12
13 = 1.Door sensor =
14
15
16 Application: Connect to Door Sensor detect door open / close and send to IoT server
17
18 Sensor Type: Normal Close Type Door Sensor as below
19
20 [[image:image-20240424100239-8.png||height="227" width="946"]]
21
22
23 == 1.1 Hardware Connection ==
24
25 * (((
26 LHT65N VDD <~-~-> one wire of Door Sensor
27 )))
28 * (((
29 LHT65N Interrupt Pin <~-~-> one wire of Door Sensor
30 )))
31
32 [[image:image-20240424100415-9.png||height="355" width="796"]]
33
34 == 1.2 Software Configuration ==
35
36 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
37
38 * (((
39 AT Command : AT+EXT=4,1
40 )))
41 * (((
42 Downlink Command: 0xA20401 :   Same as AT+EXT=4,1
43 )))
44
45 Enlarge the TDC time so LHT65N will send Keep Alive message every 12 hours so to save battery life.
46
47 * (((
48 AT Command :AT+TDC=43200000
49 )))
50 * (((
51 Downlink Command:  0x0100A8C0   Same as AT+TDC=43200000
52 )))
53
54 == 1.3 Test Result ==
55
56 Move the magnet part to generate Open / Close event and check the uplink packet in the platform.
57
58 [[image:image-20240424100951-10.jpeg||height="333" width="741"]]
59
60 [[image:image-20240424100951-11.png||height="280" width="1247"]]
61
62
63 == 1.4 Power Consumption Notice ==
64
65
66 Connect a Normal Close Door Sensor won't increase sleep current (~~6uA). The power consumption mainly depends on the how many open/close event happen every day.
67
68
69
70
71 = 2. Water Sensor =
72
73
74 Application: Connect to Water leakage Sensor detect door open / close and send to IoT server
75
76
77 == 2.1 Hardware Connection ==
78
79 * LHT65N VDD <~-~-> one wire of water leakage Sensor
80 * LHT65N Interrupt Pin <~-~-> one wire of water leakage Sensor
81
82 [[image:image-20240802092327-1.jpeg||height="312" width="694"]]
83
84 == 2.2  Software Configuration ==
85
86 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
87
88 * AT Command : AT+EXT=4,1
89 * Downlink Command:  0xA20401 :   Same as AT+EXT=4,1
90
91 Enlarge the TDC time so LHT65N will send Keep Alive message every 12 hours so to save battery life.
92
93 * (((
94 AT Command :AT+TDC=43200000
95 )))
96 * (((
97 Downlink Command:  0x0100A8C0   Same as AT+TDC=4320000
98 )))
99
100 == 2.3 Test Result ==
101
102
103 Partial contact of the sensor probe with water generates open/close events and checks for upstream packets in the platform.
104
105 [[image:image-20240424101908-12.png||height="331" width="435"]]
106
107 [[image:image-20240424101927-13.png||height="303" width="766"]]
108
109
110 == 2.4 Power Consumption Notice ==
111
112 * Connecting the water leak sensor increases the sleep current (~~40uA). When using a water leak sensor, the battery life will be reduced.
113
114 [[image:image-20240424102048-14.png||height="495" width="926"]]
115
116 When the probe comes into contact with water, it will increase the low power consumption by about 300uA.
117
118 Then when it is out of contact with water, the power consumption will slowly drop. The reason for the slow drop is that there are water beads hanging on the surface of the probe. When it dries, It will reduce power consumption.
119
120
121
122 = 3 Smoke Sensor =
123
124 Application:  Mainly suitable for hotels, warehouses, guesthouses, restaurants, hostels, factories, oil field well teams, prefabricated houses and other public places.When it is detected that the smoke in the air reaches a certain concentration value, an alarm signal is triggered immediately. False alarms are likely to occur when dew, oil smoke, water vapor, sudden temperature changes, corrosive gases, strong airflow or air conditioning, or outdoor environments occur.
125
126 * Technical Notes:
127
128 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:510px" %)
129 |=(% style="width: 156px;background-color:#4F81BD;color:white" %)**Parameter name**|=(% style="width: 137px;background-color:#4F81BD;color:white" %)**Explanation**
130 |(% style="width:156px" %)Power|(% style="width:137px" %)DC 3V(Two 1.5V alkaline batteries)
131 |(% style="width:156px" %)Indicator lights|(% style="width:137px" %)It will flash once every minute in the monitoring state, and it will stay on when smoke is detected.
132 |(% style="width:156px" %)Working temperature|(% style="width:137px" %)-10℃~~+50℃
133 |(% style="width:156px" %)Working humidity|(% style="width:137px" %)≤95% (Under 40℃ working environment)
134
135 == 3.1 Hardware Connection ==
136
137 * LHT65N VDD <~-~-> Sound vibration film red line
138 * LHT65N Interrupt Pin <~-~-> sound vibration film black line
139
140 [[image:image-20240428090354-1.jpeg||height="456" width="1015"]]
141
142
143 == 3.2 Software Configuration ==
144
145
146 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
147
148 * AT Command : AT+EXT=4,1
149 * Downlink Command:  0xA20401 :   Same as AT+EXT=4,1
150
151 Enlarge the TDC time so LHT65N will send Keep Alive message every 12 hours so to save battery life.
152
153 * (((
154 AT Command :AT+TDC=43200000
155 )))
156 * (((
157 Downlink Command:  0x0100A8C0   Same as AT+TDC=4320000
158 )))
159
160 == 3.3 Test Result ==
161
162
163 [[image:image-20240428090354-2.png||height="771" width="1011"]]
164
165 [[image:image-20240428090354-3.png||height="314" width="1015"]]
166
167 When triggered, the node will send data packets twice. When it is not triggered or the trigger ends, it needs to wait for the TDC time to send data packets.
168
169
170 == 3.4 Power Consumption Notice ==
171
172 When there is smoke detect, the smoke sensor will be trigger , there will be sound from speaker and trigger the LHT65N to send uplink
173
174
175
176 = 4. SOS switch sensor =
177
178 Application:Connected to the SOS switch, the sensor detects whether an alarm is triggered and sends it to the IoT server.
179
180 When the red button is pressed, 1 and 2 are connected, and 1 and 3 are disconnected. When you release your hand, the red button automatically pops up, 1 and 2 are disconnected, 1 and 3 are connected, and it automatically resets without a key; This emergency help button is used for emergencies or emergencies. Press this red button to give an alarm and SOS emergency call (COM is 1, NO is 2, NC is 3)
181
182 == 4.1 Hardware Connection ==
183
184
185 LHT65N VDD <~-~--> COM port of the SOS button
186
187 LHT65N Interrupt Pin <~-~-> The NO port of the SOS button
188
189 [[image:image-20240429133616-4.jpeg||height="937" width="1065"]]
190
191
192 == 4.2 Software Configuration ==
193
194
195 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
196
197 * AT Command : AT+EXT=4,1
198 * Downlink Command:  0xA20401 :   Same as AT+EXT=4,1
199
200 Enlarge the TDC time so LHT65N will send Keep Alive message every 12 hours so to save battery life.
201
202 * AT Command :AT+TDC=86400000
203 * Downlink Command:  01015180  Same as AT+TDC=86400000
204
205 == 4.3 Test Result ==
206
207 [[image:image-20240429133616-5.jpeg||height="685" width="753"]]
208
209 Note: When the LHT65N triggers an interrupt packet, it needs to wait 6s before a new trigger is generated.
210
211 When the button is pressed, the SOS button will be triggered, and the LHT65N will also be triggered to send the uplink signal.
212
213
214 == 4.4 Power Consumption Notice ==
215
216 Connect SOS button Sensor won't increase sleep current (~~6uA). The power consumption mainly depends on the how many open/close event happen every day.
217
218
219 = 5. Flow sensor =
220
221 Application: It detects water flow volume and uplink to IoT server via LoRaWAN network. User can use this to monitor the water usage for buildings.
222
223 == 5.1 Hardware Connection ==
224
225 LHT65N VDD <~-~--> Flow sensor red line
226
227 LHT65N Interrupt Pin <~-~-> Flow sensor Signal line
228
229 LHT65N GND <~-~--> Flow sensor black line(Note: If the sensor does not need power supply, please connect the red line (rising edge trigger) or the black line (falling edge trigger) as needed.)
230
231 [[image:image-20240506111329-1.jpeg||height="654" width="388"]]
232
233
234 == 5.2 Software Configuration ==
235
236 Note: Because the traffic sensor is a counting sensor, the node can only be set in counting mode.
237
238 Set LHT65N to Counting Mode so device will uplink when there is open/close event
239
240 * AT Command : AT+EXT=8,1
241 * Downlink Command:  0xA2080101 :   Same as AT+EXT=8,1
242
243 Enlarge the TDC time so LHT65N will send Keep Alive message every 12 hours so to save battery life.
244
245 * (((
246 AT Command :AT+TDC=43200000
247 )))
248 * (((
249 Downlink Command:  0x0100A8C0   Same as AT+TDC=4320000
250 )))
251
252 == 5.3 Test Result ==
253
254 [[image:image-20240506111329-2.jpeg||height="533" width="336"]]
255
256 When the water passes through the flow sensor, the cumulative count will be generated (note: when installing the flow sensor, it is necessary to pay attention to the inlet direction of the installation).
257
258 [[image:image-20240506111329-3.png||height="377" width="1134"]]
259
260
261 == 5.4 Power Consnmption Notice ==
262