Version 77.28 by Xiaoling on 2022/06/10 08:41

Show last authors
1 (% style="text-align:center" %)
2 [[image:image-20220523163353-1.jpeg||height="604" width="500"]]
3
4 **LT-22222-L LoRa IO Controller User Manual **
5
6
7 **Table of Contents:**
8
9 {{toc/}}
10
11
12
13
14
15
16
17 = 1.Introduction =
18
19 == 1.1 What is LT Series I/O Controller ==
20
21 (((
22 The Dragino (% style="color:blue" %)**LT series I/O Modules**(%%) are Long Range LoRaWAN I/O Controller. It contains different I/O Interfaces such as:** (% style="color:blue" %)analog current Input, analog voltage input(%%)**(% style="color:blue" %), **relay output**, **digital input**(%%) and (% style="color:blue" %)**digital output**(%%) etc. The LT I/O Modules are designed to simplify the installation of I/O monitoring.
23 )))
24
25 (((
26 The LT I/O Controllers allows the user to send data and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, smartphone detection, building automation, and so on.
27 )))
28
29 (((
30 The LT I/O Controllers is aiming to provide an (% style="color:blue" %)**easy and low cost installation** (%%)by using LoRa wireless technology.
31 )))
32
33 (((
34 The use environment includes:
35 )))
36
37 (((
38 1) If user’s area has LoRaWAN service coverage, they can just install the I/O controller and configure it to connect the LoRaWAN provider via wireless.
39 )))
40
41 (((
42 2) User can set up a LoRaWAN gateway locally and configure the controller to connect to the gateway via wireless.
43 )))
44
45 (((
46 [[image:1653295757274-912.png]]
47
48
49 )))
50
51 == 1.2  Specifications ==
52
53 (((
54
55
56 **Hardware System:**
57 )))
58
59 * (((
60 STM32L072CZT6 MCU
61 )))
62 * (((
63 SX1276/78 Wireless Chip 
64 )))
65 * (((
66 (((
67 Power Consumption:
68 )))
69
70 * (((
71 Idle: 4mA@12v
72 )))
73 * (((
74 20dB Transmit: 34mA@12v
75 )))
76 )))
77
78
79 (((
80 **Interface for Model: LT22222-L:**
81 )))
82
83 * (((
84 2 x Digital dual direction Input (Detect High/Low signal, Max: 50v, or 220v with optional external resistor)
85 )))
86 * (((
87 2 x Digital Output (NPN output. Max pull up voltage 36V,450mA)
88 )))
89 * (((
90 2 x Relay Output (5A@250VAC / 30VDC)
91 )))
92 * (((
93 2 x 0~~20mA Analog Input (res:0.01mA)
94 )))
95 * (((
96 2 x 0~~30V Analog Input (res:0.01v)
97 )))
98 * (((
99 Power Input 7~~ 24V DC. 
100 )))
101
102
103 (((
104 **LoRa Spec:**
105 )))
106
107 * (((
108 (((
109 Frequency Range:
110 )))
111
112 * (((
113 Band 1 (HF): 862 ~~ 1020 Mhz
114 )))
115 * (((
116 Band 2 (LF): 410 ~~ 528 Mhz
117 )))
118 )))
119 * (((
120 168 dB maximum link budget.
121 )))
122 * (((
123 +20 dBm - 100 mW constant RF output vs.
124 )))
125 * (((
126 +14 dBm high efficiency PA.
127 )))
128 * (((
129 Programmable bit rate up to 300 kbps.
130 )))
131 * (((
132 High sensitivity: down to -148 dBm.
133 )))
134 * (((
135 Bullet-proof front end: IIP3 = -12.5 dBm.
136 )))
137 * (((
138 Excellent blocking immunity.
139 )))
140 * (((
141 Low RX current of 10.3 mA, 200 nA register retention.
142 )))
143 * (((
144 Fully integrated synthesizer with a resolution of 61 Hz.
145 )))
146 * (((
147 FSK, GFSK, MSK, GMSK, LoRaTM and OOK modulation.
148 )))
149 * (((
150 Built-in bit synchronizer for clock recovery.
151 )))
152 * (((
153 Preamble detection.
154 )))
155 * (((
156 127 dB Dynamic Range RSSI.
157 )))
158 * (((
159 Automatic RF Sense and CAD with ultra-fast AFC.
160 )))
161 * (((
162 Packet engine up to 256 bytes with CRC.
163
164
165 )))
166
167
168
169 == 1.3 Features ==
170
171 * LoRaWAN Class A & Class C protocol
172 * Optional Customized LoRa Protocol
173 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915/RU864/IN865
174 * AT Commands to change parameters
175 * Remote configure parameters via LoRa Downlink
176 * Firmware upgradable via program port
177 * Counting
178
179
180
181 == 1.4  Applications ==
182
183 * Smart Buildings & Home Automation
184 * Logistics and Supply Chain Management
185 * Smart Metering
186 * Smart Agriculture
187 * Smart Cities
188 * Smart Factory
189
190
191
192 == 1.5 Hardware Variants ==
193
194 (% border="1" style="background-color:#f7faff; width:500px" %)
195 |(% style="width:103px" %)**Model**|(% style="width:131px" %)**Photo**|(% style="width:334px" %)**Description**
196 |(% style="width:103px" %)**LT22222-L**|(% style="width:131px" %)[[image:1653296302983-697.png]]|(% style="width:334px" %)(((
197 * 2 x Digital Input (Bi-direction)
198 * 2 x Digital Output
199 * 2 x Relay Output (5A@250VAC / 30VDC)
200 * 2 x 0~~20mA Analog Input (res:0.01mA)
201 * 2 x 0~~30V Analog Input (res:0.01v)
202 * 1 x Counting Port
203 )))
204
205
206
207 = 2. Power ON Device =
208
209 The LT controller can be powered by 7 ~~ 24V DC power source. Connect VIN to Power Input V+ and GND to power input V- to power the LT controller.
210
211 (((
212 PWR will on when device is properly powered.
213 )))
214
215 [[image:1653297104069-180.png]]
216
217
218
219 = 3. Operation Mode =
220
221 == 3.1 How it works? ==
222
223 (((
224 The LT is configured as LoRaWAN OTAA Class C mode by default. It has OTAA keys to join network. To connect a local LoRaWAN network, user just need to input the OTAA keys in the network server and power on the LT. It will auto join the network via OTAA. For LT-22222-L, the LED will show the Join status: After power on **TX LED** will fast blink 5 times, LT-22222-L will enter working mode and start to JOIN LoRaWAN network. **TX LED** will be on for 5 seconds after joined in network. When there is message from server, the **RX LED** will be on for 1 second. 
225 )))
226
227 (((
228 In case user can’t set the OTAA keys in the network server and has to use the existing keys from server. User can [[use AT Command>>||anchor="H4.UseATCommand"]] to set the keys in the devices.
229
230
231 )))
232
233
234
235 == 3.2 Example to join LoRaWAN network ==
236
237 (((
238 This chapter shows an example for how to join the TTN LoRaWAN Network. Below is the network structure, we use our LG308 as LoRaWAN gateway here. 
239 )))
240
241 [[image:image-20220523172350-1.png||height="266" width="864"]]
242
243 (((
244 The LG308 is already set to connect to [[TTN network >>url:https://www.thethingsnetwork.org/]]. So what we need to do now is only configure register this device to TTN:
245 )))
246
247 (((
248 **Step 1**: Create a device in TTN with the OTAA keys from LT IO controller.
249 )))
250
251 (((
252 Each LT is shipped with a sticker with the default device EUI as below:
253 )))
254
255 [[image:1653297924498-393.png]]
256
257 Input these keys in the LoRaWAN Server portal. Below is TTN screen shot:
258
259 Add APP EUI in the application.
260
261 [[image:1653297955910-247.png||height="321" width="716"]]
262
263
264 Add APP KEY and DEV EUI
265
266 [[image:1653298023685-319.png]]
267
268
269 (((
270 **Step 2**: Power on LT and it will auto join to the TTN network. After join success, it will start to upload message to TTN and user can see in the panel.
271 )))
272
273 [[image:1653298044601-602.png||height="405" width="709"]]
274
275
276
277 == 3.3 Uplink Payload ==
278
279 There are five working modes + one interrupt mode on LT for different type application:
280
281 * **MOD1**: (default setting): 2 x ACI + 2AVI + DI + DO + RO
282 * **MOD2**: Double DI Counting + DO + RO
283 * **MOD3**: Single DI Counting + 2 x ACI + DO + RO
284 * **MOD4**: Single DI Counting + 1 x Voltage Counting + DO + RO
285 * **MOD5**: Single DI Counting + 2 x AVI + 1 x ACI + DO + RO
286 * **ADDMOD6**: Trigger Mode, Optional, used together with MOD1 ~~ MOD5
287
288
289
290 === 3.3.1 AT+MOD~=1, 2ACI+2AVI ===
291
292 The uplink payload includes totally 9 bytes. Uplink packets use FPORT=2 and every 10 minutes send one uplink by default.
293
294 [[image:image-20220523174024-3.png]]
295
296 (((
297 (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
298 )))
299
300 [[image:image-20220523174254-4.png]]
301
302 * RO is for relay. ROx=1 : close,ROx=0 always open.
303 * DI is for digital input. DIx=1: high or float, DIx=0: low.
304 * DO is for reverse digital output. DOx=1: output low, DOx=0: high or float.
305
306 (% style="color:red" %)Note: DI3 and DO3 bit are not valid for LT-22222-L
307
308 For example if payload is: [[image:image-20220523175847-2.png]]
309
310 **The value for the interface is:  **
311
312 AVI1 channel voltage is 0x04AB/1000=1195(DEC)/1000=1.195V
313
314 AVI2 channel voltage is 0x04AC/1000=1.196V
315
316 ACI1 channel current is 0x1310/1000=4.880mA
317
318 ACI2 channel current is 0x1300/1000=4.864mA
319
320 The last byte 0xAA= 10101010(B) means
321
322 * [1] RO1 relay channel is close and the RO1 LED is ON.
323 * [0] RO2 relay channel is open and RO2 LED is OFF;
324
325
326 **LT22222-L:**
327
328 * [1] DI2 channel is high input and DI2 LED is ON;
329 * [0] DI1 channel is low input;
330
331 * [0] DO3 channel output state
332 ** DO3 is float in case no load between DO3 and V+.;
333 ** DO3 is high in case there is load between DO3 and V+.
334 ** DO3 LED is off in both case
335 * [1] DO2 channel output is low and DO2 LED is ON.
336 * [0] DO1 channel output state
337 ** DO1 is float in case no load between DO1 and V+.;
338 ** DO1 is high in case there is load between DO1 and V+.
339 ** DO1 LED is off in both case
340
341
342
343 === 3.3.2 AT+MOD~=2, (Double DI Counting) ===
344
345 **For LT-22222-L**: this mode the **DI1 and DI2** are used as counting pins.
346
347 (((
348 Total : 11 bytes payload
349 )))
350
351 [[image:image-20220523180452-3.png]]
352
353 (((
354 (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DO3, DO2 and DO1. Totally 1bytes as below
355 )))
356
357 [[image:image-20220523180506-4.png]]
358
359 * RO is for relay. ROx=1 : close,ROx=0 always open.
360 * FIRST: Indicate this is the first packet after join network.
361 * DO is for reverse digital output. DOx=1: output low, DOx=0: high or float.
362
363 (((
364 (% style="color:red" %)Note: DO3 bit is not valid for LT-22222-L.
365 )))
366
367 (((
368 **To use counting mode, please run:**
369 )))
370
371 (% class="box infomessage" %)
372 (((
373 (((
374 **AT+MOD=2**
375 )))
376 )))
377
378 (% class="box infomessage" %)
379 (((
380 (((
381 **ATZ**
382 )))
383 )))
384
385 (((
386 (% style="color:#4f81bd" %)**AT Commands for counting:**
387 )))
388
389 (((
390 **For LT22222-L:**
391 )))
392
393 (% class="box infomessage" %)
394 (((
395 (((
396 **AT+TRIG1=0,100 (set DI1 port to trigger on low level, valid signal is 100ms) **
397 )))
398 )))
399
400 (% class="box infomessage" %)
401 (((
402 (((
403 **AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms ) **
404 )))
405 )))
406
407 (% class="box infomessage" %)
408 (((
409 (((
410 **AT+TRIG2=0,100 (set DI2 port to trigger on low level, valid signal is 100ms) **
411 )))
412 )))
413
414 (% class="box infomessage" %)
415 (((
416 (((
417 **AT+TRIG2=1,100 (set DI2 port to trigger on high level, valid signal is 100ms ) **
418 )))
419 )))
420
421 (% class="box infomessage" %)
422 (((
423 (((
424 **AT+SETCNT=1,60   (Set COUNT1 value to 60)**
425 )))
426 )))
427
428 (% class="box infomessage" %)
429 (((
430 (((
431 **AT+SETCNT=2,60   (Set COUNT2 value to 60)**
432 )))
433 )))
434
435
436
437 === 3.3.3 AT+MOD~=3, Single DI Counting + 2 x ACI ===
438
439 **LT22222-L**: This mode the DI1 is used as a counting pin.
440
441 [[image:image-20220523181246-5.png]]
442
443 (((
444 (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
445 )))
446
447 [[image:image-20220523181301-6.png]]
448
449 * RO is for relay. ROx=1 : close,ROx=0 always open.
450 * FIRST: Indicate this is the first packet after join network.
451 * DO is for reverse digital output. DOx=1: output low, DOx=0: high or float.
452
453 (((
454 (% style="color:red" %)Note: DO3 is not valid for LT-22222-L.
455 )))
456
457 (((
458 **To use counting mode, please run:**
459 )))
460
461 (% class="box infomessage" %)
462 (((
463 (((
464 **AT+MOD=3**
465 )))
466 )))
467
468 (% class="box infomessage" %)
469 (((
470 (((
471 **ATZ**
472 )))
473 )))
474
475 (((
476 Other AT Commands for counting are similar to [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]].
477
478
479 )))
480
481
482
483 === 3.3.4 AT+MOD~=4, Single DI Counting + 1 x Voltage Counting ===
484
485 **LT22222-L**: This mode the DI1 is used as a counting pin.
486
487 The AVI1 is also used for counting. AVI1 is used to monitor the voltage. It will check the voltage **every 60s**, if voltage is higher or lower than VOLMAX mV, the AVI1 Counting increase 1, so AVI1 counting can be used to measure a machine working hour.
488
489 [[image:image-20220523181903-8.png]]
490
491 (((
492 (% style="color:#4f81bd" %)**DIDORO **(%%)is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
493 )))
494
495 [[image:image-20220523181727-7.png]]
496
497 * RO is for relay. ROx=1 : close,ROx=0 always open.
498 * FIRST: Indicate this is the first packet after join network.
499 * DO is for reverse digital output. DOx=1: output low, DOx=0: high or float.
500
501 (((
502 (% style="color:red" %)Note: DO3 is not valid for LT-22222-L.
503 )))
504
505 (((
506 **To use this mode, please run:**
507 )))
508
509 (% class="box infomessage" %)
510 (((
511 (((
512 **AT+MOD=4**
513 )))
514 )))
515
516 (% class="box infomessage" %)
517 (((
518 (((
519 **ATZ**
520 )))
521 )))
522
523 (((
524
525 )))
526
527 (((
528 Other AT Commands for counting are similar to [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]].
529 )))
530
531 (((
532 **Plus below command for AVI1 Counting:**
533 )))
534
535 (% class="box infomessage" %)
536 (((
537 (((
538 **AT+SETCNT=3,60   (set AVI Count to 60)**
539 )))
540 )))
541
542 (% class="box infomessage" %)
543 (((
544 (((
545 **AT+VOLMAX=20000   (If AVI1 voltage higher than VOLMAX (20000mV =20v), counter increase 1)**
546 )))
547 )))
548
549 (% class="box infomessage" %)
550 (((
551 (((
552 **AT+VOLMAX=20000,0   (If AVI1 voltage lower than VOLMAX (20000mV =20v), counter increase 1)**
553 )))
554 )))
555
556 (% class="box infomessage" %)
557 (((
558 (((
559 **AT+VOLMAX=20000,1   (If AVI1 voltage higer than VOLMAX (20000mV =20v), counter increase 1)**
560 )))
561 )))
562
563
564
565 === 3.3.5 AT+MOD~=5, Single DI Counting + 2 x AVI + 1 x ACI ===
566
567 **LT22222-L**: This mode the DI1 is used as a counting pin.
568
569 [[image:image-20220523182334-9.png]]
570
571 (((
572 (% style="color:#4f81bd" %)**DIDORO**(%%) is a combination for RO1, RO2, DI3, DI2, DI1, DO3, DO2 and DO1. Totally 1bytes as below
573 )))
574
575 * RO is for relay. ROx=1 : close,ROx=0 always open.
576 * FIRST: Indicate this is the first packet after join network.
577 * (((
578 DO is for reverse digital output. DOx=1: output low, DOx=0: high or float.
579 )))
580
581 (((
582 (% style="color:red" %)Note: DO3 is not valid for LT-22222-L.
583 )))
584
585 (((
586 **To use this mode, please run:**
587 )))
588
589 (% class="box infomessage" %)
590 (((
591 (((
592 **AT+MOD=5**
593 )))
594 )))
595
596 (% class="box infomessage" %)
597 (((
598 (((
599 **ATZ**
600 )))
601 )))
602
603 (((
604 Other AT Commands for counting are similar to [[MOD2 Counting Command>>||anchor="H3.3.2AT2BMOD3D22C28DoubleDICounting29"]].
605
606
607 )))
608
609
610
611 === 3.3.6 AT+ADDMOD~=6. (Trigger Mode, Optional) ===
612
613 (% style="color:#4f81bd" %)**This mode is an optional mode for trigger purpose. It can run together with other mode.**
614
615 For example, if user has configured below commands:
616
617 * **AT+MOD=1 ** **~-~->** The normal working mode
618 * **AT+ADDMOD6=1**   **~-~->** Enable trigger
619
620 LT will keep monitoring AV1/AV2/AC1/AC2 every 5 seconds; LT will send uplink packets in two cases:
621
622 1. Periodically uplink (Base on TDC time). Payload is same as the normal MOD (MOD 1 for above command). This uplink uses LoRaWAN (% style="color:#4f81bd" %)**unconfirmed**(%%) data type
623 1. Trigger uplink when meet the trigger condition. LT will sent two packets in this case, the first uplink use payload specify in this mod (mod=6), the second packets use the normal mod payload(MOD=1 for above settings). Both Uplinks use LoRaWAN (% style="color:#4f81bd" %)**CONFIRMED data type.**
624
625 **AT Command to set Trigger Condition**:
626
627 (% style="color:#4f81bd" %)**Trigger base on voltage**:
628
629 Format: AT+AVLIM=<AV1_LIMIT_LOW>,< AV1_LIMIT_HIGH>,<AV2_LIMIT_LOW>,< AV2_LIMIT_HIGH>
630
631 **Example:**
632
633 AT+AVLIM=3000,6000,0,2000   (If AVI1 voltage lower than 3v or higher than 6v. or AV2 voltage is higher than 2v, LT will trigger Uplink)
634
635 AT+AVLIM=5000,0,0,0   (If AVI1 voltage lower than 5V , trigger uplink, 0 means ignore)
636
637
638 (% style="color:#4f81bd" %)**Trigger base on current**:
639
640 Format: AT+ACLIM=<AC1_LIMIT_LOW>,< AC1_LIMIT_HIGH>,<AC2_LIMIT_LOW>,< AC2_LIMIT_HIGH>
641
642 **Example:**
643
644 AT+ACLIM=10000,15000,0,0   (If ACI1 voltage lower than 10mA or higher than 15mA, trigger an uplink)
645
646
647 (% style="color:#4f81bd" %)**Trigger base on DI status**:
648
649 DI status trigger Flag.
650
651 Format: AT+DTRI=<DI1_TIRGGER_FlAG>,< DI2_TIRGGER_FlAG >
652
653 **Example:**
654
655 AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
656
657
658 **Downlink Command to set Trigger Condition**
659
660 Type Code: 0xAA. Downlink command same as AT Command **AT+AVLIM, AT+ACLIM**
661
662 Format: AA xx yy1 yy1 yy2 yy2 yy3 yy3 yy4 yy4
663
664 AA: Code for this downlink Command:
665
666 xx: 0: Limit for AV1 and AV2;  1: limit for AC1 and AC2 ; 2 DI1, DI2 trigger enable/disable
667
668 yy1 yy1: AC1 or AV1 low limit or DI1/DI2 trigger status.
669
670 yy2 yy2: AC1 or AV1 high limit.
671
672 yy3 yy3: AC2 or AV2 low limit.
673
674 Yy4 yy4: AC2 or AV2 high limit.
675
676 **Example1**: AA 00 13 88 00 00 00 00 00 00
677
678 Same as AT+AVLIM=5000,0,0,0   (If AVI1 voltage lower than 5V , trigger uplink, 0 means ignore)
679
680 **Example2**: AA 02 01 00
681
682 Same as AT+ DTRI =1,0  (Enable DI1 trigger / disable DI2 trigger)
683
684 (% style="color:#4f81bd" %)**Trigger Settings Payload Explanation:**
685
686 MOD6 Payload : total 11 bytes payload
687
688 [[image:image-20220524085923-1.png]]
689
690 (% style="color:#4f81bd" %)**TRI FLAG1**(%%) is a combination to show if trigger is set for this part. Totally 1byte as below
691
692 [[image:image-20220524090106-2.png]]
693
694 * Each bits shows if the corresponding trigger has been configured.
695
696 **Example:**
697
698 10100000: Means the system has configure to use the trigger: AC1_LOW and AV2_LOW
699
700
701 (% style="color:#4f81bd" %)**TRI Status1**(%%) is a combination to show which condition is trigger. Totally 1byte as below
702
703 [[image:image-20220524090249-3.png]]
704
705 * Each bits shows which status has been trigger on this uplink.
706
707 **Example:**
708
709 10000000: Means this packet is trigger by AC1_LOW. Means voltage too low.
710
711
712 (% style="color:#4f81bd" %)**TRI_DI FLAG+STA **(%%)is a combination to show which condition is trigger. Totally 1byte as below
713
714 [[image:image-20220524090456-4.png]]
715
716 * Each bits shows which status has been trigger on this uplink.
717
718 **Example:**
719
720 00000111: Means both DI1 and DI2 trigger are enabled and this packet is trigger by DI1.
721
722 00000101: Means both DI1 and DI2 trigger are enabled.
723
724
725 (% style="color:#4f81bd" %)**Enable/Disable MOD6 **(%%): 0x01: MOD6 is enable. 0x00: MOD6 is disable.
726
727 Downlink command to poll MOD6 status:
728
729 **AB 06**
730
731 When device got this command, it will send the MOD6 payload.
732
733
734
735 === 3.3.7 Payload Decoder ===
736
737 (((
738 **Decoder for TTN/loraserver/ChirpStack**: [[http:~~/~~/www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/Payload_decoder/>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/Payload_decoder/]]
739
740
741 )))
742
743
744
745 == 3.4 ​Configure LT via AT or Downlink ==
746
747 User can configure LT I/O Controller via AT Commands or LoRaWAN Downlink Commands
748
749 (((
750 There are two kinds of Commands:
751 )))
752
753 * (% style="color:#4f81bd" %)**Common Commands**(%%): They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
754
755 * (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for LT-22222-L.  User can see these commands below:
756
757
758
759 === 3.4.1 Common Commands ===
760
761 They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.5.4, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
762
763
764
765 === 3.4.2 Sensor related commands ===
766
767 ==== 3.4.2.1 Set Transmit Interval ====
768
769 Set device uplink interval.
770
771 * AT Command:
772
773 (% class="box infomessage" %)
774 (((
775 **AT+TDC=N **
776 )))
777
778 **Example: **AT+TDC=30000. Means set interval to 30 seconds
779
780 * Downlink Payload (prefix 0x01):
781
782 (% class="box infomessage" %)
783 (((
784 **0x01 aa bb cc     ~/~/ Same as AT+TDC=0x(aa bb cc)**
785 )))
786
787
788
789 ==== 3.4.2.2 Set Work Mode (AT+MOD) ====
790
791 Set work mode.
792
793 * AT Command:
794
795 (% class="box infomessage" %)
796 (((
797 **AT+MOD=N  **
798 )))
799
800 **Example**: AT+MOD=2. Set work mode to Double DI counting mode
801
802 * Downlink Payload (prefix 0x0A):
803
804 (% class="box infomessage" %)
805 (((
806 **0x0A aa     ~/~/ Same as AT+MOD=aa**
807 )))
808
809
810
811 ==== 3.4.2.3 Poll an uplink ====
812
813 * AT Command:
814
815 There is no AT Command to poll uplink
816
817 * Downlink Payload (prefix 0x08):
818
819 (% class="box infomessage" %)
820 (((
821 **0x08 FF     ~/~/ Poll an uplink,**
822 )))
823
824 **Example**: 0x08FF, ask device to send an Uplink
825
826
827
828 ==== 3.4.2.4 Enable Trigger Mode ====
829
830 Use of trigger mode, please check [[ADDMOD6>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
831
832 * AT Command:
833
834 (% class="box infomessage" %)
835 (((
836 **AT+ADDMOD6=1 or 0**
837 )))
838
839 1: Enable Trigger Mode
840
841 0: Disable Trigger Mode
842
843 * Downlink Payload (prefix 0x0A 06):
844
845 (% class="box infomessage" %)
846 (((
847 **0x0A 06 aa     ~/~/ Same as AT+ADDMOD6=aa,**
848 )))
849
850
851
852 ==== 3.4.2.5 Poll trigger settings ====
853
854 Poll trigger settings,
855
856 * AT Command:
857
858 There is no AT Command for this feature.
859
860 * Downlink Payload (prefix 0x AB 06):
861
862 (% class="box infomessage" %)
863 (((
864 **0xAB 06  ~/~/ Poll trigger settings, device will uplink trigger settings once receive this command**
865 )))
866
867
868
869 ==== 3.4.2.6 Enable / Disable DI1/DI2/DI3 as trigger ====
870
871 Enable Disable DI1/DI2/DI2 as trigger,
872
873 * AT Command:
874
875 (% class="box infomessage" %)
876 (((
877 **Format: AT+DTRI=<DI1_TIRGGER_FlAG>,< DI2_TIRGGER_FlAG >**
878 )))
879
880 **Example:**
881
882 AT+ DTRI =1,0   (Enable DI1 trigger / disable DI2 trigger)
883
884 * Downlink Payload (prefix 0xAA 02):
885
886 (% class="box infomessage" %)
887 (((
888 **0xAA 02 aa bb  ~/~/ Same as AT+DTRI=aa,bb**
889 )))
890
891
892
893 ==== 3.4.2.7 Trigger1 – Set DI1 or DI3 as trigger ====
894
895 Set DI1 or DI3(for LT-33222-L) trigger.
896
897 * AT Command:
898
899 (% class="box infomessage" %)
900 (((
901 **AT+TRIG1=a,b**
902 )))
903
904 a : Interrupt mode. 0: falling edge; 1: rising edge, 2: falling and raising edge(for MOD=1).
905
906 b : delay timing.
907
908 **Example:**
909
910 AT+TRIG1=1,100(set DI1 port to trigger on high level, valid signal is 100ms )
911
912 * Downlink Payload (prefix 0x09 01 ):
913
914 (% class="box infomessage" %)
915 (((
916 **0x09 01 aa bb cc ~/~/ same as AT+TRIG1=aa,0x(bb cc)**
917 )))
918
919
920
921 ==== 3.4.2.8 Trigger2 – Set DI2 as trigger ====
922
923 Set DI2 trigger.
924
925 * AT Command:
926
927 (% class="box infomessage" %)
928 (((
929 **AT+TRIG2=a,b**
930 )))
931
932 a : Interrupt mode. 0: falling edge; 1: rising edge, 2: falling and raising edge(for MOD=1).
933
934 b : delay timing.
935
936 **Example:**
937
938 AT+TRIG2=0,100(set DI1 port to trigger on low level, valid signal is 100ms )
939
940 * Downlink Payload (prefix 0x09 02 ):
941
942 (% class="box infomessage" %)
943 (((
944 **0x09 02 aa bb cc ~/~/ same as AT+TRIG1=aa,0x(bb cc)**
945 )))
946
947
948
949 ==== 3.4.2.9 Trigger – Set AC (current) as trigger ====
950
951 Set current trigger , base on AC port. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
952
953 * AT Command:
954
955 (% class="box infomessage" %)
956 (((
957 **AT+ACLIM. **
958 )))
959
960 * Downlink Payload (prefix 0xAA 01 ):
961
962 (% class="box infomessage" %)
963 (((
964 **0x AA 01 aa bb cc dd ee ff gg hh ~/~/ same as AT+ACLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
965 )))
966
967
968
969 ==== 3.4.2.10 Trigger – Set AV (voltage) as trigger ====
970
971 Set current trigger , base on AV port. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]
972
973 * AT Command:
974
975 (% class="box infomessage" %)
976 (((
977 **AT+AVLIM. See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]]**
978 )))
979
980 * Downlink Payload (prefix 0xAA 00 ):
981
982 (% class="box infomessage" %)
983 (((
984 **0x AA 00 aa bb cc dd ee ff gg hh ~/~/ same as AT+AVLIM See [[trigger mode>>||anchor="H3.3.6AT2BADDMOD3D6.28TriggerMode2COptional29"]] **
985 )))
986
987
988
989 ==== 3.4.2.11 Trigger – Set minimum interval ====
990
991 Set AV and AC trigger minimum interval, system won’t response to the second trigger within this set time after the first trigger.
992
993 * AT Command:
994
995 (% class="box infomessage" %)
996 (((
997 **AT+ATDC=5. Device won’t response the second trigger within 5 minute after the first trigger.**
998 )))
999
1000 * Downlink Payload (prefix 0xAC ):
1001
1002 (% class="box infomessage" %)
1003 (((
1004 **0x AC aa bb ~/~/ same as AT+ATDC=0x(aa bb)   . Unit (min)**
1005 )))
1006
1007
1008 ==== 3.4.2.12 DO ~-~- Control Digital Output DO1/DO2/DO3 ====
1009
1010 * AT Command:
1011
1012 There is no AT Command to control Digital Output
1013
1014 * Downlink Payload (prefix 0x02):
1015
1016 (% class="box infomessage" %)
1017 (((
1018 **0x02 aa bb cc     ~/~/ Set DO1/DO2/DO3 output**
1019 )))
1020
1021 (((
1022 If payload = 0x02010001, while there is load between V+ and DOx, it means set DO1 to low, DO2 to high and DO3 to low.
1023 )))
1024
1025 (((
1026 01: Low,  00: High ,  11: No action
1027 )))
1028
1029 [[image:image-20220524092754-5.png]]
1030
1031 (((
1032 (% style="color:red" %)Note: For LT-22222-L, there is no DO3, the last byte can use any value.
1033 )))
1034
1035 (((
1036 (% style="color:red" %)Device will upload a packet if downlink code executes successfully.
1037 )))
1038
1039
1040 ==== 3.4.2.13 DO ~-~- Control Digital Output DO1/DO2/DO3 with time control ====
1041
1042 * AT Command:
1043
1044 There is no AT Command to control Digital Output
1045
1046 * Downlink Payload (prefix 0xA9):
1047
1048 (% class="box infomessage" %)
1049 (((
1050 (((
1051 **0xA9 aa bb cc     ~/~/ Set DO1/DO2/DO3 output with time control**
1052 )))
1053 )))
1054
1055 This is to control the digital output time of DO pin. Include four bytes:
1056
1057 (% style="color:#4f81bd" %)**First Byte**(%%)**:** Type code (0xA9)
1058
1059 (% style="color:#4f81bd" %)**Second Byte**(%%): Inverter Mode
1060
1061 01: DO pins will change back to original state after timeout.
1062
1063 00: DO pins will change to an inverter state after timeout 
1064
1065 (% style="color:#4f81bd" %)**Third Byte**(%%): Control Method and Ports status:
1066
1067 [[image:image-20220524093238-6.png]]
1068
1069 (% style="color:#4f81bd" %)**Fourth Byte**(%%): Control Method and Ports status:
1070
1071 [[image:image-20220524093328-7.png]]
1072
1073 (% style="color:#4f81bd" %)**Fifth Byte**(%%): Control Method and Ports status:
1074
1075 [[image:image-20220524093351-8.png]]
1076
1077 (% style="color:#4f81bd" %)**Sixth and Seventh Byte**:
1078
1079 Latching time. Unit: ms
1080
1081 Device will upload a packet if downlink code executes successfully.
1082
1083 **Example payload:**
1084
1085 **~1. A9 01 01 01 01 07 D0**
1086
1087 DO1 pin & DO2 pin & DO3 pin will be set to Low, last 2 seconds, then change back to original state.
1088
1089 **2. A9 01 00 01 11 07 D0**
1090
1091 DO1 pin set high, DO2 pin set low, DO3 pin no action, last 2 seconds, then change back to original state.
1092
1093 **3. A9 00 00 00 00 07 D0**
1094
1095 DO1 pin & DO2 pin & DO3 pin will be set to high, last 2 seconds, then both change to low.
1096
1097 **4. A9 00 11 01 00 07 D0**
1098
1099 DO1 pin no action, DO2 pin set low, DO3 pin set high, last 2 seconds, then DO1 pin no action, DO2 pin set high, DO3 pin set low
1100
1101
1102 === 3.4.2.14 Relay ~-~- Control Relay Output RO1/RO2 ===
1103
1104 * AT Command:
1105
1106 There is no AT Command to control Relay Output
1107
1108 * Downlink Payload (prefix 0x03):
1109
1110 (% class="box infomessage" %)
1111 (((
1112 **0x03 aa bb     ~/~/ Set RO1/RO2 output**
1113 )))
1114
1115 (((
1116 If payload = 0x030100, it means set RO1 to close and RO2 to open.
1117 )))
1118
1119 (((
1120 01: Close ,  00: Open , 11: No action
1121 )))
1122
1123 (((
1124 [[image:image-20220524093724-9.png]]
1125 )))
1126
1127 Device will upload a packet if downlink code executes successfully.
1128
1129
1130 ==== 3.4.2.15 Relay ~-~- Control Relay Output RO1/RO2 with time control ====
1131
1132 * AT Command:
1133
1134 There is no AT Command to control Relay Output
1135
1136 * Downlink Payload (prefix 0x05):
1137
1138 (% class="box infomessage" %)
1139 (((
1140 **0x05 aa bb cc dd     ~/~/ Set RO1/RO2 relay with time control:**
1141 )))
1142
1143 This is to control the relay output time of relay. Include four bytes:
1144
1145 (% style="color:#4f81bd" %)**First Byte **(%%)**:** Type code (0x05)
1146
1147 (% style="color:#4f81bd" %)**Second Byte(aa)**(%%): Inverter Mode
1148
1149 01: Relays will change back to original state after timeout.
1150
1151 00: Relays will change to an inverter state after timeout
1152
1153 (% style="color:#4f81bd" %)**Third Byte(bb)**(%%): Control Method and Ports status:
1154
1155 [[image:image-20220524093831-10.png]]
1156
1157 (% style="color:#4f81bd" %)**Fourth/Fifth Bytes(cc)**(%%): Latching time. Unit: ms
1158
1159 Device will upload a packet if downlink code executes successfully.
1160
1161 **Example payload:**
1162
1163 **~1. 05 01 11 07 D0**
1164
1165 Relay1 and Relay 2 will be set to NO , last 2 seconds, then change back to original state.
1166
1167 **2. 05 01 10 07 D0**
1168
1169 Relay1 will change to NO, Relay2 will change to NC, last 2 seconds, then both change back to original state.
1170
1171 **3. 05 00 01 07 D0**
1172
1173 Relay1 will change to NC, Relay2 will change to NO, last 2 seconds, then relay change to NO, Relay2 change to NC.
1174
1175 **4. 05 00 00 07 D0**
1176
1177 Relay 1 & relay2 will change to NC, last 2 seconds, then both change to NO.
1178
1179
1180 ==== 3.4.2.16 Counting ~-~- Voltage threshold counting ====
1181
1182 When voltage exceed the threshold, count. Feature see [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]
1183
1184 * AT Command:
1185
1186 (% class="box infomessage" %)
1187 (((
1188 **AT+VOLMAX    ~/~/ See [[MOD4>>||anchor="H3.3.4AT2BMOD3D42CSingleDICounting2B1xVoltageCounting"]]**
1189 )))
1190
1191 * Downlink Payload (prefix 0xA5):
1192
1193 (% class="box infomessage" %)
1194 (((
1195 **0xA5 aa bb cc   ~/~/ Same as AT+VOLMAX=(aa bb),cc**
1196 )))
1197
1198
1199 ==== 3.4.2.17 Counting ~-~- Pre-configure the Count Number ====
1200
1201 * AT Command:
1202
1203 (% class="box infomessage" %)
1204 (((
1205 **AT+SETCNT=aa,(bb cc dd ee) **
1206 )))
1207
1208 aa: 1: Set count1,
1209
1210 2: Set count2,
1211
1212 3: Set AV1 count
1213
1214 Bb cc dd ee: number to be set
1215
1216 * Downlink Payload (prefix 0xA8):
1217
1218 (% class="box infomessage" %)
1219 (((
1220 **0x A8 aa bb cc dd ee     ~/~/ same as AT+SETCNT=aa,(bb cc dd ee)**
1221 )))
1222
1223
1224 ==== 3.4.2.18 Counting ~-~- Clear Counting ====
1225
1226 Clear counting for counting mode
1227
1228 * AT Command:
1229
1230 (% class="box infomessage" %)
1231 (((
1232 **AT+CLRCOUNT ~/~/ clear all counting**
1233 )))
1234
1235 * Downlink Payload (prefix 0xA6):
1236
1237 (% class="box infomessage" %)
1238 (((
1239 **0x A6 01     ~/~/ clear all counting,**
1240 )))
1241
1242
1243 ==== 3.4.2.19 Counting ~-~- Change counting mode save time ====
1244
1245 * AT Command:
1246
1247 (% class="box infomessage" %)
1248 (((
1249 **AT+COUTIME=60  ~/~/ Set save time to 60 seconds. Device will save the counting result in internal flash every 60 seconds. (min value: 30)**
1250 )))
1251
1252 * Downlink Payload (prefix 0xA7):
1253
1254 (% class="box infomessage" %)
1255 (((
1256 **0x A7 aa bb cc     ~/~/ same as AT+COUTIME =aa bb cc,**
1257 )))
1258
1259 (((
1260 range: aa bb cc:0 to 16777215,  (unit:second)
1261
1262
1263 )))
1264
1265 == 3.5 Integrate with Mydevice ==
1266
1267 Mydevices provides a human friendly interface to show the sensor data, once we have data in TTN, we can use Mydevices to connect to TTN and see the data in Mydevices. Below are the steps:
1268
1269 (((
1270 **Step 1**: Be sure that your device is programmed and properly connected to the network at this time.
1271 )))
1272
1273 (((
1274 **Step 2**: To configure the Application to forward data to Mydevices you will need to add integration. To add the Mydevices integration, perform the following steps:
1275 )))
1276
1277 [[image:1653356737703-362.png||height="232" width="732"]]
1278
1279 [[image:image-20220524094641-11.png||height="390" width="723"]]
1280
1281 [[image:image-20220524094641-12.png||height="402" width="718"]]
1282
1283
1284 **Step 3**: Create an account or log in Mydevices.
1285
1286 **Step 4**: Search LT-22222-L(for both LT-22222-L / LT-33222-L) and add DevEUI.(% style="display:none" %)
1287
1288 Search under The things network
1289
1290 [[image:1653356838789-523.png||height="337" width="740"]]
1291
1292
1293 After added, the sensor data arrive TTN, it will also arrive and show in Mydevices.
1294
1295 [[image:image-20220524094909-1.png||height="335" width="729"]]
1296
1297 [[image:image-20220524094909-2.png||height="337" width="729"]]
1298
1299 [[image:image-20220524094909-3.png||height="338" width="727"]]
1300
1301 [[image:image-20220524094909-4.png||height="339" width="728"]](% style="display:none" %)
1302
1303 [[image:image-20220524094909-5.png||height="341" width="734"]]
1304
1305
1306 == 3.6 Interface Detail ==
1307
1308 === 3.6.1 Digital Input Port: DI1/DI2 /DI3 ( For LT-33222-L, low active ) ===
1309
1310 Support NPN Type sensor
1311
1312 [[image:1653356991268-289.png]]
1313
1314
1315 === 3.6.2 Digital Input Port: DI1/DI2 ( For LT-22222-L) ===
1316
1317 (((
1318 The DI port of LT-22222-L can support NPN or PNP output sensor.
1319 )))
1320
1321 (((
1322 (((
1323 Internal circuit as below, the NEC2501 is a photocoupler, the Active current (from NEC2501 pin 1 to pin 2 is 1ma and the max current is 50mA. When there is active current pass NEC2501 pin1 to pin2. The DI will be active high
1324 )))
1325 )))
1326
1327 [[image:1653357170703-587.png]]
1328
1329 (((
1330 (((
1331 When use need to connect a device to the DI port, both DI1+ and DI1- must be connected.
1332 )))
1333 )))
1334
1335 (((
1336
1337 )))
1338
1339 (((
1340 **Example1**: Connect to a Low active sensor.
1341 )))
1342
1343 (((
1344 This type of sensor will output a low signal GND when active.
1345 )))
1346
1347 * (((
1348 Connect sensor’s output to DI1-
1349 )))
1350 * (((
1351 Connect sensor’s VCC to DI1+.
1352 )))
1353
1354 (((
1355 So when sensor active, the current between NEC2501 pin1 and pin2 is:
1356 )))
1357
1358 (((
1359 [[image:1653968155772-850.png||height="23" width="19"]]**= DI1+ / 1K.**
1360 )))
1361
1362 (((
1363 If DI1+ = 12v, the [[image:1653968155772-850.png||height="23" width="19"]]= 12mA , So the LT-22222-L will be able to detect this active signal.
1364 )))
1365
1366 (((
1367
1368 )))
1369
1370 (((
1371 **Example2**: Connect to a High active sensor.
1372 )))
1373
1374 (((
1375 This type of sensor will output a high signal (example 24v) when active.
1376 )))
1377
1378 * (((
1379 Connect sensor’s output to DI1+
1380 )))
1381 * (((
1382 Connect sensor’s GND DI1-.
1383 )))
1384
1385 (((
1386 So when sensor active, the current between NEC2501 pin1 and pin2 is:
1387 )))
1388
1389 (((
1390 [[image:1653968155772-850.png||height="23" width="19"]]**= DI1+ / 1K.**
1391 )))
1392
1393 (((
1394 If **DI1+ = 24v**, the[[image:1653968155772-850.png||height="23" width="19"]] 24mA , So the LT-22222-L will be able to detect this high active signal.
1395 )))
1396
1397 (((
1398
1399 )))
1400
1401 (((
1402 **Example3**: Connect to a 220v high active sensor.
1403 )))
1404
1405 (((
1406 Assume user want to monitor an active signal higher than 220v, to make sure not burn the photocoupler  
1407 )))
1408
1409 * (((
1410 Connect sensor’s output to DI1+ with a serial 50K resistor
1411 )))
1412 * (((
1413 Connect sensor’s GND DI1-.
1414 )))
1415
1416 (((
1417 So when sensor active, the current between NEC2501 pin1 and pin2 is:
1418 )))
1419
1420 (((
1421 [[image:1653968155772-850.png||height="23" width="19"]]**= DI1+ / 51K.**
1422 )))
1423
1424 (((
1425 If sensor output is 220v, the [[image:1653968155772-850.png||height="23" width="19"]](% id="cke_bm_243359S" style="display:none" %)[[image:image-20220524095628-8.png]](%%) = DI1+ / 51K.  = 4.3mA , So the LT-22222-L will be able to detect this high active signal safely.
1426 )))
1427
1428
1429 === 3.6.3 Digital Output Port: DO1/DO2 /DO3 ===
1430
1431 NPN output: GND or Float. Max voltage can apply to output pin is 36v.
1432
1433 [[image:1653357531600-905.png]]
1434
1435
1436 === 3.6.4 Analog Input Interface ===
1437
1438 The analog input interface is as below. The LT will measure the IN2 voltage so to calculate the current pass the Load. The formula is:
1439
1440 **AC2 = (IN2 voltage )/12**
1441
1442 [[image:1653357592296-182.png]]
1443
1444 Example to connect a 4~~20mA sensor
1445
1446 We take the wind speed sensor as an example for reference only.
1447
1448 Specifications of the wind speed sensor:
1449
1450 Red:12~~24v
1451
1452 Yellow:4~~20mA
1453
1454 Black:GND
1455
1456
1457 Connection diagram:
1458
1459 [[image:1653357640609-758.png]]
1460
1461 [[image:1653357648330-671.png||height="155" width="733"]]
1462
1463
1464 === 3.6.5 Relay Output ===
1465
1466 (((
1467 The LT serial controller has two relay interfaces; each interface uses two pins of the screw terminal. User can connect other device’s Power Line to in serial of RO1_1 and RO_2. Such as below:
1468 )))
1469
1470 [[image:image-20220524100215-9.png]]
1471
1472 [[image:image-20220524100215-10.png||height="382" width="723"]]
1473
1474
1475 == 3.7 LEDs Indicators ==
1476
1477 [[image:image-20220524100748-11.png]]
1478
1479
1480 = 4. Use AT Command =
1481
1482 == 4.1 Access AT Command ==
1483
1484 LT supports AT Command set. User can use a USB to TTL adapter plus the 3.5mm Program Cable to connect to LT for using AT command, as below.
1485
1486 [[image:1653358238933-385.png]]
1487
1488 (((
1489 In PC, User needs to set (% style="color:#4f81bd" %)**serial tool**(%%)(such as [[putty>>url:https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to (% style="color:green" %)**9600**(%%) to access to access serial console for LT. The AT commands are disable by default and need to enter password (default:(% style="color:green" %)**123456**)(%%) to active it. As shown below:
1490 )))
1491
1492 [[image:1653358355238-883.png]]
1493
1494 (((
1495 More detail AT Command manual can be found at [[AT Command Manual>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/]]
1496 )))
1497
1498 (((
1499 AT+<CMD>?        : Help on <CMD>
1500 )))
1501
1502 (((
1503 AT+<CMD>         : Run <CMD>
1504 )))
1505
1506 (((
1507 AT+<CMD>=<value> : Set the value
1508 )))
1509
1510 (((
1511 AT+<CMD>=?       : Get the value
1512 )))
1513
1514 (((
1515 ATZ: Trig a reset of the MCU
1516 )))
1517
1518 (((
1519 AT+FDR: Reset Parameters to Factory Default, Keys Reserve 
1520 )))
1521
1522 (((
1523 AT+DEUI: Get or Set the Device EUI
1524 )))
1525
1526 (((
1527 AT+DADDR: Get or Set the Device Address
1528 )))
1529
1530 (((
1531 AT+APPKEY: Get or Set the Application Key
1532 )))
1533
1534 (((
1535 AT+NWKSKEY: Get or Set the Network Session Key
1536 )))
1537
1538 (((
1539 AT+APPSKEY: Get or Set the Application Session Key
1540 )))
1541
1542 (((
1543 AT+APPEUI: Get or Set the Application EUI
1544 )))
1545
1546 (((
1547 AT+ADR: Get or Set the Adaptive Data Rate setting. (0: off, 1: on)
1548 )))
1549
1550 (((
1551 AT+TXP: Get or Set the Transmit Power (0-5, MAX:0, MIN:5, according to LoRaWAN Spec)
1552 )))
1553
1554 (((
1555 AT+DR: Get or Set the Data Rate. (0-7 corresponding to DR_X)  
1556 )))
1557
1558 (((
1559 AT+DCS: Get or Set the ETSI Duty Cycle setting - 0=disable, 1=enable - Only for testing
1560 )))
1561
1562 (((
1563 AT+PNM: Get or Set the public network mode. (0: off, 1: on)
1564 )))
1565
1566 (((
1567 AT+RX2FQ: Get or Set the Rx2 window frequency
1568 )))
1569
1570 (((
1571 AT+RX2DR: Get or Set the Rx2 window data rate (0-7 corresponding to DR_X)
1572 )))
1573
1574 (((
1575 AT+RX1DL: Get or Set the delay between the end of the Tx and the Rx Window 1 in ms
1576 )))
1577
1578 (((
1579 AT+RX2DL: Get or Set the delay between the end of the Tx and the Rx Window 2 in ms
1580 )))
1581
1582 (((
1583 AT+JN1DL: Get or Set the Join Accept Delay between the end of the Tx and the Join Rx Window 1 in ms
1584 )))
1585
1586 (((
1587 AT+JN2DL: Get or Set the Join Accept Delay between the end of the Tx and the Join Rx Window 2 in ms
1588 )))
1589
1590 (((
1591 AT+NJM: Get or Set the Network Join Mode. (0: ABP, 1: OTAA)
1592 )))
1593
1594 (((
1595 AT+NWKID: Get or Set the Network ID
1596 )))
1597
1598 (((
1599 AT+FCU: Get or Set the Frame Counter Uplink
1600 )))
1601
1602 (((
1603 AT+FCD: Get or Set the Frame Counter Downlink
1604 )))
1605
1606 (((
1607 AT+CLASS: Get or Set the Device Class
1608 )))
1609
1610 (((
1611 AT+JOIN: Join network
1612 )))
1613
1614 (((
1615 AT+NJS: Get OTAA Join Status
1616 )))
1617
1618 (((
1619 AT+SENDB: Send hexadecimal data along with the application port
1620 )))
1621
1622 (((
1623 AT+SEND: Send text data along with the application port
1624 )))
1625
1626 (((
1627 AT+RECVB: Print last received data in binary format (with hexadecimal values)
1628 )))
1629
1630 (((
1631 AT+RECV: Print last received data in raw format
1632 )))
1633
1634 (((
1635 AT+VER: Get current image version and Frequency Band
1636 )))
1637
1638 (((
1639 AT+CFM: Get or Set the confirmation mode (0-1)
1640 )))
1641
1642 (((
1643 AT+CFS: Get confirmation status of the last AT+SEND (0-1)
1644 )))
1645
1646 (((
1647 AT+SNR: Get the SNR of the last received packet
1648 )))
1649
1650 (((
1651 AT+RSSI: Get the RSSI of the last received packet
1652 )))
1653
1654 (((
1655 AT+TDC: Get or set the application data transmission interval in ms
1656 )))
1657
1658 (((
1659 AT+PORT: Get or set the application port
1660 )))
1661
1662 (((
1663 AT+DISAT: Disable AT commands
1664 )))
1665
1666 (((
1667 AT+PWORD: Set password, max 9 digits
1668 )))
1669
1670 (((
1671 AT+CHS: Get or Set Frequency (Unit: Hz) for Single Channel Mode
1672 )))
1673
1674 (((
1675 AT+CHE: Get or Set eight channels mode, Only for US915, AU915, CN470
1676 )))
1677
1678 (((
1679 AT+CFG: Print all settings
1680
1681
1682 )))
1683
1684 == 4.2 Common AT Command Sequence ==
1685
1686 === 4.2.1 Multi-channel ABP mode (Use with SX1301/LG308) ===
1687
1688 (((
1689 If device has not joined network yet:
1690 )))
1691
1692 (((
1693 (% style="background-color:#dcdcdc" %)123456
1694 )))
1695
1696 (((
1697 (% style="background-color:#dcdcdc" %)AT+FDR
1698 )))
1699
1700 (((
1701 (% style="background-color:#dcdcdc" %)123456
1702 )))
1703
1704 (((
1705 (% style="background-color:#dcdcdc" %)AT+NJM=0
1706 )))
1707
1708 (((
1709 (% style="background-color:#dcdcdc" %)ATZ
1710 )))
1711
1712
1713 (((
1714 If device already joined network:
1715 )))
1716
1717 (((
1718 (% style="background-color:#dcdcdc" %)AT+NJM=0
1719 )))
1720
1721 (((
1722 (% style="background-color:#dcdcdc" %)ATZ
1723
1724
1725 )))
1726
1727 === 4.2.2 Single-channel ABP mode (Use with LG01/LG02) ===
1728
1729 (((
1730 (% style="background-color:#dcdcdc" %) 123456(%%)   Enter Password to have AT access.
1731 )))
1732
1733 (((
1734 (% style="background-color:#dcdcdc" %) AT+FDR(%%)   Reset Parameters to Factory Default, Keys Reserve
1735 )))
1736
1737 (((
1738 (% style="background-color:#dcdcdc" %) 123456(%%)   Enter Password to have AT access.
1739 )))
1740
1741 (((
1742 (% style="background-color:#dcdcdc" %) AT+CLASS=C(%%) Set to work in CLASS C
1743 )))
1744
1745 (((
1746 (% style="background-color:#dcdcdc" %) AT+NJM=0(%%) Set to ABP mode
1747 )))
1748
1749 (((
1750 (% style="background-color:#dcdcdc" %) AT+ADR=0(%%) Set the Adaptive Data Rate Off
1751 )))
1752
1753 (((
1754 (% style="background-color:#dcdcdc" %) AT+DR=5(%%)  Set Data Rate
1755 )))
1756
1757 (((
1758 (% style="background-color:#dcdcdc" %) AT+TDC=60000(%%)  Set transmit interval to 60 seconds
1759 )))
1760
1761 (((
1762 (% style="background-color:#dcdcdc" %) AT+CHS=868400000(%%) Set transmit frequency to 868.4Mhz
1763 )))
1764
1765 (((
1766 (% style="background-color:#dcdcdc" %) AT+RX2FQ=868400000(%%) Set RX2Frequency to 868.4Mhz (according to the result from server)
1767 )))
1768
1769 (((
1770 (% style="background-color:#dcdcdc" %) AT+RX2DR=5(%%)  Set RX2DR to match the downlink DR from server. see below
1771 )))
1772
1773 (((
1774 (% style="background-color:#dcdcdc" %) AT+DADDR=26 01 1A F1 (%%)Set Device Address to 26 01 1A F1, this ID can be found in the LoRa Server portal.
1775 )))
1776
1777 (((
1778 (% style="background-color:#dcdcdc" %) ATZ         (%%) Reset MCU
1779 )))
1780
1781 (((
1782 (% style="color:red" %)**Note:**
1783 )))
1784
1785 (((
1786 (% style="color:red" %)1. Make sure the device is set to ABP mode in the IoT Server.
1787 2. Make sure the LG01/02 gateway RX frequency is exactly the same as AT+CHS setting.
1788 3. Make sure SF / bandwidth setting in LG01/LG02 match the settings of AT+DR. refer [[this link>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_Gateway/&file=LoRaWAN%201.0.3%20Regional%20Parameters.xlsx]] to see what DR means.
1789 4. The command AT+RX2FQ and AT+RX2DR is to let downlink work. to set the correct parameters, user can check the actually downlink parameters to be used. As below. Which shows the RX2FQ should use 868400000 and RX2DR should be 5
1790 )))
1791
1792 (((
1793 [[image:1653359097980-169.png||height="188" width="729"]]
1794 )))
1795
1796 (((
1797
1798 )))
1799
1800 === 4.2.3 Change to Class A ===
1801
1802 If sensor JOINED
1803 (% style="background-color:#dcdcdc" %)AT+CLASS=A
1804 ATZ
1805
1806
1807 = 5. FAQ =
1808
1809 == 5.1 How to upgrade the image? ==
1810
1811 The LT LoRaWAN Controller is shipped with a 3.5mm cable, the cable is used to upload image to LT to:
1812
1813 * Support new features
1814 * For bug fix
1815 * Change LoRaWAN bands.
1816 Below shows the hardware connection for how to upload an image to the LT:
1817 * [[image:1653359603330-121.png]]
1818
1819 (((
1820 **Step1:** Download [[flash loader>>url:https://www.st.com/content/st_com/en/products/development-tools/software-development-tools/stm32-software-development-tools/stm32-programmers/flasher-stm32.html]].
1821 **Step2**: Download the [[LT Image files>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/image/]].
1822 **Step3: **Open flashloader; choose the correct COM port to update.
1823 **For LT-22222-L**:
1824 Hold down the PRO button and then momentarily press the RST reset button and the **DO1 led** will change from OFF to ON. When **DO1 LED** is on, it means the device is in download mode.
1825 )))
1826
1827 [[image:image-20220524103407-12.png]]
1828
1829 [[image:image-20220524103429-13.png]]
1830
1831 [[image:image-20220524104033-15.png]]
1832
1833 (% style="color:red" %)**Notice**(%%): In case user has lost the program cable. User can hand made one from a 3.5mm cable. The pin mapping is:
1834
1835 [[image:1653360054704-518.png||height="186" width="745"]]
1836
1837
1838 (((
1839 (((
1840 == 5.2 How to change the LoRa Frequency Bands/Region? ==
1841 )))
1842 )))
1843
1844 (((
1845 User can follow the introduction for [[how to upgrade image>>||anchor="H5.1Howtoupgradetheimage3F"]]. When download the images, choose the required image file for download.
1846
1847
1848 )))
1849
1850 (((
1851 == 5.3 How to set up LT to work with Single Channel Gateway such as LG01/LG02? ==
1852 )))
1853
1854 (((
1855 (((
1856 In this case, users need to set LT-33222-L to work in ABP mode & transmit in only one frequency.
1857 )))
1858 )))
1859
1860 (((
1861 (((
1862 Assume we have a LG02 working in the frequency 868400000 now , below is the step.
1863 )))
1864 )))
1865
1866 (((
1867 (% style="color:#4f81bd" %)**Step1**(%%): Log in TTN, Create an ABP device in the application and input the network session key (NETSKEY), app session key (APPSKEY) from the device.
1868 )))
1869
1870 (((
1871 [[image:1653360231087-571.png||height="401" width="727"]]
1872 )))
1873
1874 (((
1875 (% style="color:red" %)Note: user just need to make sure above three keys match, User can change either in TTN or Device to make then match. In TTN, NETSKEY and APPSKEY can be configured by user in setting page, but Device Addr is generated by TTN.
1876 )))
1877
1878 (((
1879 (% style="color:#4f81bd" %)**Step2**(%%)**: **Run AT Command to make LT work in Single frequency & ABP mode. Below is the AT commands:
1880 )))
1881
1882 (((
1883 (% style="background-color:#dcdcdc" %)123456 (%%) Enter Password to have AT access.
1884 (% style="background-color:#dcdcdc" %)AT+FDR  (%%) Reset Parameters to Factory Default, Keys Reserve
1885 (% style="background-color:#dcdcdc" %)123456  (%%) Enter Password to have AT access.
1886 (% style="background-color:#dcdcdc" %)AT+NJM=0 (%%)Set to ABP mode
1887 (% style="background-color:#dcdcdc" %)AT+ADR=0 (%%)Set the Adaptive Data Rate Off
1888 (% style="background-color:#dcdcdc" %)AT+DR=5 (%%) Set Data Rate (Set AT+DR=3 for 915 band)
1889 (% style="background-color:#dcdcdc" %)AT+TDC=60000  (%%)Set transmit interval to 60 seconds
1890 (% style="background-color:#dcdcdc" %)AT+CHS=868400000 (%%)Set transmit frequency to 868.4Mhz
1891 (% style="background-color:#dcdcdc" %)AT+DADDR=26 01 1A F1(%%) Set Device Address to 26 01 1A F1
1892 (% style="background-color:#dcdcdc" %)ATZ                (%%)Reset MCU
1893 )))
1894
1895 (((
1896 As shown in below:
1897 )))
1898
1899 [[image:1653360498588-932.png||height="485" width="726"]]
1900
1901
1902 == 5.4 Can I see counting event in Serial? ==
1903
1904 (((
1905 User can run AT+DEBUG command to see the counting event in serial. If firmware too old and doesn’t support AT+DEBUG. User can update to latest firmware first.
1906
1907
1908 == 5.5 Can i use point to point communication for LT-22222-L? ==
1909
1910 Yes, please refer [[Point to Point Communication>>doc:Main. Point to Point Communication of LT-22222-L.WebHome]]
1911
1912
1913 )))
1914
1915 (((
1916 = 6. Trouble Shooting =
1917 )))
1918
1919 (((
1920 (((
1921 == 6.1 Downlink doesn’t work, how to solve it? ==
1922 )))
1923 )))
1924
1925 (((
1926 Please see this link for how to debug: [[LoRaWAN Communication Debug>>doc:Main.LoRaWAN Communication Debug.WebHome||anchor="H5.1Howitwork"]]
1927
1928
1929 )))
1930
1931 (((
1932 == 6.2 Have trouble to upload image. ==
1933 )))
1934
1935 (((
1936 See this link for trouble shooting: [[Firmware Upgrade Instruction>>doc:Main.Firmware Upgrade Instruction for STM32 base products.WebHome]]
1937 )))
1938
1939 (((
1940
1941 )))
1942
1943 (((
1944 == 6.3 Why I can’t join TTN in US915 /AU915 bands? ==
1945 )))
1946
1947 (((
1948 It might be about the channels mapping. [[Please see this link for detail>>doc:Main.LoRaWAN Communication Debug.WebHome||anchor="H2.NoticeofUS9152FCN4702FAU915Frequencyband"]]
1949 )))
1950
1951 (((
1952
1953 )))
1954
1955 (((
1956 = 7. Order Info =
1957 )))
1958
1959 (((
1960 (((
1961 (% style="color:#4f81bd" %)**LT-22222-L-XXX:**
1962 )))
1963 )))
1964
1965 (((
1966 (((
1967 (% style="color:#4f81bd" %)**XXX:**
1968 )))
1969 )))
1970
1971 (((
1972 * (((
1973 (% style="color:#4f81bd" %)**EU433**(%%): LT with frequency bands EU433
1974 )))
1975 )))
1976
1977 (((
1978 * (((
1979 (% style="color:#4f81bd" %)**EU868**(%%): LT with frequency bands EU868
1980 )))
1981 )))
1982
1983 (((
1984 * (((
1985 (% style="color:#4f81bd" %)**KR920**(%%): LT with frequency bands KR920
1986 )))
1987 )))
1988
1989 (((
1990 * (((
1991 (% style="color:#4f81bd" %)**CN470**(%%): LT with frequency bands CN470
1992 )))
1993 )))
1994
1995 (((
1996 * (((
1997 (% style="color:#4f81bd" %)**AS923**(%%): LT with frequency bands AS923
1998 )))
1999 )))
2000
2001 (((
2002 * (((
2003 (% style="color:#4f81bd" %)**AU915**(%%): LT with frequency bands AU915
2004 )))
2005 )))
2006
2007 (((
2008 * (((
2009 (% style="color:#4f81bd" %)**US915**(%%): LT with frequency bands US915
2010 )))
2011 )))
2012
2013 (((
2014 * (((
2015 (% style="color:#4f81bd" %)**IN865**(%%): LT with frequency bands IN865
2016 )))
2017 )))
2018
2019 (((
2020 * (((
2021 (% style="color:#4f81bd" %)**CN779**(%%): LT with frequency bands CN779
2022
2023
2024 )))
2025
2026 = 8. Packing Info =
2027 )))
2028
2029 (((
2030 (((
2031 **Package Includes**:
2032 )))
2033 )))
2034
2035 (((
2036 (((
2037 * LT-22222-L I/O Controller x 1
2038 * Stick Antenna for LoRa RF part x 1
2039 * Bracket for controller x1
2040 * Program cable x 1
2041 )))
2042 )))
2043
2044 (((
2045 (((
2046 **Dimension and weight**:
2047 )))
2048 )))
2049
2050 (((
2051 (((
2052 * Device Size: 13.5 x 7 x 3 cm
2053 * Device Weight: 105g
2054 * Package Size / pcs : 14.5 x 8 x 5 cm
2055 * Weight / pcs : 170g
2056
2057
2058 )))
2059 )))
2060
2061 (((
2062 = 9. Support =
2063 )))
2064
2065 * (((
2066 (((
2067 Support is provided Monday to Friday, from 09:00 to 18:00 GMT+8. Due to different timezones we cannot offer live support. However, your questions will be answered as soon as possible in the before-mentioned schedule.
2068 )))
2069 )))
2070 * (((
2071 (((
2072 Provide as much information as possible regarding your enquiry (product models, accurately describe your problem and steps to replicate it etc) and send a mail to
2073 )))
2074 )))
2075
2076 (((
2077 (((
2078 [[support@dragino.com>>url:file:///D:/市场资料/说明书/LoRa/LT系列/support@dragino.com]]
2079
2080
2081 )))
2082
2083 (((
2084 = 10. Reference​​​​​ =
2085
2086 * Product Page:
2087
2088 LT-22222-L: [[http:~~/~~/www.dragino.com/products/lora-lorawan-end-node/item/156-lt-22222-l.html>>url:http://www.dragino.com/products/lora-lorawan-end-node/item/156-lt-22222-l.html]]
2089
2090 * [[Image Download>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/image/]]
2091 * [[AT Command Manual>>url:http://www.dragino.com/downloads/index.php?dir=LT_LoRa_IO_Controller/LT33222-L/]]
2092 * [[Hardware Source>>url:https://github.com/dragino/Lora/tree/master/LT/LT-33222-L/v1.0]]
2093 )))
2094 )))