Command to control Relay Output
1107 1107  
1108 -
1109 1109  * Downlink Payload (prefix 0x03):
1110 1110  
1111 1111  (% class="box infomessage" %)
... ... @@ -1135,7 +1135,6 @@
1135 1135  
1136 1136  There is no AT Command to control Relay Output
1137 1137  
1138 -
1139 1139  * Downlink Payload (prefix 0x05):
1140 1140  
1141 1141  (% class="box infomessage" %)
... ... @@ -1153,17 +1153,14 @@
1153 1153  
1154 1154  00: Relays will change to an inverter state after timeout
1155 1155  
1156 -
1157 1157  (% style="color:#4f81bd" %)**Third Byte(bb)**(%%): Control Method and Ports status:
1158 1158  
1159 1159  [[image:image-20220524093831-10.png]]
1160 1160  
1161 -
1162 1162  (% style="color:#4f81bd" %)**Fourth/Fifth Bytes(cc)**(%%): Latching time. Unit: ms
1163 1163  
1164 1164  Device will upload a packet if downlink code executes successfully.
1165 1165  
1166 -
1167 1167  **Example payload:**
1168 1168  
1169 1169  **~1. 05 01 11 07 D0**
... ... @@ -1195,7 +1195,6 @@
1195 1195  **AT+VOLMAX    ~/~/ See [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]**
1196 1196  )))
1197 1197  
1198 -
1199 1199  * Downlink Payload (prefix 0xA5):
1200 1200  
1201 1201  (% class="box infomessage" %)
... ... @@ -1222,7 +1222,6 @@
1222 1222  
1223 1223  Bb cc dd ee: number to be set
1224 1224  
1225 -
1226 1226  * Downlink Payload (prefix 0xA8):
1227 1227  
1228 1228  (% class="box infomessage" %)
... ... @@ -1275,16 +1275,17 @@
1275 1275  )))
1276 1276  
1277 1277  
1257 +
1278 1278  == 3.5 Integrate with Mydevice ==
1279 1279  
1280 1280  Mydevices provides a human friendly interface to show the sensor data, once we have data in TTN, we can use Mydevices to connect to TTN and see the data in Mydevices. Below are the steps:
1281 1281  
1282 1282  (((
1283 -(% style="color:blue" %)**Step 1**(%%): Be sure that your device is programmed and properly connected to the network at this time.
1263 +**Step 1**: Be sure that your device is programmed and properly connected to the network at this time.
1284 1284  )))
1285 1285  
1286 1286  (((
1287 -(% style="color:blue" %)**Step 2**(%%): To configure the Application to forward data to Mydevices you will need to add integration. To add the Mydevices integration, perform the following steps:
1267 +**Step 2**: To configure the Application to forward data to Mydevices you will need to add integration. To add the Mydevices integration, perform the following steps:
1288 1288  )))
1289 1289  
1290 1290  [[image:1653356737703-362.png||height="232" width="732"]]
... ... @@ -1291,13 +1291,12 @@
1291 1291  
1292 1292  [[image:image-20220524094641-11.png||height="390" width="723"]]
1293 1293  
1294 -
1295 1295  [[image:image-20220524094641-12.png||height="402" width="718"]]
1296 1296  
1297 1297  
1298 -(% style="color:blue" %)**Step 3**(%%): Create an account or log in Mydevices.
1277 +**Step 3**: Create an account or log in Mydevices.
1299 1299  
1300 -(% style="color:blue" %)**Step 4**(%%): Search LT-22222-L(for both LT-22222-L / LT-33222-L) and add DevEUI.(% style="display:none" %)
1279 +**Step 4**: Search LT-22222-L(for both LT-22222-L / LT-33222-L) and add DevEUI.(% style="display:none" %)
1301 1301  
1302 1302  Search under The things network
1303 1303  
... ... @@ -1304,21 +1304,16 @@
1304 1304  [[image:1653356838789-523.png||height="337" width="740"]]
1305 1305  
1306 1306  
1307 -
1308 1308  After added, the sensor data arrive TTN, it will also arrive and show in Mydevices.
1309 1309  
1310 1310  [[image:image-20220524094909-1.png||height="335" width="729"]]
1311 1311  
1312 -
1313 1313  [[image:image-20220524094909-2.png||height="337" width="729"]]
1314 1314  
1315 -
1316 1316  [[image:image-20220524094909-3.png||height="338" width="727"]]
1317 1317  
1318 -
1319 1319  [[image:image-20220524094909-4.png||height="339" width="728"]](% style="display:none" %)
1320 1320  
1321 -
1322 1322  [[image:image-20220524094909-5.png||height="341" width="734"]]
1323 1323  
1324 1324  
... ... @@ -1358,7 +1358,7 @@
1358 1358  )))
1359 1359  
1360 1360  (((
1361 -(% style="color:blue" %)**Example1**(%%): Connect to a Low active sensor.
1335 +**Example1**: Connect to a Low active sensor.
1362 1362  )))
1363 1363  
1364 1364  (((
... ... @@ -1389,7 +1389,7 @@
1389 1389  )))
1390 1390  
1391 1391  (((
1392 -(% style="color:blue" %)**Example2**(%%): Connect to a High active sensor.
1366 +**Example2**: Connect to a High active sensor.
1393 1393  )))
1394 1394  
1395 1395  (((
... ... @@ -1420,7 +1420,7 @@
1420 1420  )))
1421 1421  
1422 1422  (((
1423 -(% style="color:blue" %)**Example3**(%%): Connect to a 220v high active sensor.
1397 +**Example3**: Connect to a 220v high active sensor.
1424 1424  )))
1425 1425  
1426 1426  (((