... ... @@ -1100,11 +1100,11 @@
1100 1100  * Connect sensor’s output to DI1-
1101 1101  * Connect sensor’s VCC to DI1+.
1102 1102  
1103 -So when sensor active, the current between NEC2501 pin1 and pin2 is: ​​
1103 +So when sensor active, the current between NEC2501 pin1 and pin2 is:
1104 1104  
1105 - //IF// = DI1+ / 1K.
1105 + //IF//[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image021.png]] = DI1+ / 1K.
1106 1106  
1107 -If DI1+ = 12v, the //IF// = 12mA , So the LT-22222-L will be able to detect this active signal.
1107 +If DI1+ = 12v, the //IF//[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image022.png]] = 12mA , So the LT-22222-L will be able to detect this active signal.
1108 1108  
1109 1109  
1110 1110  **Example2**: Connect to a High active sensor.
... ... @@ -1116,12 +1116,12 @@
1116 1116  
1117 1117  So when sensor active, the current between NEC2501 pin1 and pin2 is:
1118 1118  
1119 -[[image:/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LT-22222-L/WebHome/image-20220524095628-8.png]]** [[image:image-20220524095628-8.png]]= DI1+ / 1K.**
1119 + //IF//[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image021.png]] = DI1+ / 1K.
1120 1120  
1121 -If **DI1+ = 24v**, the [[image:/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LT-22222-L/WebHome/image-20220524095628-8.png]]**[[image:image-20220524095628-8.png]]** = 24mA , So the LT-22222-L will be able to detect this high active signal.
1121 +If DI1+ = 24v, the //IF//[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image022.png]] = 24mA , So the LT-22222-L will be able to detect this high active signal.
1122 1122  
1123 1123  
1124 -**Example3**: Connect to a 220v high active sensor.
1124 +**Example3**: Connect to a 220v high active sensor.公司测试一下
1125 1125  
1126 1126  Assume user want to monitor an active signal higher than 220v, to make sure not burn the photocoupler  
1127 1127  
... ... @@ -1130,15 +1130,18 @@
1130 1130  
1131 1131  So when sensor active, the current between NEC2501 pin1 and pin2 is:
1132 1132  
1133 - [[image:/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LT-22222-L/WebHome/image-20220524095628-8.png]]**[[image:image-20220524095628-8.png]] = DI1+ / 51K.**
1133 + //IF//[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image021.png]] = DI1+ / 51K.
1134 1134  
1135 -If sensor output is 220v, the (% id="cke_bm_243359S" style="display:none" %) [[image:image-20220524095628-8.png]](%%) = DI1+ / 51K.  = 4.3mA , So the LT-22222-L will be able to detect this high active signal safely.
1135 +If sensor output is 220v, the //IF//[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image022.png]] = 4.3mA , So the LT-22222-L will be able to detect this high active signal safely.
1136 1136  
1137 -=== 3.6.3 Digital Output Port: DO1/DO2 /DO3 ===
1138 1138  
1138 +1.
1139 +11.
1140 +111. Digital Output Port: DO1/DO2 /DO3
1141 +
1139 1139  NPN output: GND or Float. Max voltage can apply to output pin is 36v.
1140 1140  
1141 -[[image:1653357531600-905.png]]
1144 +[[image:file:///C:/Users/93456/AppData/Local/Temp/msohtmlclip1/01/clip_image023.png]]
1142 1142  
1143 1143  
1144 1144  
1653357592296-182.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Xiaoling
Size
... ... @@ -1,1 +1,0 @@
1 -42.2 KB
Content
1653357640609-758.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Xiaoling
Size
... ... @@ -1,1 +1,0 @@
1 -558.1 KB
Content
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0