... ... @@ -230,13 +230,12 @@
230 230  
231 231  [[image:image-20220523172350-1.png||height="266" width="864"]]
232 232  
233 -
234 234  (((
235 235  The LG308 is already set to connect to [[TTN network >>url:https://www.thethingsnetwork.org/]]. So what we need to do now is only configure register this device to TTN:
236 236  )))
237 237  
238 238  (((
239 -(% style="color:blue" %)**Step 1**(%%): Create a device in TTN with the OTAA keys from LT IO controller.
238 +**Step 1**: Create a device in TTN with the OTAA keys from LT IO controller.
240 240  )))
241 241  
242 242  (((
... ... @@ -245,7 +245,6 @@
245 245  
246 246  [[image:1653297924498-393.png]]
247 247  
248 -
249 249  Input these keys in the LoRaWAN Server portal. Below is TTN screen shot:
250 250  
251 251  Add APP EUI in the application.
... ... @@ -259,7 +259,7 @@
259 259  
260 260  
261 261  (((
262 -(% style="color:blue" %)**Step 2**(%%): Power on LT and it will auto join to the TTN network. After join success, it will start to upload message to TTN and user can see in the panel.
260 +**Step 2**: Power on LT and it will auto join to the TTN network. After join success, it will start to upload message to TTN and user can see in the panel.
263 263  )))
264 264  
265 265  [[image:1653298044601-602.png||height="405" width="709"]]
... ... @@ -277,7 +277,6 @@
277 277  * **MOD5**: Single DI Counting + 2 x AVI + 1 x ACI + DO + RO
278 278  * **ADDMOD6**: Trigger Mode, Optional, used together with MOD1 ~~ MOD5
279 279  
280 -
281 281  === 3.3.1 AT+MOD~=1, 2ACI+2AVI ===
282 282  
283 283  The uplink payload includes totally 9 bytes. Uplink packets use FPORT=2 and every 10 minutes send one uplink by default.
... ... @@ -285,8 +285,6 @@
285 285  [[image:image-20220523174024-3.png]]
286 286  
287 287  (((
288 -
289 -
290 290  (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
291 291  )))
292 292  
... ... @@ -300,7 +300,6 @@
300 300  
301 301  For example if payload is: [[image:image-20220523175847-2.png]]
302 302  
303 -
304 304  **The value for the interface is:  **
305 305  
306 306  AVI1 channel voltage is 0x04AB/1000=1195(DEC)/1000=1.195V
... ... @@ -316,7 +316,6 @@
316 316  * [1] RO1 relay channel is close and the RO1 LED is ON.
317 317  * [0] RO2 relay channel is open and RO2 LED is OFF;
318 318  
319 -
320 320  **LT22222-L:**
321 321  
322 322  * [1] DI2 channel is high input and DI2 LED is ON;
... ... @@ -332,10 +332,8 @@
332 332  ** DO1 is high in case there is load between DO1 and V+.
333 333  ** DO1 LED is off in both case
334 334  
335 -
336 336  === 3.3.2 AT+MOD~=2, (Double DI Counting) ===
337 337  
338 -
339 339  **For LT-22222-L**: this mode the **DI1 and DI2** are used as counting pins.
340 340  
341 341  (((
... ... @@ -344,7 +344,6 @@
344 344  
345 345  [[image:image-20220523180452-3.png]]
346 346  
347 -
348 348  (((
349 349  (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DO3, DO2 and DO1. Totally 1bytes as below
350 350  )))
... ... @@ -360,8 +360,6 @@
360 360  )))
361 361  
362 362  (((
363 -
364 -
365 365  **To use counting mode, please run:**
366 366  )))
367 367  
... ... @@ -380,8 +380,6 @@
380 380  )))
381 381  
382 382  (((
383 -
384 -
385 385  (% style="color:#4f81bd" %)**AT Commands for counting:**
386 386  )))
387 387  
... ... @@ -478,9 +478,9 @@
478 478  )))
479 479  
480 480  
467 +
481 481  === 3.3.4 AT+MOD~=4, Single DI Counting + 1 x Voltage Counting ===
482 482  
483 -
484 484  **LT22222-L**: This mode the DI1 is used as a counting pin.
485 485  
486 486  The AVI1 is also used for counting. AVI1 is used to monitor the voltage. It will check the voltage **every 60s**, if voltage is higher or lower than VOLMAX mV, the AVI1 Counting increase 1, so AVI1 counting can be used to measure a machine working hour.
... ... @@ -487,7 +487,6 @@
487 487  
488 488  [[image:image-20220523181903-8.png]]
489 489  
490 -
491 491  (((
492 492  (% style="color:#4f81bd" %)**DIDORO **(%%)is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
493 493  )))
... ... @@ -568,7 +568,6 @@
568 568  
569 569  === 3.3.5 AT+MOD~=5, Single DI Counting + 2 x AVI + 1 x ACI ===
570 570  
571 -
572 572  **LT22222-L**: This mode the DI1 is used as a counting pin.
573 573  
574 574  [[image:image-20220523182334-9.png]]
... ... @@ -617,7 +617,6 @@
617 617  
618 618  === 3.3.6 AT+ADDMOD~=6. (Trigger Mode, Optional) ===
619 619  
620 -
621 621  (% style="color:#4f81bd" %)**This mode is an optional mode for trigger purpose. It can run together with other mode.**
622 622  
623 623  For example, if user has configured below commands:
... ... @@ -625,6 +625,7 @@
625 625  * **AT+MOD=1 ** **~-~->** The normal working mode
626 626  * **AT+ADDMOD6=1**   **~-~->** Enable trigger
627 627  
611 +
628 628  LT will keep monitoring AV1/AV2/AC1/AC2 every 5 seconds; LT will send uplink packets in two cases:
629 629  
630 630  1. Periodically uplink (Base on TDC time). Payload is same as the normal MOD (MOD 1 for above command). This uplink uses LoRaWAN (% style="color:#4f81bd" %)**unconfirmed**(%%) data type
... ... @@ -644,7 +644,6 @@
644 644  AT+AVLIM=5000,0,0,0   (If AVI1 voltage lower than 5V , trigger uplink, 0 means ignore)
645 645  
646 646  
647 -
648 648  (% style="color:#4f81bd" %)**Trigger base on current**:
649 649  
650 650  Format: AT+ACLIM=<AC1_LIMIT_LOW>,< AC1_LIMIT_HIGH>,<AC2_LIMIT_LOW>,< AC2_LIMIT_HIGH>
... ... @@ -654,7 +654,6 @@
654 654  AT+ACLIM=10000,15000,0,0   (If ACI1 voltage lower than 10mA or higher than 15mA, trigger an uplink)
655 655  
656 656  
657 -
658 658  (% style="color:#4f81bd" %)**Trigger base on DI status**:
659 659  
660 660  DI status trigger Flag.
... ... @@ -661,13 +661,12 @@
661 661  
662 662  Format: AT+DTRI=<DI1_TIRGGER_FlAG>,< DI2_TIRGGER_FlAG >
663 663  
664 -
665 665  **Example:**
666 666  
667 667  AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
668 668  
669 669  
670 -**Downlink Command to set Trigger Condition:**
651 +**Downlink Command to set Trigger Condition**
671 671  
672 672  Type Code: 0xAA. Downlink command same as AT Command **AT+AVLIM, AT+ACLIM**
673 673  
... ... @@ -696,7 +696,6 @@
696 696  Same as AT+ DTRI =1,0  (Enable DI1 trigger / disable DI2 trigger)
697 697  
698 698  
699 -
700 700  (% style="color:#4f81bd" %)**Trigger Settings Payload Explanation:**
701 701  
702 702  MOD6 Payload : total 11 bytes payload
... ... @@ -755,8 +755,6 @@
755 755  === 3.3.7 Payload Decoder ===
756 756  
757 757  (((
758 -
759 -
760 760  **Decoder for TTN/loraserver/ChirpStack**: [[http:~~/~~/www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/Payload_decoder/>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/Payload_decoder/]]
761 761  
762 762  
... ... @@ -777,6 +777,7 @@
777 777  * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for LT-22222-L.  User can see these commands below:
778 778  
779 779  
758 +
780 780  === 3.4.1 Common Commands ===
781 781  
782 782  They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]