LHT52 - LoRaWAN Temperature & Humidity Sensor User Manual

Version 174.2 by Xiaoling on 2022/06/21 09:50

1655774244188-589.png

Table of Contents:

1.  Introduction

1.1  What is LHT52 Temperature & Humidity Sensor

 

The Dragino LHT52 Temperature & Humidity sensor is a Long Range LoRaWAN Sensor. It includes a built-in Temperature & Humidity sensor and has a USB Type-C sensor connector to connect to external sensors such as external Temperature Sensor.

LHT52 senses environment temperature and humidity and send these values via long-range wireless LoRaWAN protocol. It targets professional wireless sensor network applications such as food service, smart metering, smart cities, building automation, and so on.

LHT52 supports 2 x AAA batteries and works for a long time up to several years. Use can replace the batteries easily after they are finished.

LHT52 is fully compatible with LoRaWAN v1.0.3 protocol, it can work with standard LoRaWAN gateway.

LHT52 supports Datalog feature to make sure users won’t miss sensor data. It records sensor value for every uplink. These values can be retrieved by LoRaWAN server via downlink command.

LHT52 supports temperature alarm feature. It can uplink alarm in a short interval while temperature exceeds preset limits.

*Battery life depends how often to send data, please see battery analyzer.

1655774519494-861.png

 

1.2  Features

  • Wall Attachable.
  • LoRaWAN v1.0.3 Class A protocol.
  • Built-in Temperature & Humidity sensor
  • Optional External Probe
  • Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915
  • AT Commands to change parameters
  • Remote configure parameters via LoRaWAN Downlink
  • Firmware upgradable via program port
  • Support 2 x AAA LR03 batteries.
  • Datalog feature
  • IP Rating: IP52

1.3  Specification

 

Built-in Temperature Sensor:

  • Resolution: 0.01 °C
  • Accuracy Tolerance: Typ ±0.3 °C
  • Long Term Drift: < 0.02 °C/yr
  • Operating Range: -20 ~ 50 °C

 

Built-in Humidity Sensor:

  • Resolution: 0.1 %RH
  • Accuracy Tolerance: Typ ±3 %RH
  • Long Term Drift: < 0.02 °C/yr
  • Operating Range: 0 ~ 99.0 %RH(no Dew)

 

 

1.4  Power Consumption

LHT52 (without external sensor): Idle: 5uA, Transmit: max 110mA

LHT52 + External Temperature Probe (AS-01): Idle: 6uA, Transmit: max 110mA.

1.5  Storage & Operation Temperature

-20°C to +50°C

1.6  Applications

  • Smart Buildings & Home Automation
  • Logistics and Supply Chain Management
  • Smart Metering
  • Smart Agriculture
  • Smart Cities
  • Smart Factory

 

2.  Operation Mode

2.1 How it work?

Each LHT52 is shipped with a worldwide unique set of LoRaWAN OTAA keys. To use LHT52 in a LoRaWAN network, user needs to input the OTAA keys in LoRaWAN network server. After this, if LHT52 is under this LoRaWAN network coverage, LHT52 can join the LoRaWAN network and start to transmit sensor data. The default period for each uplink is 20 minutes.

 

 

2.2 How to Activate LHT52?

 1.  Open enclosure from below position.

image-20220621093835-1.png

 2.  Insert 2 x AAA LR03 batteries.

image-20220621093835-2.png

 3.  Press the reset button to activate device.

image-20220621093835-3.png  

User can check LED Status to know the working state of LHT52.

2.3 Example to join LoRaWAN network

This section shows an example for how to join the TheThingsNetwork LoRaWAN IoT server. Usages with other LoRaWAN IoT servers are of similar procedure.

1655775912928-657.png

Assume the DLOS8 is already set to connect to TTN V3 network . We need to add the LHT52 device in TTN V3 portal.  

Step 1:  Create a device in TTN V3 with the OTAA keys from LHT52.

Each LHT52 is shipped with a sticker with the default DEV EUI as below:

image-20220617150003-1.jpeg

Enter these keys in the LoRaWAN Server portal. Below is TTN V3 screen shot:

Add APP EUI in the application.

choose to create the device manually.

Add APP KEY and DEV EUI

image-20220522232916-3.png

1655776122894-257.png

Default mode OTAA

1655776241177-240.png

Input APP EUI,  APP KEY and DEV EUI:

image-20220522233118-7.png

2.3.2 Step 2: Activate LHT65N by pressing the ACT button for more than 5 seconds.

Use ACT button to activate LHT65N and it will auto-join to the TTN V3 network. After join success, it will start to upload sensor data to TTN V3 and user can see in the panel.

image-20220522233300-8.png

2.4 Uplink Payload

The uplink payload includes totally 11 bytes. Uplink packets use FPORT=2 and every 20 minutes send one uplink by default. 

After each uplink, the BLUE LED will blink once.

Size(bytes)

2

2

2

1

4

Value

Ext #

  • The First 6 bytes: has fix meanings for every LHT65N.
  • The 7th byte (EXT #): defines the external sensor model. 
  • The 8th ~ 11th byte: the value for external sensor value. The definition is based on external sensor type. (If EXT=0, there won’t be these four bytes.)

2.4.1 Decoder in TTN V3

When the uplink payload arrives TTNv3, it shows HEX format and not friendly to read. We can add LHT65N decoder in TTNv3 for friendly reading.

Below is the position to put the decoder and LHT65N decoder can be download from here:

https://www.dropbox.com/sh/r2i3zlhsyrpavla/AAB1sZw3mdT0K7XjpHCITt13a?dl=0 

image-20220522234118-10.png

2.4.2 BAT-Battery Info

These two bytes of BAT include the battery state and the actually voltage

image-20220523152839-18.png

image-20220522235639-1.png

Check the battery voltage for LHT65N.

  • BAT status=(0Xcba4>>14)&0xFF=11(B),very good
  • Battery Voltage =0xCBF6&0x3FFF=0x0BA4=2980mV

2.4.3 Built-in Temperature

image-20220522235639-2.png

  • Temperature:  0x0ABB/100=27.47℃

image-20220522235639-3.png

  • Temperature:  (0xF5C6-65536)/100=-26.18℃

2.4.4 Built-in Humidity

image-20220522235639-4.png

  • Humidity:    0x025C/10=60.4%

2.4.5 Ext #

Bytes for External Sensor:

image-20220523152822-17.png

2.4.6 Ext value

2.4.6.1 Ext=1, E3 Temperature Sensor

image-20220522235639-5.png

  • DS18B20 temp=0x0ADD/100=27.81℃

The last 2 bytes of data are meaningless

image-20220522235639-6.png

  • External temperature= (0xF54F-65536)/100=-27.37℃

The last 2 bytes of data are meaningless

If the external sensor is 0x01, and there is no external temperature connected. The temperature will be set to 7FFF which is 327.67℃

2.4.6.2 Ext=9, E3 sensor with Unix Timestamp

Timestamp mode is designed for LHT65N with E3 probe, it will send the uplink payload with Unix timestamp. With the limitation of 11 bytes (max distance of AU915/US915/AS923 band), the time stamp mode will be lack of BAT voltage field, instead, it shows the battery status. The payload is as below:

Size(bytes)

2

2

2

1

4

Value

BAT Status &

Status & Ext

  • Battery status & Built-in Humidity
Bit(bit)[15:14][11:0]
Value

BAT Status

00(b): Ultra Low ( BAT <= 2.50v)

01(b): Low  (2.50v <=BAT <= 2.55v)

10(b): OK   (2.55v <= BAT <=2.65v)

11(b): Good   (BAT >= 2.65v)

  • Status & Ext Byte

image-20220523152434-16.png

  • Poll Message Flag: 1: This message is a poll message reply, 0: means this is a normal uplink.
  • Sync time OK: 1: Set time ok,0: N/A. After time SYNC request is sent, LHT65N will set this bit to 0 until got the time stamp from the application server.
  • Unix Time Request:1: Request server downlink Unix time, 0 : N/A. In this mode, LHT65N will set this bit to 1 every 10 days to request a time SYNC. (AT+SYNCMOD to set this)

2.4.6.3 Ext=6, ADC Sensor (use with E2 Cable)

In this mode, user can connect external ADC sensor to check ADC value. The 3V3_OUT can

be used to power the external ADC sensor; user can control the power on time for this

sensor by setting:

AT+EXT=6,timeout          Time to power this sensor, from 0 ~ 65535ms

2.5 Show data on Datacake

Datacake IoT platform provides a human-friendly interface to show the sensor data, once we have sensor data in TTN V3, we can use Datacake to connect to TTN V3 and see the data in Datacake. Below are the steps:

Step 1: Be sure that your device is programmed and properly connected to the LoRaWAN network.

Step 2: Configure your Application to forward data to Datacake you will need to add integration. Go to TTN V3 Console --> Applications --> Integrations --> Add Integrations.

Add Datacake:

image-20220523000825-7.png

Select default key as Access Key:

image-20220523000825-8.png

In Datacake console (https://datacake.co/) , add LHT65 device.

image-20220523000825-9.png

image-20220523000825-10.png

2.6 Datalog Feature

Datalog Feature is to ensure IoT Server can get all sampling data from Sensor even if the LoRaWAN network is down. For each sampling, LHT65N will store the reading for future retrieving purposes. There are two ways for IoT servers to get datalog from LHT65N.

2.6.1 Ways to get datalog via LoRaWAN

There are two methods:

  1.  IoT Server sends a downlink LoRaWAN command to poll the value for specify time range.
  2.  Set PNACKMD=1, LHT65N will wait for ACK for every uplink, when there is no LoRaWAN network, LHT65N will store the sensor data, and it will send all messages after network recover. 

2.6.2 Unix TimeStamp

LHT65N uses Unix TimeStamp format based on

image-20220523001219-11.png

User can get this time from link:  https://www.epochconverter.com/ :

Below is the converter example

image-20220523001219-12.png

So, we can use AT+TIMESTAMP=1611889405 or downlink 3060137afd00 to set the current time 2021 – Jan -- 29 Friday 03:03:25

2.6.3 Set Device Time

There are two ways to set device’s time:

1. Through LoRaWAN MAC Command (Default settings)

User need to set SYNCMOD=1 to enable sync time via MAC command.

Once LHT65N Joined LoRaWAN network, it will send the MAC command (DeviceTimeReq) and the server will reply with (DeviceTimeAns) to send the current time to LHT65N. If LHT65N fails to get the time from the server, LHT65N will use the internal time and wait for next time request (AT+SYNCTDC to set the time request period, default is 10 days).

Note: LoRaWAN Server need to support LoRaWAN v1.0.3(MAC v1.0.3) or higher to support this MAC command feature, Chirpstack,TTN V3 v3 and loriot support but TTN V3 v2 doesn’t support. If server doesn’t support this command, it will through away uplink packet with this command, so user will lose the packet with time request for TTN V3 v2 if SYNCMOD=1.

 

2. Manually Set Time

User needs to set SYNCMOD=0 to manual time, otherwise, the user set time will be overwritten by the time set by the server.

 

2.6.4 Poll sensor value

User can poll sensor value based on timestamps from the server. Below is the downlink command.

image-20220523152302-15.png

Timestamp start and Timestamp end use Unix TimeStamp format as mentioned above. Devices will reply with all data log during this time period, use the uplink interval.

For example, downlink command 31 5FC5F350 5FC6 0160 05 

Is to check 2020/12/1 07:40:00 to 2020/12/1 08:40:00’s data

Uplink Internal =5s,means LHT65N will send one packet every 5s. range 5~255s.

2.6.5 Datalog Uplink payload

The Datalog poll reply uplink will use below payload format.

Retrieval data payload

Size(bytes)

2

2

2

1

4

Value

Poll message flag & Ext

Poll message flag & Ext

image-20220523152208-14.png

Poll Message Flag: 1: This message is a poll message reply.

  • Poll Message Flag is set to 1.

  • Each data entry is 11 bytes, to save airtime and battery, devices will send max bytes according to the current DR and Frequency bands.

 

For example, in US915 band, the max payload for different DR is:

a) DR0: max is 11 bytes so one entry of data

b) DR1: max is 53 bytes so devices will upload 4 entries of data (total 44 bytes)

c) DR2: total payload includes 11 entries of data

d) DR3: total payload includes 22 entries of data.

If devise doesn’t have any data in the polling time. Device will uplink 11 bytes of 0    

Example:

If LHT65N has below data inside Flash:

image-20220523144455-1.png

If user sends below downlink command:  3160065F9760066DA705

   Where : Start time: 60065F97 = time 21/1/19 04:27:03

          Stop time 60066DA7= time 21/1/19 05:27:03

 

LHT65N will uplink this payload.

image-20220523001219-13.png

7FFF089801464160065F977FFF088E014B41600660097FFF0885014E41600660667FFF0875015141600662BE7FFF086B015541600665167FFF08660155416006676E7FFF085F015A41600669C67FFF0857015D4160066C1E

Where the first 11 bytes is for the first entry:

7FFF089801464160065F97

Ext sensor data=0x7FFF/100=327.67

Temp=0x0898/100=22.00

Hum=0x0146/10=32.6

poll message flag & Ext=0x41,means reply data,Ext=1

Unix time is 0x60065F97=1611030423s=21/1/19 04:27:03

2.7 Alarm Mode

when the device is in alarm mode, it checks the built-in sensor temperature for a short time. if the temperature exceeds the preconfigured range, it sends an uplink immediately.

note: alarm mode adds a little power consumption, and we recommend extending the normal read time when this feature is enabled.

AT COMMAND FOR ALARM MODE:

AT+WMOD=1:              Enable/disable alarm mode. (0: Disabled, 1: Enabled)

AT+CITEMP=1:             The interval between checking the alarm temperature. (In minutes)

AT+ARTEMP:                 Gets or sets the alarm range of the internal temperature sensor

AT+ARTEMP=? :          Gets the alarm range of the internal temperature sensor 

AT+ARTEMP=45,105:   Set the internal temperature sensor alarm range from 45 to 105.

2.8 LED Indicator

The LHT65 has a triple color LED which for easy showing different stage .

While user press ACT button, the LED will work as per LED status with ACT button.

In a normal working state:

  • For each uplink, the BLUE LED or RED LED will blink once. 

    BLUE LED when external sensor is connected

  • RED LED when external sensor is not connected

  • For each success downlink, the PURPLE LED will blink once

     

2.9 installation

image-20220516231650-1.png

3. Sensors and Accessories

3.1 E2 Extension Cable

image-20220619092222-1.pngimage-20220619092313-2.png

1m long breakout cable for LHT65N

image-20220619092421-3.png

3.1 E3 Temperature Probe

photo-20220515080154-4.png              image-20220515080330-5.png

Temperature sensor with 2 meters cable long

  • Resolution: 0.0625 °C
  • ±0.5°C accuracy from -10°C to +85°C
  • ±2°C accuracy from -55°C to +125°C
  • Operating Range: -40 ~ 125 °C
  • -55°C to 125°C
  • Working voltage 2.35v ~ 5v

4. Configure LHT65N via AT command or LoRaWAN downlink

Use can configure LHT65N via AT Command or LoRaWAN Downlink.

 

There are two kinds of commands to configure LHT65N, they are:

General Commands.

These commands are to configure:

  • General system settings like: uplink interval.

  • LoRaWAN protocol & radio-related commands.

They are the same for all Dragino Devices which supports DLWS-005 LoRaWAN Stack(Note**). These commands can be found on the wiki: End Device Downlink Command

 

Commands special design for LHT65N

These commands are only valid for LHT65N, as below:

 

4.1 Set Transmit Interval Time

Feature: Change LoRaWAN End Node Transmit Interval.

AT Command: AT+TDC

image-20220523150701-2.png

 

Downlink Command: 0x01

Format: Command Code (0x01) followed by 3 bytes time value.

If the downlink payload=0100003C, it means set the END Node’s Transmit Interval to 0x00003C=60(S), while type code is 01.

  • Example 1: Downlink Payload: 0100001E // Set Transmit Interval (TDC) = 30 seconds

  • Example 2: Downlink Payload: 0100003C // Set Transmit Interval (TDC) = 60 seconds

     

4.2 Set External Sensor Mode

Feature: Change External Sensor Mode.

AT Command: AT+EXT

image-20220523150759-3.png

 

Downlink Command: 0xA2

Total bytes: 2 ~ 5 bytes

Example:

  • 0xA201: Set external sensor type to E1

  • 0xA209: Same as AT+EXT=9

  • 0xA20702003c,Same as AT+SETCNT=60

     

4.3 Enable/Disable uplink Temperature probe ID

Feature: If PID is enabled, device will send the temperature probe ID on:

  • First Packet after OTAA Join
  • Every 24 hours since the first packet.

PID is default set to disable (0)

AT Command:

image-20220523150928-4.png

Downlink Command:

  • 0xA800     --> AT+PID=0
  • 0xA801     --> AT+PID=1

4.4 Set Password

Feature: Set device password, max 9 digits

AT Command: AT+PWORD

image-20220523151052-5.png

 

Downlink Command:

No downlink command for this feature.

 

4.5 Quit AT Command

Feature: Quit AT Command mode, so user needs to input password again before use AT Commands.

AT Command: AT+DISAT

image-20220523151132-6.png

Downlink Command:

No downlink command for this feature.

4.6 Set to sleep mode

Feature: Set device to sleep mode

  • AT+Sleep=0  : Normal working mode, device will sleep and use lower power when there is no LoRa message
  • AT+Sleep=1 : Device is in deep sleep mode, no LoRa activation happen, used for storage or shipping.

AT Command: AT+SLEEP

image-20220523151218-7.png

Downlink Command:

  • There is no downlink command to set to Sleep mode.

4.7 Set system time

Feature: Set system time, unix format. See here for format detail.

AT Command:

image-20220523151253-8.png

Downlink Command:

0x306007806000 // Set timestamp to 0x(6007806000),Same as AT+TIMESTAMP=1611104352

4.8 Set Time Sync Mode

Feature: Enable/Disable Sync system time via LoRaWAN MAC Command (DeviceTimeReq), LoRaWAN server must support v1.0.3 protocol to reply this command.

SYNCMOD is set to 1 by default. If user want to set a different time from LoRaWAN server, user need to set this to 0.

AT Command:

image-20220523151336-9.png

Downlink Command:

0x28 01 // Same As AT+SYNCMOD=1

0x28 00 // Same As AT+SYNCMOD=0

4.9 Set Time Sync Interval

Feature: Define System time sync interval. SYNCTDC default value: 10 days.

AT Command:

image-20220523151411-10.png

Downlink Command:

0x29 0A // Same as AT+SYNCTDC=0x0A

4.10 Print data entries base on page.

Feature: Print the sector data from start page to stop page (max is 416 pages).

AT Command: AT+PDTA

image-20220523151450-11.png

Downlink Command:

No downlink commands for feature

4.11 Print last few data entries.

Feature: Print the last few data entries

AT Command: AT+PLDTA

image-20220523151524-12.png

Downlink Command:

No downlink commands for feature

4.12 Clear Flash Record

Feature: Clear flash storage for data log feature.

AT Command: AT+CLRDTA

image-20220523151556-13.png

Downlink Command: 0xA3

  • Example: 0xA301   //Same as AT+CLRDTA

4.13 Auto Send None-ACK messages

Feature: LHT65N will wait for ACK for each uplink, If LHT65N doesn't get ACK from the IoT server, it will consider the message doesn't arrive server and store it. LHT65N keeps sending messages in normal periodically. Once LHT65N gets ACK from a server, it will consider the network is ok and start to send the not-arrive message.

AT Command: AT+PNACKMD

The default factory setting is 0

Command ExampleFunctionResponse
AT+PNACKMD=1Poll None-ACK messageOK

Downlink Command: 0x34

  • Example: 0x3401   //Same as AT+PNACKMD=1

5. Battery & How to replace

5.1 Battery Type

LHT65N is equipped with a 2400mAH Li-MnO2 (CR17505) battery . The battery is an un-rechargeable battery with low discharge rate targeting for up to 8~10 years use. This type of battery is commonly used in IoT devices for long-term running, such as water meters.

The discharge curve is not linear so can’t simply use percentage to show the battery level. Below is the battery performance.
image-20220515075034-1.png

The minimum Working Voltage for the LHT65N is ~ 2.5v. When battery is lower than 2.6v, it is time to change the battery.
 

5.2 Replace Battery

LHT65N has two screws on the back, Unscrew them, and changing the battery inside is ok. The battery is a general CR17450 battery. Any brand should be ok.

image-20220515075440-2.pngimage-20220515075625-3.png

5.3 Battery Life Analyze

Dragino battery-powered products are all run in Low Power mode. User can check the guideline from this link to calculate the estimated battery life:
https://www.dragino.com/downloads/downloads/LoRa_End_Node/Battery_Analyze/DRAGINO_Battery_Life_Guide.pdf

 

A full detail test report for LHT65N on different frequency can be found at : https://www.dropbox.com/sh/r2i3zlhsyrpavla/AAB1sZw3mdT0K7XjpHCITt13a?dl=0

6. FAQ

6.1 How to use AT Command?

LHT65N supports AT Command set.User can use a USB to TTL adapter plus the Program Cable to connect to LHT65 for using AT command, as below.

image-20220530085651-1.png

Connection:

✓ USB to TTL GND <-->GND

✓  USB to TTL RXD <--> D+

✓  USB to TTL TXD <--> A11

✓  USB to TTL 3.3V <--> D-

In PC, User needs to set serial tool(such as putty, SecureCRT) baud rate to 9600 to access to access serial console for LHT65N. The AT commands are disable by default and need to enter password (default:123456to active it. Timeout to input AT Command is 5 min, after 5-minute, user need to input password again. User can use AT+DISAT command to disable AT command before timeout.

Input password and ATZ to activate LHT65N,As shown below:

image-20220530095701-4.png

AT Command List is as below:

AT+<CMD>? :                  Help on <CMD>

AT+<CMD> :                   Run <CMD>

AT+<CMD>=<value> :   Set the value

AT+<CMD>=? :               Get the value

AT+DEBUG:    Set more info output

ATZ:                Trig a reset of the MCU

AT+FDR:         Reset Parameters to Factory Default, Keys Reserve

AT+DEUI:       Get or Set the Device EUI

AT+DADDR:   Get or Set the Device Address

AT+APPKEY:   Get or Set the Application Key

AT+NWKSKEY:   Get or Set the Network Session Key

AT+APPSKEY:     Get or Set the Application Session Key

AT+APPEUI:       Get or Set the Application EUI

AT+ADR:       Get or Set the Adaptive Data Rate setting. (0: off, 1: on)

AT+TXP:        Get or Set the Transmit Power (0-5, MAX:0, MIN:5, according to LoRaWAN Spec)

AT+DR:         Get or Set the Data Rate. (0-7 corresponding to DR_X)

AT+DCS:       Get or Set the ETSI Duty Cycle setting - 0=disable, 1=enable - Only for testing

AT+PNM:      Get or Set the public network mode. (0: off, 1: on)

AT+RX2FQ:    Get or Set the Rx2 window frequency

AT+RX2DR:    Get or Set the Rx2 window data rate (0-7 corresponding to DR_X)

AT+RX1DL:    Get or Set the delay between the end of the Tx and the Rx Window 1 in ms

AT+RX2DL:    Get or Set the delay between the end of the Tx and the Rx Window 2 in ms

AT+JN1DL:     Get or Set the Join Accept Delay between the end of the Tx and the Join Rx Window 1 in ms

AT+JN2DL:     Get or Set the Join Accept Delay between the end of the Tx and the Join Rx Window 2 in ms

AT+NJM:        Get or Set the Network Join Mode. (0: ABP, 1: OTAA)

AT+NWKID:    Get or Set the Network ID

AT+FCU:        Get or Set the Frame Counter Uplink

AT+FCD:        Get or Set the Frame Counter Downlink

AT+CLASS:    Get or Set the Device Class

AT+JOIN:       Join network

AT+NJS:        Get the join status

AT+SENDB:   Send hexadecimal data along with the application port

AT+SEND:     Send text data along with the application port

AT+RECVB:    Print last received data in binary format (with hexadecimal values)

AT+RECV:      Print last received data in raw format

AT+VER:        Get current image version and Frequency Band

AT+CFM:       Get or Set the confirmation mode (0-1)

AT+CFS:        Get confirmation status of the last AT+SEND (0-1)

AT+SNR:       Get the SNR of the last received packet

AT+RSSI:       Get the RSSI of the last received packet

AT+TDC:       Get or set the application data transmission interval in ms

AT+PORT:     Get or set the application port

AT+DISAT:    Disable AT commands

AT+PWORD:    Set password, max 9 digits

AT+CHS:       Get or Set Frequency (Unit: Hz) for Single Channel Mode

AT+CHE:       Get or Set eight channels mode,Only for US915,AU915,CN470

AT+PDTA:      Print the sector data from start page to stop page

AT+PLDTA:    Print the last few sets of data

AT+CLRDTA:  Clear the storage, record position back to 1st

AT+SLEEP:     Set sleep mode

AT+EXT:        Get or Set external sensor model

AT+BAT:        Get the current battery voltage in mV

AT+CFG:        Print all configurations

AT+WMOD:   Get or Set Work Mode

AT+ARTEMP:  Get or set the internal Temperature sensor alarm range

AT+CITEMP:   Get or set the internal Temperature sensor collection interval in min

AT+SETCNT:   Set the count at present

AT+RJTDC:     Get or set the ReJoin data transmission interval in min

AT+RPL:         Get or set response level

AT+TIMESTAMP:   Get or Set UNIX timestamp in second

AT+LEAPSEC:        Get or Set Leap Second

AT+SYNCMOD:    Get or Set time synchronization method

AT+SYNCTDC:      Get or set time synchronization interval in day

AT+PID:                Get or set the PID

6.2 Where to use AT commands and Downlink commands

AT commands:

image-20220620153708-1.png

Downlink commands:

TTN:

image-20220615092124-2.png

Helium:

image-20220615092551-3.png

Chirpstack:The downlink window will not be displayed until the network is accessed

image-20220615094850-6.png

image-20220615094904-7.png

Aws:

image-20220615092939-4.png

6.3 How to change the uplink interval?

http://wiki.dragino.com/xwiki/bin/view/Main/How%20to%20set%20the%20transmit%20time%20interval/ 

6.4 How to use TTL-USB to connect a PC to input AT commands?

image-20220615153355-1.png

image-20220620154900-5.jpeg

1    < - ->    GND  < - ->    Black

5    < - ->    RXD   < - ->    White

9    < - ->    TXD   < - ->    Green

To switch from download mode to command mode, press reset key

In PC, User needs to set serial tool(such as putty, SecureCRT) baud rate to 9600 to access to access serial console for LHT65N. The AT commands are disable by default and need to enter password (default:123456) to active it. Timeout to input AT Command is 5 min, after 5-minute, user need to input password again. User can use AT+DISAT command to disable AT command before timeout.

Input password and ATZ to activate LHT65N,As shown below:

image-20220615154519-3.png

 

6.5 How to use TTL-USB to connect PC to upgrade firmware?

image-20220615153355-1.png

1    < - ->    GND  < - ->    Black

4    < - ->    3.3V   < - ->    Blue

5    < - ->    RXD   < - ->    White

9    < - ->    TXD   < - ->    Green

image-20220620160241-6.jpeg

Press reset after connecting the 4boot cable to enter the download mode.

image-20220620160516-7.png

Step1: Install TremoProgrammer  first.

image-20220615170542-5.png

Step2:Download the LHT65N image files.

Step3:Select the serial port and baud rate of the device and the firmware to be upgraded.

image-20220615171334-6.png

Step4:Click Start 

image-20220620160723-8.png

7. Order Info

Part Number:  LHT65N-XX-YY

XX : The default frequency band

  •  AS923: LoRaWAN AS923 band

  •  AU915: LoRaWAN AU915 band

  •  EU433: LoRaWAN EU433 band

  •  EU868: LoRaWAN EU868 band

  •  KR920: LoRaWAN KR920 band

  •  US915: LoRaWAN US915 band

  •  IN865: LoRaWAN IN865 band

  •  CN470: LoRaWAN CN470 band

YY: Sensor Accessories

  • E3: External Temperature Probe

     

8. Packing Info

 

Package Includes:

  • LHT65N Temperature & Humidity Sensor x 1

  • Optional external sensor

Dimension and weight:

  • Device Size:  10 x 10 x 3.5 cm

  • Device Weight: 120.5g

 

9. Reference material

10. FCC Warning

This device complies with part 15 of the FCC Rules.Operation is subject to the following two conditions:

(1) This device may not cause harmful interference;

(2) this device must accept any interference received, including interference that may cause undesired operation.

Tags:
    