Changes for page LT-22222-L -- LoRa I/O Controller User Manual
Last modified by Mengting Qiu on 2025/06/04 18:42
From version 243.11
edited by Xiaoling
on 2025/03/20 15:55
on 2025/03/20 15:55
Change comment:
There is no comment for this version
To version 249.1
edited by Mengting Qiu
on 2025/05/23 16:52
on 2025/05/23 16:52
Change comment:
There is no comment for this version
Summary
-
Page properties (2 modified, 0 added, 0 removed)
Details
- Page properties
-
- Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. Xiaoling1 +XWiki.ting - Content
-
... ... @@ -1511,9 +1511,9 @@ 1511 1511 |(% style="width:113px" %)**Parameters**|(% style="width:384px" %)((( 1512 1512 **RO1_status** : 1 byte in hex 1513 1513 1514 -00: Close1514 +00: Open 1515 1515 1516 -01: Open1516 +01: Close 1517 1517 1518 1518 11: No action 1519 1519 ... ... @@ -1520,9 +1520,9 @@ 1520 1520 1521 1521 **RO2_status** : 1 byte in hex 1522 1522 1523 -00: Close1523 +00: Open 1524 1524 1525 -01: Open1525 +01: Close 1526 1526 1527 1527 11: No action 1528 1528 ))) ... ... @@ -1542,7 +1542,6 @@ 1542 1542 (% style="color:red" %)**The device will transmit an uplink packet if the downlink payload is executed successfully.** 1543 1543 ))) 1544 1544 1545 - 1546 1546 ==== 3.4.2.15 Relay ~-~- Control Relay Output RO1/RO2 with time control ==== 1547 1547 1548 1548 ... ... @@ -1674,7 +1674,6 @@ 1674 1674 If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1 1675 1675 ))) 1676 1676 1677 - 1678 1678 ==== 3.4.2.17 Counting ~-~- Pre-configure the Count Number ==== 1679 1679 1680 1680 ... ... @@ -1725,7 +1725,6 @@ 1725 1725 Sets the COUNT1 to 10. 1726 1726 ))) 1727 1727 1728 - 1729 1729 ==== 3.4.2.18 Counting ~-~- Clear Counting ==== 1730 1730 1731 1731 ... ... @@ -1748,11 +1748,12 @@ 1748 1748 ))) 1749 1749 |(% style="width:141px" %)**Example**|(% style="width:357px" %)A6 **01** 1750 1750 1751 -==== 3.4.2.19 Counting ~-~-SetSaving Intervalfor'CountingResult'====1748 +==== 3.4.2.19 Set the save intervals of the counting results, RO (Relay Output), and DO (Digital Output) states ==== 1752 1752 1750 +This command configures the device to periodically save the counting results, RO (Relay Output), and DO (Digital Output) states to internal flash memory at a user-defined interval. By setting a save interval, the device ensures that critical data (counting values and output states) is preserved in case of power loss. 1751 +The save interval can be adjusted to the user's needs, with a minimum value of (% style="color:blue" %)**30**(%%) seconds. 1752 +The saved RO/DO states can be restored after a device reset by combining this function with the (% style="color:blue" %)**AT+RODORESET**(%%) command. 1753 1753 1754 -This command allows you to configure the device to save its counting result to internal flash memory at specified intervals. By setting a save time, the device will periodically store the counting data to prevent loss in case of power failure. The save interval can be adjusted to suit your requirements, with a minimum value of 30 seconds. 1755 - 1756 1756 (% style="color:#037691" %)**AT Command** 1757 1757 1758 1758 (% border="2" style="width:500px" %) ... ... @@ -1762,7 +1762,7 @@ 1762 1762 |(% style="width:124px" %)**Example**|(% style="width:374px" %)((( 1763 1763 AT+COUTIME=60 1764 1764 1765 -Sets the device to save its counting results to the memory every 60 seconds. 1763 +Sets the device to save its counting results, RO and DO states to the memory every 60 seconds. 1766 1766 ))) 1767 1767 1768 1768 (% style="color:#037691" %)**Downlink Payload** ... ... @@ -1777,7 +1777,7 @@ 1777 1777 |(% style="width:123px" %)**Example**|(% style="width:375px" %)((( 1778 1778 A7 **00 00 3C** 1779 1779 1780 -Sets the device to save its counting results to the memory every 60 seconds. 1778 +SSets the device to save its counting results, RO and DO states to the memory every 60 seconds. 1781 1781 ))) 1782 1782 1783 1783 ==== 3.4.2.20 Reset saved RO and DO states ====