... ... @@ -19,6 +19,8 @@
19 19  == 1.1 What is LT Series I/O Controller ==
20 20  
21 21  (((
22 +
23 +
22 22  The Dragino (% style="color:blue" %)**LT series I/O Modules**(%%) are Long Range LoRaWAN I/O Controller. It contains different I/O Interfaces such as:** (% style="color:blue" %)analog current Input, analog voltage input(%%)**(% style="color:blue" %), **relay output**, **digital input**(%%) and (% style="color:blue" %)**digital output**(%%) etc. The LT I/O Modules are designed to simplify the installation of I/O monitoring.
23 23  )))
24 24  
... ... @@ -48,6 +48,7 @@
48 48  
49 49  )))
50 50  
53 +
51 51  == 1.2  Specifications ==
52 52  
53 53  (((
... ... @@ -76,6 +76,8 @@
76 76  )))
77 77  
78 78  (((
82 +
83 +
79 79  **Interface for Model: LT22222-L:**
80 80  )))
81 81  
... ... @@ -99,6 +99,8 @@
99 99  )))
100 100  
101 101  (((
107 +
108 +
102 102  **LoRa Spec:**
103 103  )))
104 104  
... ... @@ -159,6 +159,8 @@
159 159  * (((
160 160  Packet engine up to 256 bytes with CRC.
161 161  
169 +
170 +
162 162  
163 163  )))
164 164  
... ... @@ -194,7 +194,6 @@
194 194  * 1 x Counting Port
195 195  )))
196 196  
197 -
198 198  = 2. Power ON Device =
199 199  
200 200  The LT controller can be powered by 7 ~~ 24V DC power source. Connect VIN to Power Input V+ and GND to power input V- to power the LT controller.
... ... @@ -275,8 +275,6 @@
275 275  * **MOD5**: Single DI Counting + 2 x AVI + 1 x ACI + DO + RO
276 276  * **ADDMOD6**: Trigger Mode, Optional, used together with MOD1 ~~ MOD5
277 277  
278 -
279 -
280 280  === 3.3.1 AT+MOD~=1, 2ACI+2AVI ===
281 281  
282 282  The uplink payload includes totally 9 bytes. Uplink packets use FPORT=2 and every 10 minutes send one uplink by default.
... ... @@ -315,7 +315,6 @@
315 315  * [1] RO1 relay channel is close and the RO1 LED is ON.
316 316  * [0] RO2 relay channel is open and RO2 LED is OFF;
317 317  
318 -
319 319  **LT22222-L:**
320 320  
321 321  * [1] DI2 channel is high input and DI2 LED is ON;
... ... @@ -331,8 +331,6 @@
331 331  ** DO1 is high in case there is load between DO1 and V+.
332 332  ** DO1 LED is off in both case
333 333  
334 -
335 -
336 336  === 3.3.2 AT+MOD~=2, (Double DI Counting) ===
337 337  
338 338  
... ... @@ -473,11 +473,10 @@
473 473  
474 474  (((
475 475  Other AT Commands for counting are similar to [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]].
476 -
477 -
478 478  )))
479 479  
480 480  
482 +
481 481  === 3.3.4 AT+MOD~=4, Single DI Counting + 1 x Voltage Counting ===
482 482  
483 483  
... ... @@ -630,7 +630,6 @@
630 630  1. Periodically uplink (Base on TDC time). Payload is same as the normal MOD (MOD 1 for above command). This uplink uses LoRaWAN (% style="color:#4f81bd" %)**unconfirmed**(%%) data type
631 631  1. Trigger uplink when meet the trigger condition. LT will sent two packets in this case, the first uplink use payload specify in this mod (mod=6), the second packets use the normal mod payload(MOD=1 for above settings). Both Uplinks use LoRaWAN (% style="color:#4f81bd" %)**CONFIRMED data type.**
632 632  
633 -
634 634  **AT Command to set Trigger Condition**:
635 635  
636 636  (% style="color:#4f81bd" %)**Trigger base on voltage**:
... ... @@ -710,7 +710,6 @@
710 710  
711 711  * Each bits shows if the corresponding trigger has been configured.
712 712  
713 -
714 714  **Example:**
715 715  
716 716  10100000: Means the system has configure to use the trigger: AC1_LOW and AV2_LOW
... ... @@ -722,7 +722,6 @@
722 722  
723 723  * Each bits shows which status has been trigger on this uplink.
724 724  
725 -
726 726  **Example:**
727 727  
728 728  10000000: Means this packet is trigger by AC1_LOW. Means voltage too low.
... ... @@ -734,7 +734,6 @@
734 734  
735 735  * Each bits shows which status has been trigger on this uplink.
736 736  
737 -
738 738  **Example:**
739 739  
740 740  00000111: Means both DI1 and DI2 trigger are enabled and this packet is trigger by DI1.
... ... @@ -763,7 +763,6 @@
763 763  )))
764 764  
765 765  
766 -
767 767  == 3.4 ​Configure LT via AT or Downlink ==
768 768  
769 769  User can configure LT I/O Controller via AT Commands or LoRaWAN Downlink Commands
... ... @@ -776,7 +776,6 @@
776 776  
777 777  * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for LT-22222-L.  User can see these commands below:
778 778  
779 -
780 780  === 3.4.1 Common Commands ===
781 781  
782 782  They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
... ... @@ -2008,8 +2008,16 @@
2008 2008  )))
2009 2009  
2010 2010  (((
2011 -
2007 +== 5.6 Why does the relay output become the default and open relay after the lt22222 is powered off? ==
2012 2012  
2009 +If the device is not shut down, but directly powered off.
2010 +
2011 +It will default that this is a power-off state.
2012 +
2013 +In modes 2 to 5, DO RO status and pulse count are saved in flash.
2014 +
2015 +After restart, the status before power failure will be read from flash.
2016 +
2013 2013  = 6. Trouble Shooting =