11
12
13 = 1.Door sensor =
14
15
16 Application: Connect to Door Sensor detect door open / close and send to IoT server
17
18 Sensor Type: Normal Close Type Door Sensor as below
19
20 [[image:image-20240424100239-8.png||height="227" width="946"]]
21
22
23 == 1.1 Hardware Connection ==
24
25 * (((
26 LHT65N VDD <~-~-> one wire of Door Sensor
27 )))
28 * (((
29 LHT65N Interrupt Pin <~-~-> one wire of Door Sensor
30 )))
31
32 [[image:image-20240424100415-9.png||height="355" width="796"]]
33
34 == 1.2 Software Configuration ==
35
36 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
37
38 * (((
39 AT Command : AT+EXT=4,1
40 )))
41 * (((
42 Downlink Command: 0xA20401 :   Same as AT+EXT=4,1
43 )))
44
45 Enlarge the TDC time so LHT65N will send Keep Alive message every 24 hours so to save battery life.
46
47 * (((
48 AT Command :AT+TDC=86400000
49 )))
50 * (((
51 Downlink Command:  0x01015180   Same as AT+TDC=86400000
52 )))
53
54 == 1.3 Test Result ==
55
56 Move the magnet part to generate Open / Close event and check the uplink packet in the platform.
57
58 [[image:image-20240424100951-10.jpeg||height="333" width="741"]]
59
60 [[image:image-20240424100951-11.png||height="280" width="1247"]]
61
62
63 == 1.4 Power Consumption Notice ==
64
65
66 Connect a Normal Close Door Sensor won't increase sleep current (~~6uA). The power consumption mainly depends on the how many open/close event happen every day.
67
68
69
70
71 = 2. Water Sensor =
72
73
74 Application: Connect to Water leakage Sensor detect door open / close and send to IoT server
75
76
77 == 2.1 Hardware Connection ==
78
79 * LHT65N VDD <~-~-> one wire of water leakage Sensor
80 * LHT65N Interrupt Pin <~-~-> one wire of water leakage Sensor
81
82 [[image:image-20240802092327-1.jpeg||height="312" width="694"]]
83
84 == 2.2  Software Configuration ==
85
86 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
87
88 * AT Command : AT+EXT=4,1
89 * Downlink Command:  0xA20401 :   Same as AT+EXT=4,1
90
91 Enlarge the TDC time so LHT65N will send Keep Alive message every 24 hours so to save battery life.
92
93 * AT Command :AT+TDC=86400000
94 * Downlink Command:  01015180  Same as AT+TDC=86400000
95
96 == 2.3 Test Result ==
97
98
99 Partial contact of the sensor probe with water generates open/close events and checks for upstream packets in the platform.
100
101 [[image:image-20240424101908-12.png||height="331" width="435"]]
102
103 [[image:image-20240424101927-13.png||height="303" width="766"]]
104
105
106 == 2.4 Power Consumption Notice ==
107
108 * Connecting the water leak sensor increases the sleep current (~~40uA). When using a water leak sensor, the battery life will be reduced.
109
110 [[image:image-20240424102048-14.png||height="495" width="926"]]
111
112 When the probe comes into contact with water, it will increase the low power consumption by about 300uA.
113
114 Then when it is out of contact with water, the power consumption will slowly drop. The reason for the slow drop is that there are water beads hanging on the surface of the probe. When it dries, It will reduce power consumption.
115
116
117
118 = 3 Smoke Sensor =
119
120 Application:  Mainly suitable for hotels, warehouses, guesthouses, restaurants, hostels, factories, oil field well teams, prefabricated houses and other public places.When it is detected that the smoke in the air reaches a certain concentration value, an alarm signal is triggered immediately. False alarms are likely to occur when dew, oil smoke, water vapor, sudden temperature changes, corrosive gases, strong airflow or air conditioning, or outdoor environments occur.
121
122 * Technical Notes:
123
124 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:510px" %)
125 |=(% style="width: 156px;background-color:#4F81BD;color:white" %)**Parameter name**|=(% style="width: 137px;background-color:#4F81BD;color:white" %)**Explanation**
126 |(% style="width:156px" %)Power|(% style="width:137px" %)DC 3V(Two 1.5V alkaline batteries)
127 |(% style="width:156px" %)Indicator lights|(% style="width:137px" %)It will flash once every minute in the monitoring state, and it will stay on when smoke is detected.
128 |(% style="width:156px" %)Working temperature|(% style="width:137px" %)-10℃~~+50℃
129 |(% style="width:156px" %)Working humidity|(% style="width:137px" %)≤95% (Under 40℃ working environment)
130
131 == 3.1 Hardware Connection ==
132
133 * LHT65N VDD <~-~-> Sound vibration film red line
134 * LHT65N Interrupt Pin <~-~-> sound vibration film black line
135
136 [[image:image-20240428090354-1.jpeg||height="456" width="1015"]]
137
138
139 == 3.2 Software Configuration ==
140
141
142 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
143
144 * AT Command : AT+EXT=4,1
145 * Downlink Command:  0xA20401 :   Same as AT+EXT=4,1
146
147 Enlarge the TDC time so LHT65N will send Keep Alive message every 24 hours so to save battery life.
148
149 * AT Command :AT+TDC=86400000
150 * Downlink Command:  01015180  Same as AT+TDC=86400000
151
152 == 3.3 Test Result ==
153
154
155 [[image:image-20240428090354-2.png||height="771" width="1011"]]
156
157 [[image:image-20240428090354-3.png||height="314" width="1015"]]
158
159 When triggered, the node will send data packets twice. When it is not triggered or the trigger ends, it needs to wait for the TDC time to send data packets.
160
161
162 == 3.4 Power Consumption Notice ==
163
164 When there is smoke detect, the smoke sensor will be trigger , there will be sound from speaker and trigger the LHT65N to send uplink
165
166
167
168 = 4. SOS switch sensor =
169
170 Application:Connected to the SOS switch, the sensor detects whether an alarm is triggered and sends it to the IoT server.
171
172 When the red button is pressed, 1 and 2 are connected, and 1 and 3 are disconnected. When you release your hand, the red button automatically pops up, 1 and 2 are disconnected, 1 and 3 are connected, and it automatically resets without a key; This emergency help button is used for emergencies or emergencies. Press this red button to give an alarm and SOS emergency call (COM is 1, NO is 2, NC is 3)
173
174 == 4.1 Hardware Connection ==
175
176
177 LHT65N VDD <~-~--> COM port of the SOS button
178
179 LHT65N Interrupt Pin <~-~-> The NO port of the SOS button
180
181 [[image:image-20240429133616-4.jpeg||height="937" width="1065"]]
182
183
184 == 4.2 Software Configuration ==
185
186
187 Set LHT65N to Interrupt Mode so device will uplink when there is open/close event
188
189 * AT Command : AT+EXT=4,1
190 * Downlink Command:  0xA20401 :   Same as AT+EXT=4,1
191
192 Enlarge the TDC time so LHT65N will send Keep Alive message every 24 hours so to save battery life.
193
194 * AT Command :AT+TDC=86400000
195 * Downlink Command:  01015180  Same as AT+TDC=86400000
196
197 == 4.3 Test Result ==
198
199 [[image:image-20240429133616-5.jpeg||height="685" width="753"]]
200
201 Note: When the LHT65N triggers an interrupt packet, it needs to wait 6s before a new trigger is generated.
202
203 When the button is pressed, the SOS button will be triggered, and the LHT65N will also be triggered to send the uplink signal.
204
205
206 == 4.4 Power Consumption Notice ==
207
208 Connect SOS button Sensor won't increase sleep current (~~6uA). The power consumption mainly depends on the how many open/close event happen every day.
209
210
211 = 5. Flow sensor =
212
213 Application: It detects water flow volume and uplink to IoT server via LoRaWAN network. User can use this to monitor the water usage for buildings.
214
215 == 5.1 Hardware Connection ==
216
217 LHT65N VDD <~-~--> Flow sensor red line
218
219 LHT65N Interrupt Pin <~-~-> Flow sensor Signal line
220
221 LHT65N GND <~-~--> Flow sensor black line(Note: If the sensor does not need power supply, please connect the red line (rising edge trigger) or the black line (falling edge trigger) as needed.)
222
223 [[image:image-20240506111329-1.jpeg||height="654" width="388"]]
224
225
226 == 5.2 Software Configuration ==
227
228 Note: Because the traffic sensor is a counting sensor, the node can only be set in counting mode.
229
230 Set LHT65N to Counting Mode so device will uplink when there is open/close event
231
232 * AT Command : AT+EXT=8,1
233 * Downlink Command:  0xA2080101 :   Same as AT+EXT=8,1
234
235 Enlarge the TDC time so LHT65N will send Keep Alive message every 24 hours so to save battery life.
236
237 * AT Command :AT+TDC=86400000
238 * Downlink Command:  01015180  Same as AT+TDC=86400000
239
240 == 5.3 Test Result ==
241
242 [[image:image-20240506111329-2.jpeg||height="533" width="336"]]
243
244 When the water passes through the flow sensor, the cumulative count will be generated (note: when installing the flow sensor, it is necessary to pay attention to the inlet direction of the installation).
245
246 [[image:image-20240506111329-3.png||height="377" width="1134"]]
247
248
249 == 5.4 Power Consnmption Notice ==
250
251 Connect Flow Sensor won't increase sleep current (~~6uA). The power consumption mainly depends on the how many counting event happen every day.