... ... @@ -905,16 +905,16 @@
905 905  
906 906  Explique:
907 907  
908 -* (% style="color:#037691" %)**Parâmetro 1: **(%%)Set Working Mode to **Mode 3**
909 -* (% style="color:#037691" %)**Parâmetro 2:**(%%) Set the temperature sampling mode to** 1**(1:DS18B20;2:TMP117;3:** **Internal GXHT30).
910 -* (% style="color:#037691" %)**Parâmetro 3: **(%%)Sampling Interval is **60**s.
911 -* (% style="color:#037691" %)**Parâmetro 4: **(%%)When there is **20** sampling dats, Device will send these data via one uplink. (max value is 60, means max 60 sampling in one uplink)
912 -* (% style="color:#037691" %)**Parâmetro 5: & Parâmetro 6: **(%%)Temperature alarm range is **-16** to **32**°C,
913 -* (% style="color:#037691" %)**Parâmetro 7:**(%%) 1 to enable temperature alarm, **0** to disable the temperature alarm. If alarm is enabled, a data will be sent immediately  if temperate exceeds the Alarm range.
908 +* (% style="color:#037691" %)**Parâmetro 1: **(%%)Definir o Modo de Trabalho para o Modo 3
909 +* (% style="color:#037691" %)**Parâmetro 2:**(%%) Ajuste o modo de amostragem de temperatura para 1 (1: DS18B20; 2: TMP117;3: GXHT30 interno).
910 +* (% style="color:#037691" %)**Parâmetro 3: **(%%)Intervalo de amostragem é de 60.
911 +* (% style="color:#037691" %)**Parâmetro 4: **(%%)Quando houver 20 datas de amostragem, o dispositivo enviará esses dados por meio de um uplink. (valor máximo é 60, significa amostragem máxima 60 em um uplink)
912 +* (% style="color:#037691" %)**Parâmetro 5: & Parâmetro 6: **(%%)A escala do alarme da temperatura é -16 a 32°C,
913 +* (% style="color:#037691" %)**Parâmetro 7:**(%%) 1 para ativar o alarme de temperatura, 0 para desativar o alarme de temperatura. Se o alarme estiver ativado, um dado se enviado imediatamente se o temperamento exceder o intervalo de alarme.
914 914  
915 -(% style="color:#4f81bd" %)**Downlink Command:**
915 +(% style="color:#4f81bd" %)**Comando Downlink:**
916 916  
917 -**Example: **A50301003C14FFF0002001
917 +**Exemplo: A50301003C14FFF0002001**
918 918  
919 919  MOD=03
920 920  
... ... @@ -922,7 +922,7 @@
922 922  
923 923  CITEMP=003C(S)
924 924  
925 -Total number of acquisitions=14
925 +Número total de aquisições=14
926 926  
927 927  TEMPlow=FFF0
928 928  
... ... @@ -931,49 +931,49 @@
931 931  ARTEMP=01
932 932  
933 933  
934 -**Uplink payload( Fport=3)**
934 +**Carga útil de ligação ascendente (Fport=3)**
935 935  
936 -**Example: CBEA**01**0992**//0A41//**09C4**
936 +**Exemplo: CBEA0109920A4109C4**
937 937  
938 938  BatV=CBEA
939 939  
940 940  TEMP=DS18B20
941 941  
942 -Temp1=0992  ~/~/ 24.50℃
942 +Temp1=0992  ~/~/ 24,50℃
943 943  
944 -Temp2=0A41  ~/~/ 26.25℃
944 +Temp2=0A41  ~/~/ 26,25℃
945 945  
946 -Temp3=09C4  ~/~/ 25.00℃
946 +Temp3=09C4 ~/~/ 25,00℃
947 947  
948 -(% style="color:red" %)**Note: This uplink will automatically select the appropriate DR according to the data length**
948 +(% style="color:red" %)**Nota: Este uplink selecionará automaticamente o DR apropriado de acordo com o comprimento dos dados**
949 949  
950 -(% style="color:red" %)** In this mode, the temperature resolution of ds18b20 is 0.25℃ to save power consumption**
950 +(% style="color:red" %)** Neste modo, a resolução da temperatura de ds18b20 é 0,25℃ para economizar o consumo de energia**
951 951  )))
952 952  
953 953  
954 -=== 2.7.2 ALARM MODE ( Before v1.3.1 firmware) ===
954 +=== 2.7.2 MODO DE ALARMA (Antes do firmware v1.3.1) ===
955 955  
956 956  
957 957  (% class="box infomessage" %)
958 958  (((
959 959  (((
960 -**AT+WMOD=1**:  Enable/disable alarm mode. (0: Disabled, 1: Enabled Temperature Alarm for onboard temperature sensor)
960 +**AT+WMOD=1**:  EActivar/desactivar o modo de alarme. (0: Desativado, 1: Alarme de temperatura ativado para sensor de temperatura a bordo)
961 961  )))
962 962  
963 963  (((
964 -**AT+CITEMP=1**:  The interval between checking the alarm temperature. (In minutes)
964 +**AT+CITEMP=1**:  O intervalo entre a verificação da temperatura do alarme. (Em minutos)
965 965  )))
966 966  
967 967  (((
968 -**AT+ARTEMP**:  Gets or sets the alarm range of the internal temperature sensor
968 +**AT+ARTEMP**:  Obtém ou define a faixa de alarme do sensor de temperatura interno
969 969  )))
970 970  
971 971  (((
972 -(% _mstmutation="1" %)**AT+ARTEMP=? **(%%):  Gets the alarm range of the internal temperature sensor(% style="display:none" %)
972 +(% _mstmutation="1" %)**AT+ARTEMP=? **(%%):  Obtém a faixa de alarme do sensor de temperatura interno(% style="display:none" %)
973 973  )))
974 974  
975 975  (((
976 -**AT+ARTEMP=45,105**:  Set the internal temperature sensor alarm range from 45 to 105.
976 +**AT+ARTEMP=45,105**:  Defina a faixa interna do alarme do sensor de temperatura de 45 a 105.
977 977  )))
978 978  )))
979 979  