... ... @@ -115,6 +115,23 @@
115 115  * Smart cities
116 116  * Smart factory
117 117  
118 +== 1.5 Hardware Variants ==
119 +
120 +(% style="width:524px" %)
121 +|(% style="width:94px" %)**Model**|(% style="width:98px" %)**Photo**|(% style="width:329px" %)**Description**
122 +|(% style="width:94px" %)**LT33222-L**|(% style="width:98px" %)(((
123 +[[image:/xwiki/bin/downloadrev/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LT-22222-L/WebHome/image-20230424115112-1.png?rev=1.1&width=58&height=106||alt="image-20230424115112-1.png" height="106" width="58"]]
124 +)))|(% style="width:329px" %)(((
125 +* 2 x Digital Input (Bi-direction)
126 +* 2 x Digital Output
127 +* 2 x Relay Output (5A@250VAC / 30VDC)
128 +* 2 x 0~~20mA Analog Input (res:0.01mA)
129 +* 2 x 0~~30V Analog Input (res:0.01v)
130 +* 1 x Counting Port
131 +)))
132 +
133 +
134 +
118 118  == 2. Assembling the device ==
119 119  
120 120  == 2.1 Connecting the antenna ==
... ... @@ -556,13 +556,13 @@
556 556  )))
557 557  
558 558  (((
559 -Other AT Commands for counting are similar to the [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]]s.
576 +AT Commands for counting are similar to the [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]]s.
560 560  )))
561 561  
562 562  (((
563 563  **In addition to that, below are the commands for AVI1 Counting:**
564 564  
565 -(% style="color:blue" %)**AT+SETCNT=3,60 **(%%)**(Sets AVI Count to 60)**
582 +(% style="color:blue" %)**AT+SETCNT=3,60 **(%%)**(Sets AVI1 Count to 60)**
566 566  
567 567  (% style="color:blue" %)**AT+VOLMAX=20000 **(%%)**(If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1)**
568 568  
... ... @@ -977,7 +977,7 @@
977 977  (% border="2" style="width:500px" %)
978 978  |(% style="width:97px" %)**Payload**|(% style="width:401px" %)<prefix><enable/disable trigger_mode>
979 979  |(% style="width:97px" %)**Parameters**|(% style="width:401px" %)(((
980 -**prefix** : 0x0A 06
997 +**prefix** : 0x0A 06 (two bytes in hexadecimal)
981 981  
982 982  **working mode** : enable (1) or disable (0), represented by 1 byte in hexadecimal.
983 983  )))
... ... @@ -999,7 +999,7 @@
999 999  
1000 1000  (% border="2" style="width:500px" %)
1001 1001  |(% style="width:95px" %)**Payload**|(% style="width:403px" %)<prefix>
1002 -|(% style="width:95px" %)**Parameters**|(% style="width:403px" %)**prefix **: AB 06
1019 +|(% style="width:95px" %)**Parameters**|(% style="width:403px" %)**prefix **: AB 06 (two bytes in hexadecimal)
1003 1003  |(% style="width:95px" %)**Example**|(% style="width:403px" %)(((
1004 1004  AB 06
1005 1005  
... ... @@ -1040,7 +1040,7 @@
1040 1040  (% border="2" style="width:500px" %)
1041 1041  |(% style="width:101px" %)**Payload**|(% style="width:397px" %)<prefix><DI1_trigger><DI2_trigger>
1042 1042  |(% style="width:101px" %)**Parameters**|(% style="width:397px" %)(((
1043 -**prefix :** AA 02
1060 +**prefix :** AA 02 (two bytes in hexadecimal)
1044 1044  
1045 1045  **DI1_trigger:**
1046 1046  
... ... @@ -1064,20 +1064,7 @@
1064 1064  
1065 1065  Sets DI1 or DI3 (for LT-33222-L) as a trigger.
1066 1066  
1067 -* (% style="color:#037691" %)**AT Command:**(%%) (% style="color:blue" %)**AT+TRIG1=a,b**
1068 1068  
1069 -(% style="color:red" %)**a :** (%%)Interrupt mode. 0: falling edge; 1: rising edge, 2: falling and raising edge(for MOD=1).
1070 -
1071 -(% style="color:red" %)**b :** (%%)delay timing.
1072 -
1073 -**Example:** AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms )
1074 -
1075 -
1076 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x09 01 ):**
1077 -
1078 -(% style="color:blue" %)**0x09 01 aa bb cc    ** (%%) ~/~/ same as AT+TRIG1=aa,0x(bb cc)
1079 -
1080 -
1081 1081  (% style="color:#037691" %)**AT Command**
1082 1082  
1083 1083  (% border="2" style="width:500px" %)
... ... @@ -1100,7 +1100,7 @@
1100 1100  (% border="2" style="width:500px" %)
1101 1101  |(% style="width:101px" %)**Payload**|(% style="width:397px" %)<prefix><interrupt_mode><minimum_signal_duration>
1102 1102  |(% style="width:101px" %)**Parameters**|(% style="width:397px" %)(((
1103 -**prefix** : 09 01
1107 +**prefix** : 09 01 (hexadecimal)
1104 1104  
1105 1105  **interrupt_mode** : 0: falling edge; 1: rising edge, 2: falling and raising edge (for MOD=1), represented by 1 byte in hexadecimal.
1106 1106  
... ... @@ -1116,20 +1116,7 @@
1116 1116  
1117 1117  Sets DI2 as a trigger.
1118 1118  
1119 -* (% style="color:#037691" %)**AT Command:**(%%) (% style="color:blue" %)**AT+TRIG2=a,b**
1120 1120  
1121 -(% style="color:red" %)**a :** (%%)Interrupt mode. 0: falling edge; 1: rising edge, 2: falling and raising edge (for MOD=1).
1122 -
1123 -(% style="color:red" %)**b :** (%%)delay timing.
1124 -
1125 -**Example:** AT+TRIG2=0,100 (Set the DI1 port to trigger on a falling edge; the valid signal duration is 100 ms)
1126 -
1127 -
1128 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x09 02 ):**
1129 -
1130 -(% style="color:blue" %)**0x09 02 aa bb cc   ** (%%)~/~/ same as AT+TRIG2=aa,0x(bb cc)
1131 -
1132 -
1133 1133  (% style="color:#037691" %)**AT Command**
1134 1134  
1135 1135  (% border="2" style="width:500px" %)
... ... @@ -1151,7 +1151,7 @@
1151 1151  (% border="2" style="width:500px" %)
1152 1152  |(% style="width:96px" %)**Payload**|(% style="width:402px" %)<prefix><interrupt_mode><minimum_signal_duration>
1153 1153  |(% style="width:96px" %)**Parameters**|(% style="width:402px" %)(((
1154 -**prefix** : 09 02
1145 +**prefix** : 09 02 (hexadecimal)
1155 1155  
1156 1156  **interrupt_mode **: 0: falling edge; 1: rising edge, 2: falling and raising edge (for MOD=1), represented by 1 byte in hexadecimal.
1157 1157  
... ... @@ -1159,16 +1159,12 @@
1159 1159  )))
1160 1160  |(% style="width:96px" %)**Example**|(% style="width:402px" %)09 02 **00 00 64**
1161 1161  
1153 +==== ====
1154 +
1162 1162  ==== 3.4.2.9 Trigger – Set AC (current) as a trigger ====
1163 1163  
1164 1164  Sets the current trigger based on the AC port. See also [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1165 1165  
1166 -* (% style="color:#037691" %)**AT Command:**(%%) (% style="color:blue" %)**AT+ACLIM**
1167 -
1168 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xAA 01 )**
1169 -
1170 -(% style="color:blue" %)**0x AA 01 aa bb cc dd ee ff gg hh        ** (%%) ~/~/ same as AT+ACLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1171 -
1172 1172  (% style="color:#037691" %)**AT Command**
1173 1173  
1174 1174  (% border="2" style="width:500px" %)
... ... @@ -1177,13 +1177,13 @@
1177 1177  )))
1178 1178  |(% style="width:104px" %)**Response**|(% style="width:394px" %)
1179 1179  |(% style="width:104px" %)**Parameters**|(% style="width:394px" %)(((
1180 -**AC1_LIMIT_LOW** : lower limit of the current to be checked / threshold
1167 +**AC1_LIMIT_LOW** : lower limit of the current to be checked
1181 1181  
1182 -**AC1_LIMIT_HIGH **: higher limit of the current to be checked / threshold
1169 +**AC1_LIMIT_HIGH **: higher limit of the current to be checked
1183 1183  
1184 -**AC2_LIMIT_HIGH **: lower limit of the current to be checked / threshold
1171 +**AC2_LIMIT_HIGH **: lower limit of the current to be checked
1185 1185  
1186 -**AC2_LIMIT_LOW** : higher limit of the current to be checked / threshold
1173 +**AC2_LIMIT_LOW** : higher limit of the current to be checked
1187 1187  )))
1188 1188  |(% style="width:104px" %)**Example**|(% style="width:394px" %)(((
1189 1189  AT+ACLIM=10000,15000,0,0
... ... @@ -1190,6 +1190,7 @@
1190 1190  
1191 1191  Triggers an uplink if AC1 current is lower than 10mA or higher than 15mA
1192 1192  )))
1180 +|(% style="width:104px" %)Note|(% style="width:394px" %)See also, [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1193 1193  
1194 1194  (% style="color:#037691" %)**Downlink Payload**
1195 1195  
... ... @@ -1196,15 +1196,15 @@
1196 1196  (% border="2" style="width:500px" %)
1197 1197  |(% style="width:104px" %)**Payload**|(% style="width:394px" %)<prefix><AC1_LIMIT_LOW>,< AC1_LIMIT_HIGH>,<AC2_LIMIT_LOW>,< AC2_LIMIT_HIGH>
1198 1198  |(% style="width:104px" %)**Parameters**|(% style="width:394px" %)(((
1199 -**prefix **: AA 01 - two bytes in hexadecimal
1187 +**prefix **: AA 01 (hexadecimal)
1200 1200  
1201 -**AC1_LIMIT_LOW** : lower limit of the current to be checked / threshold, two bytes in hexadecimal
1189 +**AC1_LIMIT_LOW** : lower limit of the current to be checked, two bytes in hexadecimal
1202 1202  
1203 -**AC1_LIMIT_HIGH **: higher limit of the current to be checked / threshold, two bytes in hexadecimal
1191 +**AC1_LIMIT_HIGH **: higher limit of the current to be checked, two bytes in hexadecimal
1204 1204  
1205 -**AC2_LIMIT_HIGH **: lower limit of the current to be checked / threshold, two bytes in hexadecimal
1193 +**AC2_LIMIT_HIGH **: lower limit of the current to be checked, two bytes in hexadecimal
1206 1206  
1207 -**AC2_LIMIT_LOW** : higher limit of the current to be checked / threshold, two bytes in hexadecimal
1195 +**AC2_LIMIT_LOW** : higher limit of the current to be checked, two bytes in hexadecimal
1208 1208  )))
1209 1209  |(% style="width:104px" %)**Example**|(% style="width:394px" %)(((
1210 1210  AA 01 **27** **10 3A** **98** 00 00 00 00
... ... @@ -1211,69 +1211,121 @@
1211 1211  
1212 1212  Triggers an uplink if AC1 current is lower than 10mA or higher than 15mA. Set all values to zero for AC2 limits because we are only checking AC1 limits.
1213 1213  )))
1202 +|(% style="width:104px" %)Note|(% style="width:394px" %)See also, [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1214 1214  
1215 1215  ==== 3.4.2.10 Trigger – Set AV (voltage) as trigger ====
1216 1216  
1217 1217  Sets the current trigger based on the AV port. See also [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1218 1218  
1219 -* (% style="color:#037691" %)**AT Command**(%%): (% style="color:blue" %)**AT+AVLIM    **(%%)** See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
1208 +(% style="color:#037691" %)**AT Command**
1220 1220  
1221 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xAA 00 )**
1210 +(% border="2" style="width:500px" %)
1211 +|(% style="width:104px" %)**Command**|(% style="width:387px" %)AT+AVLIM= AV1_LIMIT_LOW>,< AV1_LIMIT_HIGH>,<AV2_LIMIT_LOW>,< AV2_LIMIT_HIGH>
1212 +|(% style="width:104px" %)**Response**|(% style="width:387px" %)
1213 +|(% style="width:104px" %)**Parameters**|(% style="width:387px" %)(((
1214 +**AC1_LIMIT_LOW** : lower limit of the current to be checked
1222 1222  
1223 -(% style="color:blue" %)**0x AA 00 aa bb cc dd ee ff gg hh    ** (%%) ~/~/ same as AT+AVLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1216 +**AC1_LIMIT_HIGH **: higher limit of the current to be checked
1224 1224  
1218 +**AC2_LIMIT_HIGH **: lower limit of the current to be checked
1225 1225  
1220 +**AC2_LIMIT_LOW** : higher limit of the current to be checked
1221 +)))
1222 +|(% style="width:104px" %)**Example**|(% style="width:387px" %)(((
1223 +AT+AVLIM=3000,6000,0,2000
1224 +
1225 +Triggers an uplink if AVI1 voltage is lower than 3V or higher than 6V, or if AV2 voltage is higher than 2V
1226 +)))
1227 +|(% style="width:104px" %)**Note**|(% style="width:387px" %)See also, [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1228 +
1229 +(% style="color:#037691" %)**Downlink Payload**
1230 +
1226 1226  (% border="2" style="width:500px" %)
1227 -|(% style="width:104px" %)Command|(% style="width:387px" %)AT+AVLIM= AV1_LIMIT_LOW>,< AV1_LIMIT_HIGH>,<AV2_LIMIT_LOW>,< AV2_LIMIT_HIGH>
1228 -|(% style="width:104px" %)Response|(% style="width:387px" %)
1229 -|(% style="width:104px" %)Parameters|(% style="width:387px" %)(((
1230 -**AC1_LIMIT_LOW** : lower limit of the current to be checked / threshold, two bytes in hexadecimal
1232 +|(% style="width:104px" %)**Payload**|(% style="width:394px" %)<prefix><AV1_LIMIT_LOW>,< AV1_LIMIT_HIGH>,<AV2_LIMIT_LOW>,< AV2_LIMIT_HIGH>
1233 +|(% style="width:104px" %)**Parameters**|(% style="width:394px" %)(((
1234 +**prefix **: AA 00 (hexadecimal)
1231 1231  
1232 -**AC1_LIMIT_HIGH **: higher limit of the current to be checked / threshold, two bytes in hexadecimal
1236 +**AV1_LIMIT_LOW** : lower limit of the voltage to be checked, two bytes in hexadecimal
1233 1233  
1234 -**AC2_LIMIT_HIGH **: lower limit of the current to be checked / threshold, two bytes in hexadecimal
1238 +**AV1_LIMIT_HIGH **: higher limit of the voltage to be checked, two bytes in hexadecimal
1235 1235  
1236 -**AC2_LIMIT_LOW** : higher limit of the current to be checked / threshold, two bytes in hexadecimal
1240 +**AV2_LIMIT_HIGH **: lower limit of the voltage to be checked, two bytes in hexadecimal
1241 +
1242 +**AV2_LIMIT_LOW** : higher limit of the voltage to be checked, two bytes in hexadecimal
1237 1237  )))
1238 -|(% style="width:104px" %)Example|(% style="width:387px" %)
1244 +|(% style="width:104px" %)**Example**|(% style="width:394px" %)(((
1245 +AA 00 **0B B8 17 70 00 00 07 D0**
1239 1239  
1247 +Triggers an uplink if AVI1 voltage is lower than 3V or higher than 6V, or if AV2 voltage is higher than 2V.
1248 +)))
1249 +|(% style="width:104px" %)**Note**|(% style="width:394px" %)See also, [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
1240 1240  
1241 -
1242 1242  ==== 3.4.2.11 Trigger – Set minimum interval ====
1243 1243  
1244 -Sets AV and AC trigger minimum interval. Device won't response to the second trigger within this set time after the first trigger.
1253 +Sets the AV and AC trigger minimum interval. The device won't respond to a second trigger within this set time after the first trigger.
1245 1245  
1246 -* (% style="color:#037691" %)**AT Command**(%%): (% style="color:blue" %)**AT+ATDC=5        ** ~/~/ (%%)Device won't response the second trigger within 5 minute after the first trigger.
1255 +(% style="color:#037691" %)**AT Command**
1247 1247  
1248 -* (% style="color:#037691" %)**Downlink Payload (prefix 0xAC )**
1257 +(% border="2" style="width:500px" %)
1258 +|(% style="width:113px" %)**Command**|(% style="width:385px" %)AT+ATDC=<time>
1259 +|(% style="width:113px" %)**Response**|(% style="width:385px" %)
1260 +|(% style="width:113px" %)**Parameters**|(% style="width:385px" %)(((
1261 +**time** : in minutes
1262 +)))
1263 +|(% style="width:113px" %)**Example**|(% style="width:385px" %)(((
1264 +AT+ATDC=5
1249 1249  
1250 -(% style="color:blue" %)**0x AC aa bb   **(%%) ~/~/ same as AT+ATDC=0x(aa bb)   . Unit (min)
1251 -
1252 -(((
1253 -(% style="color:red" %)**Note: ATDC setting must be more than 5min**
1266 +The device won't respond to the second trigger within 5 minutes after the first trigger.
1254 1254  )))
1268 +|(% style="width:113px" %)Note|(% style="width:385px" %)(% style="color:red" %)**The time must be greater than 5 minutes.**
1255 1255  
1270 +(% style="color:#037691" %)**Downlink Payload**
1256 1256  
1272 +(% border="2" style="width:500px" %)
1273 +|(% style="width:112px" %)**Payload**|(% style="width:386px" %)<prefix><time>
1274 +|(% style="width:112px" %)**Parameters**|(% style="width:386px" %)(((
1275 +**prefix** : AC (hexadecimal)
1257 1257  
1277 +**time **: in minutes (two bytes in hexadecimal)
1278 +)))
1279 +|(% style="width:112px" %)**Example**|(% style="width:386px" %)(((
1280 +AC **00 05**
1281 +
1282 +The device won't respond to the second trigger within 5 minutes after the first trigger.
1283 +)))
1284 +|(% style="width:112px" %)Note|(% style="width:386px" %)(% style="color:red" %)**The time must be greater than 5 minutes.**
1285 +
1258 1258  ==== 3.4.2.12 DO ~-~- Control Digital Output DO1/DO2/DO3 ====
1259 1259  
1260 1260  Controls the digital outputs DO1, DO2, and DO3
1261 1261  
1262 -* (% style="color:#037691" %)**AT Command**
1290 +(% style="color:#037691" %)**AT Command**
1263 1263  
1264 -There is no AT Command to control Digital Output
1292 +There is no AT Command to control the Digital Output.
1265 1265  
1266 1266  
1267 -* (% style="color:#037691" %)**Downlink Payload (prefix 0x02)**
1295 +(% style="color:#037691" %)**Downlink Payload**
1268 1268  
1269 -(% style="color:blue" %)**0x02 aa bb cc     ** (%%)~/~/ Set DO1/DO2/DO3 output
1297 +(% border="2" style="width:500px" %)
1298 +|(% style="width:115px" %)**Payload**|(% style="width:383px" %)<prefix><DO1><DO2><DO3>
1299 +|(% style="width:115px" %)**Parameters**|(% style="width:383px" %)(((
1300 +**prefix** : 02 (hexadecimal)
1270 1270  
1271 -(((
1272 -If payload = 0x02010001, while there is load between V+ and DOx, it means set DO1 to low, DO2 to high and DO3 to low.
1302 +**DOI** : 01: Low,  00: High, 11: No action (1 byte in hex)
1303 +
1304 +**DO2** : 01: Low,  00: High, 11: No action (1 byte in hex)
1305 +
1306 +**DO3 **: 01: Low,  00: High, 11: No action (1 byte in hex)
1273 1273  )))
1308 +|(% style="width:115px" %)**Examples**|(% style="width:383px" %)(((
1309 +02 **01 00 01**
1274 1274  
1311 +If there is a load between V+ and DOx, it means DO1 is set to low, DO2 is set to high, and DO3 is set to low.
1312 +
1313 +**More examples:**
1314 +
1275 1275  (((
1276 -01: Low,  00: High ,  11: No action
1316 +01: Low,  00: High,  11: No action
1277 1277  
1278 1278  (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:510px" %)
1279 1279  |(% style="background-color:#4f81bd; color:white" %)**Downlink Code**|(% style="background-color:#4f81bd; color:white" %)**DO1**|(% style="background-color:#4f81bd; color:white" %)**DO2**|(% style="background-color:#4f81bd; color:white" %)**DO3**
... ... @@ -1283,15 +1283,18 @@
1283 1283  )))
1284 1284  
1285 1285  (((
1286 -(% style="color:red" %)**Note: For LT-22222-L, there is no DO3, the last byte can use any value.**
1326 +(((
1327 +(% style="color:red" %)**Note: For the LT-22222-L, there is no DO3; the last byte can have any value.**
1287 1287  )))
1288 1288  
1289 1289  (((
1290 -(% style="color:red" %)**Device will upload a packet if downlink code executes successfully.**
1331 +(% style="color:red" %)**The device will upload a packet if downlink code executes successfully.**
1291 1291  )))
1333 +)))
1334 +)))
1292 1292  
1336 +==== ====
1293 1293  
1294 -
1295 1295  ==== 3.4.2.13 DO ~-~- Control Digital Output DO1/DO2/DO3 with time control ====
1296 1296  
1297 1297  
... ... @@ -1316,7 +1316,7 @@
1316 1316  00: DO pins will change to an inverter state after timeout 
1317 1317  
1318 1318  
1319 -(% style="color:#4f81bd" %)**Third Byte**(%%): Control Method and Ports status:
1362 +(% style="color:#4f81bd" %)**Third Byte**(%%): Control Method and Port status:
1320 1320  
1321 1321  (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:300px" %)
1322 1322  |(% style="background-color:#4f81bd; color:white" %)**Second Byte**|(% style="background-color:#4f81bd; color:white" %)**Status**
... ... @@ -1324,7 +1324,7 @@
1324 1324  |0x00|DO1 set to high
1325 1325  |0x11|DO1 NO Action
1326 1326  
1327 -(% style="color:#4f81bd" %)**Fourth Byte**(%%): Control Method and Ports status:
1370 +(% style="color:#4f81bd" %)**Fourth Byte**(%%): Control Method and Port status:
1328 1328  
1329 1329  (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:300px" %)
1330 1330  |(% style="background-color:#4f81bd; color:white" %)**Second Byte**|(% style="background-color:#4f81bd; color:white" %)**Status**
... ... @@ -1332,7 +1332,7 @@
1332 1332  |0x00|DO2 set to high
1333 1333  |0x11|DO2 NO Action
1334 1334  
1335 -(% style="color:#4f81bd" %)**Fifth Byte**(%%): Control Method and Ports status:
1378 +(% style="color:#4f81bd" %)**Fifth Byte**(%%): Control Method and Port status:
1336 1336  
1337 1337  (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:300px" %)
1338 1338  |(% style="background-color:#4f81bd; color:white" %)**Second Byte**|(% style="background-color:#4f81bd; color:white" %)**Status**
... ... @@ -1340,16 +1340,16 @@
1340 1340  |0x00|DO3 set to high
1341 1341  |0x11|DO3 NO Action
1342 1342  
1343 -(% style="color:#4f81bd" %)**Sixth and Seventh and Eighth and Ninth Byte**:(%%) Latching time. Unit: ms
1386 +(% style="color:#4f81bd" %)**Sixth, Seventh, Eighth, and Ninth Bytes**:(%%) Latching time (Unit: ms)
1344 1344  
1345 1345  
1346 1346  (% style="color:red" %)**Note: **
1347 1347  
1348 - Since Firmware v1.6.0, the latch time support 4 bytes and 2 bytes
1391 + Since firmware v1.6.0, the latch time support 4 bytes and 2 bytes
1349 1349  
1350 - Before Firmwre v1.6.0 the latch time only suport 2 bytes.
1393 + Before firmware v1.6.0, the latch time only supported 2 bytes.
1351 1351  
1352 -(% style="color:red" %)**Device will upload a packet if downlink code executes successfully.**
1395 +(% style="color:red" %)**Device will upload a packet if the downlink code executes successfully.**
1353 1353  
1354 1354  
1355 1355  **Example payload:**
... ... @@ -1356,22 +1356,21 @@
1356 1356  
1357 1357  **~1. A9 01 01 01 01 07 D0**
1358 1358  
1359 -DO1 pin & DO2 pin & DO3 pin will be set to Low, last 2 seconds, then change back to original state.
1402 +DO1 pin, DO2 pin, and DO3 pin will be set to low, last for 2 seconds, and then revert to their original state.
1360 1360  
1361 1361  **2. A9 01 00 01 11 07 D0**
1362 1362  
1363 -DO1 pin set high, DO2 pin set low, DO3 pin no action, last 2 seconds, then change back to original state.
1406 +DO1 pin is set to high, DO2 pin is set to low, and DO3 pin takes no action. This lasts for 2 seconds and then reverts to the original state.
1364 1364  
1365 1365  **3. A9 00 00 00 00 07 D0**
1366 1366  
1367 -DO1 pin & DO2 pin & DO3 pin will be set to high, last 2 seconds, then both change to low.
1410 +DO1 pin, DO2 pin, and DO3 pin will be set to high, last for 2 seconds, and then all change to low.
1368 1368  
1369 1369  **4. A9 00 11 01 00 07 D0**
1370 1370  
1371 -DO1 pin no action, DO2 pin set low, DO3 pin set high, last 2 seconds, then DO1 pin no action, DO2 pin set high, DO3 pin set low
1414 +DO1 pin takes no action, DO2 pin is set to low, and DO3 pin is set to high. This lasts for 2 seconds, after which DO1 pin takes no action, DO2 pin is set to high, and DO3 pin is set to low.
1372 1372  
1373 1373  
1374 -
1375 1375  ==== 3.4.2.14 Relay ~-~- Control Relay Output RO1/RO2 ====
1376 1376  
1377 1377  
... ... @@ -1386,11 +1386,11 @@
1386 1386  
1387 1387  
1388 1388  (((
1389 -If payload = 0x030100, it means set RO1 to close and RO2 to open.
1431 +If payload is 0x030100, it means setting RO1 to close and RO2 to open.
1390 1390  )))
1391 1391  
1392 1392  (((
1393 -00: Closed ,  01: Open , 11: No action
1435 +00: Close ,  01: Open , 11: No action
1394 1394  
1395 1395  (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:320px" %)
1396 1396  |(% style="background-color:#4f81bd; color:white" %)**Downlink Code**|(% style="background-color:#4f81bd; color:white" %)**RO1**|(% style="background-color:#4f81bd; color:white" %)**RO2**
... ... @@ -1407,9 +1407,9 @@
1407 1407  (% style="color:red" %)**Device will upload a packet if downlink code executes successfully.**
1408 1408  
1409 1409  
1410 -
1411 1411  ==== 3.4.2.15 Relay ~-~- Control Relay Output RO1/RO2 with time control ====
1412 1412  
1454 +Controls the relay output time.
1413 1413  
1414 1414  * (% style="color:#037691" %)**AT Command:**
1415 1415  
... ... @@ -1421,15 +1421,15 @@
1421 1421  (% style="color:blue" %)**0x05 aa bb cc dd     ** (%%)~/~/ Set RO1/RO2 relay with time control
1422 1422  
1423 1423  
1424 -This is to control the relay output time of relay. Include four bytes:
1466 +This is to control the relay output time. It includes four bytes:
1425 1425  
1426 1426  (% style="color:#4f81bd" %)**First Byte **(%%)**:** Type code (0x05)
1427 1427  
1428 1428  (% style="color:#4f81bd" %)**Second Byte(aa)**(%%): Inverter Mode
1429 1429  
1430 -01: Relays will change back to original state after timeout.
1472 +01: Relays will change back to their original state after timeout.
1431 1431  
1432 -00: Relays will change to an inverter state after timeout
1474 +00: Relays will change to the inverter state after timeout.
1433 1433  
1434 1434  
1435 1435  (% style="color:#4f81bd" %)**Third Byte(bb)**(%%): Control Method and Ports status:
... ... @@ -1442,12 +1442,12 @@
1442 1442  
1443 1443  (% style="color:red" %)**Note:**
1444 1444  
1445 - Since Firmware v1.6.0, the latch time support 4 bytes and 2 bytes
1487 + Since firmware v1.6.0, the latch time supports both 4 bytes and 2 bytes.
1446 1446  
1447 - Before Firmwre v1.6.0 the latch time only suport 2 bytes.
1489 + Before firmware v1.6.0, the latch time only supported 2 bytes.
1448 1448  
1449 1449  
1450 -(% style="color:red" %)**Device will upload a packet if downlink code executes successfully.**
1492 +(% style="color:red" %)**Device will upload a packet if the downlink code executes successfully.**
1451 1451  
1452 1452  
1453 1453  **Example payload:**
... ... @@ -1454,19 +1454,19 @@
1454 1454  
1455 1455  **~1. 05 01 11 07 D0**
1456 1456  
1457 -Relay1 and Relay 2 will be set to NC , last 2 seconds, then change back to original state.
1499 +Relay1 and Relay2 will be set to NC, lasting 2 seconds, then revert to their original state
1458 1458  
1459 1459  **2. 05 01 10 07 D0**
1460 1460  
1461 -Relay1 will change to NC, Relay2 will change to NO, last 2 seconds, then both change back to original state.
1503 +Relay1 will change to NC, Relay2 will change to NO, lasting 2 seconds, then both will revert to their original state.
1462 1462  
1463 1463  **3. 05 00 01 07 D0**
1464 1464  
1465 -Relay1 will change to NO, Relay2 will change to NC, last 2 seconds, then relay change to NC,Relay2 change to NO.
1507 +Relay1 will change to NO, Relay2 will change to NC, lasting 2 seconds, then Relay1 will change to NC, and Relay2 will change to NO.
1466 1466  
1467 1467  **4. 05 00 00 07 D0**
1468 1468  
1469 -Relay 1 & relay2 will change to NO, last 2 seconds, then both change to NC.
1511 +Relay1 and Relay2 will change to NO, lasting 2 seconds, then both will change to NC.
1470 1470  
1471 1471  
1472 1472  
... ... @@ -1473,7 +1473,7 @@
1473 1473  ==== 3.4.2.16 Counting ~-~- Voltage threshold counting ====
1474 1474  
1475 1475  
1476 -When voltage exceed the threshold, count. Feature see [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]
1518 +When the voltage exceeds the threshold, counting begins. For details, see [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]
1477 1477  
1478 1478  * (% style="color:#037691" %)**AT Command:**(%%) (% style="color:blue" %)**AT+VOLMAX   ** (%%)~/~/ See [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]
1479 1479  
... ... @@ -1482,15 +1482,76 @@
1482 1482  (% style="color:blue" %)**0xA5 aa bb cc   ** (%%)~/~/ Same as AT+VOLMAX=(aa bb),cc
1483 1483  
1484 1484  
1527 +(% style="color:#037691" %)**AT Command**
1485 1485  
1529 +(% border="2" style="width:500px" %)
1530 +|(% style="width:137px" %)**Command**|(% style="width:361px" %)AT+VOLMAX=<voltage><logic>
1531 +|(% style="width:137px" %)**Response**|(% style="width:361px" %)
1532 +|(% style="width:137px" %)**Parameters**|(% style="width:361px" %)(((
1533 +**voltage** : voltage threshold in mV
1534 +
1535 +**logic**:
1536 +
1537 +0 : lower than
1538 +
1539 +1: higher than
1540 +
1541 +if you leave logic parameter blank, it is considered 0
1542 +)))
1543 +|(% style="width:137px" %)**Examples**|(% style="width:361px" %)(((
1544 +AT+VOLMAX=20000
1545 +
1546 +If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1
1547 +
1548 +AT+VOLMAX=20000,0
1549 +
1550 +If AVI1 voltage lower than VOLMAX (20000mV =20v), counter increase 1
1551 +
1552 +AT+VOLMAX=20000,1
1553 +
1554 +If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1
1555 +)))
1556 +
1557 +(% style="color:#037691" %)**Downlink Payload**
1558 +
1559 +(% border="2" style="width:500px" %)
1560 +|(% style="width:140px" %)**Payload**|(% style="width:358px" %)<prefix><voltage><logic>
1561 +|(% style="width:140px" %)**Parameters**|(% style="width:358px" %)(((
1562 +**prefix** : A5 (hex)
1563 +
1564 +**voltage** : voltage threshold in mV (2 bytes in hex)
1565 +
1566 +**logic**: (1 byte in hexadecimal)
1567 +
1568 +0 : lower than
1569 +
1570 +1: higher than
1571 +
1572 +if you leave logic parameter blank, it is considered 1 (higher than)
1573 +)))
1574 +|(% style="width:140px" %)**Example**|(% style="width:358px" %)(((
1575 +A5 **4E 20**
1576 +
1577 +If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1
1578 +
1579 +A5 **4E 20 00**
1580 +
1581 +If AVI1 voltage lower than VOLMAX (20000mV =20v), counter increase 1
1582 +
1583 +A5 **4E 20 01**
1584 +
1585 +If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1
1586 +)))
1587 +
1486 1486  ==== 3.4.2.17 Counting ~-~- Pre-configure the Count Number ====
1487 1487  
1590 +This feature allows users to pre-configure specific count numbers for various counting parameters such as Count1, Count2, or AVI1 Count. Use the AT command to set the desired count number for each configuration.
1488 1488  
1489 1489  * (% style="color:#037691" %)**AT Command:**(%%) (% style="color:blue" %)**AT+SETCNT=aa,(bb cc dd ee) **
1490 1490  
1491 1491  (% style="color:red" %)**aa:**(%%) 1: Set count1; 2: Set count2; 3: Set AV1 count
1492 1492  
1493 -(% style="color:red" %)**bb cc dd ee: **(%%)number to be set
1596 +(% style="color:red" %)**bb cc dd ee: **(%%)The number to be set
1494 1494  
1495 1495  
1496 1496  * (% style="color:#037691" %)**Downlink Payload (prefix 0xA8):**
... ... @@ -1498,12 +1498,55 @@
1498 1498  (% style="color:blue" %)**0x A8 aa bb cc dd ee     ** (%%)~/~/ same as AT+SETCNT=aa,(bb cc dd ee)
1499 1499  
1500 1500  
1604 +(% style="color:#037691" %)**AT Command**
1501 1501  
1502 -==== 3.4.2.18 Counting ~-~- Clear Counting ====
1606 +(% border="2" style="width:500px" %)
1607 +|(% style="width:134px" %)**Command**|(% style="width:364px" %)AT+SETCNT=<counting_parameter><number>
1608 +|(% style="width:134px" %)**Response**|(% style="width:364px" %)
1609 +|(% style="width:134px" %)**Parameters**|(% style="width:364px" %)(((
1610 +**counting_parameter** :
1503 1503  
1612 +1: COUNT1
1504 1504  
1505 -Clear counting for counting mode
1614 +2: COUNT2
1506 1506  
1616 +3: AVI1 Count
1617 +
1618 +**number** : Start number
1619 +)))
1620 +|(% style="width:134px" %)**Example**|(% style="width:364px" %)(((
1621 +AT+SETCNT=1,10
1622 +
1623 +Sets the COUNT1 to 10.
1624 +)))
1625 +
1626 +(% style="color:#037691" %)**Downlink Payload**
1627 +
1628 +(% border="2" style="width:500px" %)
1629 +|(% style="width:135px" %)**Payload**|(% style="width:363px" %)<prefix><counting_parameter><number>
1630 +|(% style="width:135px" %)**Parameters**|(% style="width:363px" %)(((
1631 +prefix : A8 (hex)
1632 +
1633 +**counting_parameter** : (1 byte in hexadecimal)
1634 +
1635 +1: COUNT1
1636 +
1637 +2: COUNT2
1638 +
1639 +3: AVI1 Count
1640 +
1641 +**number** : Start number, 4 bytes in hexadecimal
1642 +)))
1643 +|(% style="width:135px" %)**Example**|(% style="width:363px" %)(((
1644 +A8 **01 00 00 00 0A**
1645 +
1646 +Sets the COUNT1 to 10.
1647 +)))
1648 +
1649 +==== 3.4.2.18 Counting ~-~- Clear Counting ====
1650 +
1651 +This feature clears the counting in counting mode.
1652 +
1507 1507  * (% style="color:#037691" %)**AT Command:**(%%) (% style="color:blue" %)**AT+CLRCOUNT         **(%%) ~/~/ clear all counting
1508 1508  
1509 1509  * (% style="color:#037691" %)**Downlink Payload (prefix 0xA6):**
... ... @@ -1510,14 +1510,30 @@
1510 1510  
1511 1511  (% style="color:blue" %)**0x A6 01    ** (%%)~/~/ clear all counting
1512 1512  
1659 +(% style="color:#037691" %)**AT Command**
1513 1513  
1661 +(% border="2" style="width:500px" %)
1662 +|(% style="width:142px" %)**Command**|(% style="width:356px" %)AT+CLRCOUNT
1663 +|(% style="width:142px" %)**Response**|(% style="width:356px" %)-
1514 1514  
1665 +(% style="color:#037691" %)**Downlink Payload**
1666 +
1667 +(% border="2" style="width:500px" %)
1668 +|(% style="width:141px" %)**Payload**|(% style="width:357px" %)<prefix><clear?>
1669 +|(% style="width:141px" %)**Parameters**|(% style="width:357px" %)(((
1670 +prefix : A6 (hex)
1671 +
1672 +clear? : 01 (hex)
1673 +)))
1674 +|(% style="width:141px" %)**Example**|(% style="width:357px" %)A6 **01**
1675 +
1515 1515  ==== 3.4.2.19 Counting ~-~- Change counting mode to save time ====
1516 1516  
1678 +This feature allows you to configure the device to save its counting result to internal flash memory at specified intervals. By setting a save time, the device will periodically store the counting data to prevent loss in case of power failure. The save interval can be adjusted to suit your requirements, with a minimum value of 30 seconds.
1517 1517  
1518 1518  * (% style="color:#037691" %)**AT Command:**
1519 1519  
1520 -(% style="color:blue" %)**AT+COUTIME=60  **(%%)~/~/ Set save time to 60 seconds. Device will save the counting result in internal flash every 60 seconds. (min value: 30)
1682 +(% style="color:blue" %)**AT+COUTIME=60  **(%%)~/~/ Sets the save time to 60 seconds. The device will save the counting result in internal flash every 60 seconds. (Min value: 30 seconds)
1521 1521  
1522 1522  
1523 1523  * (% style="color:#037691" %)**Downlink Payload (prefix 0xA7):**
... ... @@ -1525,7 +1525,7 @@
1525 1525  (% style="color:blue" %)**0x A7 aa bb cc     ** (%%)~/~/ same as AT+COUTIME =aa bb cc,
1526 1526  
1527 1527  (((
1528 -range: aa bb cc:0 to 16777215,  (unit:second)
1690 +Range: aa bb cc:0 to 16777215,  (unit: seconds)
1529 1529  )))
1530 1530  
1531 1531  
... ... @@ -1532,12 +1532,13 @@
1532 1532  
1533 1533  ==== 3.4.2.20 Reset save RO DO state ====
1534 1534  
1697 +This feature allows you to reset the saved relay output (RO) and digital output (DO) states when the device joins the network. By configuring this setting, you can control whether the device should retain or reset the relay states after a reset and rejoin to the network.
1535 1535  
1536 1536  * (% style="color:#037691" %)**AT Command:**
1537 1537  
1538 1538  (% style="color:blue" %)**AT+RODORESET=1    **(%%)~/~/ RODO will close when the device joining the network. (default)
1539 1539  
1540 -(% style="color:blue" %)**AT+RODORESET=0    **(%%)~/~/ After the device is reset, the previously saved RODO state (only MOD2 to MOD5) is read, and its state is not changed when it is reconnected to the network.
1703 +(% style="color:blue" %)**AT+RODORESET=0    **(%%)~/~/ After the device is reset, the previously saved RODO state (only MOD2 to MOD5) is read, and its state will not change when the device reconnects to the network.
1541 1541  
1542 1542  
1543 1543  * (% style="color:#037691" %)**Downlink Payload (prefix 0xAD):**
... ... @@ -1548,6 +1548,7 @@
1548 1548  
1549 1549  ==== 3.4.2.21 Encrypted payload ====
1550 1550  
1714 +This feature allows you to configure whether the device should upload data in an encrypted format or in plaintext. By default, the device encrypts the payload before uploading. You can toggle this setting to either upload encrypted data or transmit it without encryption.
1551 1551  
1552 1552  * (% style="color:#037691" %)**AT Command:**
1553 1553  
... ... @@ -1562,9 +1562,9 @@
1562 1562  
1563 1563  * (% style="color:#037691" %)**AT Command:**
1564 1564  
1565 -(% style="color:blue" %)**AT+GETSENSORVALUE=0    **(%%)~/~/ The serial port gets the reading of the current sensor
1729 +(% style="color:blue" %)**AT+GETSENSORVALUE=0    **(%%)~/~/ The serial port retrieves the reading of the current sensor.
1566 1566  
1567 -(% style="color:blue" %)**AT+GETSENSORVALUE=1    **(%%)~/~/ The serial port gets the current sensor reading and uploads it.
1731 +(% style="color:blue" %)**AT+GETSENSORVALUE=1    **(%%)~/~/ The serial port retrieves the current sensor reading and uploads it.
1568 1568  
1569 1569  
1570 1570  
... ... @@ -1754,7 +1754,7 @@
1754 1754  
1755 1755  == 3.6 Interface Details ==
1756 1756  
1757 -=== 3.6.1 Digital Input Ports: DI1/DI2/DI3 (For LT-33222-L, Low Active ) ===
1921 +=== 3.6.1 Digital Input Ports: DI1/DI2/DI3 (For LT-33222-L, Low Active) ===
1758 1758  
1759 1759  
1760 1760  Supports NPN-type sensors.