... ... @@ -267,17 +267,23 @@ 267 267 **3. Send the calibration command to Sensor 2**: 268 268 269 269 * Command Format: **0B 06 00 53 [(% style="color:#037691" %)K-value(%%) (2 bytes)] [CRC]** 270 -* Example for K-value 0x02EE: 0B 06 00 53 02 EE F8 5D 271 271 272 - (% style="color:red"%)**Notes:**271 +Example for K-value 0x02EE: 0B 06 00 53 02 EE F8 5D 273 273 274 -~1. Always use the sensor with the most trusted reading as the reference (do not modify its K-value). 275 275 276 - 2.ThedefaultK-value03E8(1000)implies noscaling.Valuesbelow03E8reducetheoutput;valuesabove increaseit.274 +if the value of sensor 1 is 1500 and the value of sensor 2 is 2000, it is necessary to keep the values around 1500if the value of sensor 1 is 1500 and the value of sensor 2 is 2000, it is necessary to keep the values around 1500. 277 277 278 - 3. CRC is auto-generatedby thetool(no manualcalculationneeded).276 +Modify the K value of sensor 2: 279 279 278 +* K value calculation as follows: 279 +* 1500/2000=0.75, 0.75*1000=750 280 +* Convert 750 to hexadecimal to 02EE. 281 +* Send command to sensor 2 282 +* Send:0B 06 00 53 02 EE F8 5D Send successfully and return this command 280 280 284 + 285 + 286 + 281 281 = 5. WSS-25 ~-~- Temperature, Humidity, Illuminance, Pressure = 282 282 283 283