... ... @@ -267,23 +267,17 @@
267 267  **3. Send the calibration command to Sensor 2**:
268 268  
269 269  * Command Format: **0B 06 00 53 [(% style="color:#037691" %)K-value(%%) (2 bytes)] [CRC]**
270 +* Example for K-value 0x02EE: 0B 06 00 53 02 EE F8 5D
270 270  
271 -Example for K-value 0x02EE: 0B 06 00 53 02 EE F8 5D
272 +(% style="color:red" %)**Notes:**
272 272  
274 +~1. Always use the sensor with the most trusted reading as the reference (do not modify its K-value).
273 273  
274 -if the value of sensor 1 is 1500 and the value of sensor 2 is 2000, it is necessary to keep the values around 1500if the value of sensor 1 is 1500 and the value of sensor 2 is 2000, it is necessary to keep the values around 1500.
276 +2. The default K-value 03E8 (1000) implies no scaling. Values below 03E8 reduce the output; values above increase it.
275 275  
276 -Modify the K value of sensor 2:
278 +3. CRC is auto-generated by the tool (no manual calculation needed).
277 277  
278 -* K value calculation as follows:
279 -* 1500/2000=0.75,  0.75*1000=750
280 -* Convert 750 to hexadecimal to 02EE.
281 -* Send command to sensor 2
282 -* Send:0B 06 00 53 02 EE F8 5D  Send successfully and return this command
283 283  