Last modified by Xiaoling on 2025/04/23 15:57

From version 41.9
edited by Xiaoling
on 2022/06/06 10:57
Change comment: There is no comment for this version
To version 42.2
edited by Xiaoling
on 2022/06/06 12:01
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -283,28 +283,28 @@
283 283  )))
284 284  
285 285  (% border="1" cellspacing="10" style="background-color:#ffffcc; color:green; width:510px" %)
286 -|=(% style="width: 120px;" %)(((
286 +|=(% style="width: 80px;" %)(((
287 287  (((
288 288  **AT Commands**
289 289  )))
290 -)))|=(% style="width: 190px;" %)(((
290 +)))|=(% style="width: 210px;" %)(((
291 291  (((
292 292  **Description**
293 293  )))
294 -)))|=(% style="width: 190px;" %)(((
294 +)))|=(% style="width: 2100px;" %)(((
295 295  (((
296 296  **Example**
297 297  )))
298 298  )))
299 -|(% style="width:120px" %)(((
299 +|(% style="width:80px" %)(((
300 300  (((
301 301  AT+BAUDR
302 302  )))
303 -)))|(% style="width:190px" %)(((
303 +)))|(% style="width:210px" %)(((
304 304  (((
305 305  Set the baud rate (for RS485 connection). Default Value is: 9600.
306 306  )))
307 -)))|(% style="width:190px" %)(((
307 +)))|(% style="width:210px" %)(((
308 308  (((
309 309  (((
310 310  AT+BAUDR=9600
... ... @@ -317,11 +317,11 @@
317 317  )))
318 318  )))
319 319  )))
320 -|(% style="width:120px" %)(((
320 +|(% style="width:80px" %)(((
321 321  (((
322 322  AT+PARITY
323 323  )))
324 -)))|(% style="width:190px" %)(((
324 +)))|(% style="width:210px" %)(((
325 325  (((
326 326  (((
327 327  Set UART parity (for RS485 connection)
... ... @@ -333,7 +333,7 @@
333 333  Default Value is: no parity.
334 334  )))
335 335  )))
336 -)))|(% style="width:190px" %)(((
336 +)))|(% style="width:210px" %)(((
337 337  (((
338 338  (((
339 339  AT+PARITY=0
... ... @@ -346,11 +346,11 @@
346 346  )))
347 347  )))
348 348  )))
349 -|(% style="width:120px" %)(((
349 +|(% style="width:80px" %)(((
350 350  (((
351 351  AT+STOPBIT
352 352  )))
353 -)))|(% style="width:190px" %)(((
353 +)))|(% style="width:210px" %)(((
354 354  (((
355 355  (((
356 356  Set serial stopbit (for RS485 connection)
... ... @@ -362,7 +362,7 @@
362 362  Default Value is: 1bit.
363 363  )))
364 364  )))
365 -)))|(% style="width:190px" %)(((
365 +)))|(% style="width:210px" %)(((
366 366  (((
367 367  (((
368 368  AT+STOPBIT=0 for 1bit
... ... @@ -383,7 +383,6 @@
383 383  )))
384 384  
385 385  
386 -
387 387  === 3.3.2 Configure sensors ===
388 388  
389 389  (((
... ... @@ -395,14 +395,14 @@
395 395  )))
396 396  
397 397  (% border="1" cellspacing="10" style="background-color:#ffffcc; color:green; width:510px" %)
398 -|=(% style="width: 120px;" %)**AT Commands**|=(% style="width: 190px;" %)**Description**|=(% style="width: 190px;" %)**Example**
399 -|AT+CFGDEV|(% style="width:120px" %)(((
397 +|=(% style="width: 80px;" %)**AT Commands**|=(% style="width: 210px;" %)**Description**|=(% style="width: 210px;" %)**Example**
398 +|AT+CFGDEV|(% style="width:80px" %)(((
400 400  This command is used to configure the RS485/TTL devices; they won’t be used during sampling.
401 401  
402 402  AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,
403 403  
404 404  mm: 0: no CRC, 1: add CRC-16/MODBUS in the end of this command
405 -)))|(% style="width:190px" %)AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
404 +)))|(% style="width:210px" %)AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m
406 406  
407 407  Detail of AT+CFGDEV command see [[AT+CFGDEV detail>>||anchor="HRS485DebugCommand28AT2BCFGDEV29"]].
408 408  
... ... @@ -510,6 +510,10 @@
510 510  )))
511 511  
512 512  (((
512 +
513 +)))
514 +
515 +(((
513 513  **AT+SEARCHx**: This command defines how to handle the return from AT+COMMANDx.
514 514  )))
515 515  
... ... @@ -868,7 +868,7 @@
868 868  )))
869 869  
870 870  (((
871 -**}**
874 +}
872 872  
873 873  
874 874  )))
... ... @@ -882,16 +882,23 @@
882 882  
883 883  == 3.5 Configure RS485-BL via AT or Downlink ==
884 884  
888 +(((
885 885  User can configure RS485-BL via AT Commands or LoRaWAN Downlink Commands
890 +)))
886 886  
892 +(((
887 887  There are two kinds of Commands:
894 +)))
888 888  
889 -* (% style="color:#4f81bd" %)**Common Commands**(%%): They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
896 +* (((
897 +(% style="color:#4f81bd" %)**Common Commands**(%%): They should be available for each sensor, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
898 +)))
890 890  
891 -* (% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for RS485-BL.  User can see these commands below:
900 +* (((
901 +(% style="color:#4f81bd" %)**Sensor Related Commands**(%%): These commands are special designed for RS485-BL.  User can see these commands below:
902 +)))
892 892  
893 893  
894 -
895 895  === 3.5.1 Common Commands: ===
896 896  
897 897  They should be available for each of Dragino Sensors, such as: change uplink interval, reset device. For firmware v1.3, user can find what common commands it supports: [[End Device AT Commands and Downlink Command>>doc:Main.End Device AT Commands and Downlink Command.WebHome]]
... ... @@ -927,51 +927,101 @@
927 927  
928 928  ==== **RS485 Debug Command (AT+CFGDEV)** ====
929 929  
940 +(((
930 930  This command is used to configure the RS485 or TTL sensors; they won’t be used during sampling.
942 +)))
931 931  
932 -* **AT Command**
944 +* (((
945 +**AT Command**
946 +)))
933 933  
934 934  (% class="box infomessage" %)
935 935  (((
950 +(((
936 936  **AT+CFGDEV=xx xx xx xx xx xx xx xx xx xx xx xx,m**
937 937  )))
953 +)))
938 938  
955 +(((
939 939  m: 0: no CRC; 1: add CRC-16/MODBUS in the end of this command.
957 +)))
940 940  
959 +(((
960 +
961 +)))
941 941  
942 -* **Downlink Payload**
963 +* (((
964 +**Downlink Payload**
965 +)))
943 943  
967 +(((
944 944  Format: A8 MM NN XX XX XX XX YY
969 +)))
945 945  
971 +(((
946 946  Where:
973 +)))
947 947  
948 -* MM: 1: add CRC-16/MODBUS ; 0: no CRC
949 -* NN: The length of RS485 command
950 -* XX XX XX XX: RS485 command total NN bytes
951 -* YY: How many bytes will be uplink from the return of this RS485 command, if YY=0, RS485-BL will execute the downlink command without uplink; if YY>0, RS485-BL will uplink total YY bytes from the output of this RS485 command
975 +* (((
976 +MM: 1: add CRC-16/MODBUS ; 0: no CRC
977 +)))
978 +* (((
979 +NN: The length of RS485 command
980 +)))
981 +* (((
982 +XX XX XX XX: RS485 command total NN bytes
983 +)))
984 +* (((
985 +YY: How many bytes will be uplink from the return of this RS485 command, if YY=0, RS485-BL will execute the downlink command without uplink; if YY>0, RS485-BL will uplink total YY bytes from the output of this RS485 command
986 +)))
952 952  
988 +(((
953 953  **Example 1:**
990 +)))
954 954  
992 +(((
955 955  To connect a Modbus Alarm with below commands.
994 +)))
956 956  
957 -* The command to active alarm is: 0A 05 00 04 00 01 **4C B0**. Where 0A 05 00 04 00 01 is the Modbus command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which calculate manually.
996 +* (((
997 +The command to active alarm is: 0A 05 00 04 00 01 **4C B0**. Where 0A 05 00 04 00 01 is the Modbus command to read the register 00 40 where stored the DI status. The 4C B0 is the CRC-16/MODBUS which calculate manually.
998 +)))
958 958  
959 -* The command to deactivate alarm is: 0A 05 00 04 00 00 **8D 70**. Where 0A 05 00 04 00 00 is the Modbus command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which calculate manually.
1000 +* (((
1001 +The command to deactivate alarm is: 0A 05 00 04 00 00 **8D 70**. Where 0A 05 00 04 00 00 is the Modbus command to read the register 00 40 where stored the DI status. The 8D 70 is the CRC-16/MODBUS which calculate manually.
1002 +)))
960 960  
1004 +(((
961 961  So if user want to use downlink command to control to RS485 Alarm, he can use:
1006 +)))
962 962  
1008 +(((
963 963  (% style="color:#037691" %)**A8 01 06 0A 05 00 04 00 01 00**(%%): to activate the RS485 Alarm
1010 +)))
964 964  
1012 +(((
965 965  (% style="color:#037691" %)**A8 01 06 0A 05 00 04 00 00 00**(%%): to deactivate the RS485 Alarm
1014 +)))
966 966  
1016 +(((
967 967  A8 is type code and 01 means add CRC-16/MODBUS at the end, the 3^^rd^^ byte is 06, means the next 6 bytes are the command to be sent to the RS485 network, the final byte 00 means this command don’t need to acquire output.
1018 +)))
968 968  
1020 +(((
1021 +
1022 +)))
969 969  
1024 +(((
970 970  **Example 2:**
1026 +)))
971 971  
1028 +(((
972 972  Check TTL Sensor return:
1030 +)))
973 973  
1032 +(((
974 974  [[image:1654132684752-193.png]]
1034 +)))
975 975  
976 976  
977 977  
... ... @@ -1000,62 +1000,121 @@
1000 1000  
1001 1001  ==== **Set RS485 Sampling Commands** ====
1002 1002  
1063 +(((
1003 1003  AT+COMMANDx, AT+DATACUTx and AT+SEARCHx
1065 +)))
1004 1004  
1067 +(((
1005 1005  These three commands are used to configure how the RS485-BL polling data from Modbus device. Detail of usage please see : [[polling RS485 device>>||anchor="H3.3.3Configurereadcommandsforeachsampling"]].
1069 +)))
1006 1006  
1071 +(((
1072 +
1073 +)))
1007 1007  
1008 -* **AT Command:**
1075 +* (((
1076 +**AT Command:**
1077 +)))
1009 1009  
1010 1010  (% class="box infomessage" %)
1011 1011  (((
1081 +(((
1012 1012  **AT+COMMANDx: Configure RS485 read command to sensor.**
1013 1013  )))
1084 +)))
1014 1014  
1015 1015  (% class="box infomessage" %)
1016 1016  (((
1088 +(((
1017 1017  **AT+DATACUTx: Configure how to handle return from RS485 devices.**
1018 1018  )))
1091 +)))
1019 1019  
1020 1020  (% class="box infomessage" %)
1021 1021  (((
1095 +(((
1022 1022  **AT+SEARCHx: Configure search command**
1023 1023  )))
1098 +)))
1024 1024  
1100 +(((
1101 +
1102 +)))
1025 1025  
1026 -* **Downlink Payload:**
1104 +* (((
1105 +**Downlink Payload:**
1106 +)))
1027 1027  
1108 +(((
1028 1028  **0xAF** downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
1110 +)))
1029 1029  
1112 +(((
1030 1030  (% style="color:red" %)**Note**(%%): if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
1114 +)))
1031 1031  
1116 +(((
1032 1032  Format: AF MM NN LL XX XX XX XX YY
1118 +)))
1033 1033  
1120 +(((
1034 1034  Where:
1122 +)))
1035 1035  
1036 -* MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
1037 -* NN:  0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
1038 -* LL:  The length of AT+COMMAND or AT+DATACUT command
1039 -* XX XX XX XX: AT+COMMAND or AT+DATACUT command
1040 -* YY:  If YY=0, RS485-BL will execute the downlink command without uplink; if YY=1, RS485-BL will execute an uplink after got this command.
1124 +* (((
1125 +MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
1126 +)))
1127 +* (((
1128 +NN:  0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
1129 +)))
1130 +* (((
1131 +LL:  The length of AT+COMMAND or AT+DATACUT command
1132 +)))
1133 +* (((
1134 +XX XX XX XX: AT+COMMAND or AT+DATACUT command
1135 +)))
1136 +* (((
1137 +YY:  If YY=0, RS485-BL will execute the downlink command without uplink; if YY=1, RS485-BL will execute an uplink after got this command.
1138 +)))
1041 1041  
1140 +(((
1042 1042  **Example:**
1142 +)))
1043 1043  
1144 +(((
1044 1044  (% style="color:#037691" %)**AF 03 01 06 0A 05 00 04 00 01 00**(%%): Same as AT+COMMAND3=0A 05 00 04 00 01,1
1146 +)))
1045 1045  
1148 +(((
1046 1046  (% style="color:#037691" %)**AF 03 02 06**(% style="color:orange" %)** 10 **(% style="color:red" %)**01 **(% style="color:green" %)**05 06 09 0A**(% style="color:#037691" %)** 00**(%%): Same as AT+DATACUT3=(% style="color:orange" %)**16**(%%),(% style="color:red" %)**1**(%%),(% style="color:green" %)**5+6+9+10**
1150 +)))
1047 1047  
1152 +(((
1048 1048  (% style="color:#037691" %)**AF 03 02 06 **(% style="color:orange" %)**0B**(% style="color:red" %)** 02 **(% style="color:green" %)**05 07 08 0A **(% style="color:#037691" %)**00**(%%): Same as AT+DATACUT3=(% style="color:orange" %)**11**(%%),(% style="color:red" %)**2**(%%),(% style="color:green" %)**5~~7+8~~10**
1154 +)))
1049 1049  
1156 +(((
1157 +
1158 +)))
1050 1050  
1160 +(((
1051 1051  **0xAB** downlink command can be used for set AT+SEARCHx
1162 +)))
1052 1052  
1164 +(((
1053 1053  **Example:** **AB aa 01 03 xx xx xx** (03 here means there are total 3 bytes after 03) So
1166 +)))
1054 1054  
1055 -* AB aa 01 03 xx xx xx  same as AT+SEARCHaa=1,xx xx xx
1056 -* AB aa 02 03 xx xx xx 02 yy yy(03 means there are 3 bytes after 03, they are xx xx xx;02 means there are 2 bytes after 02, they are yy yy) so the commands
1168 +* (((
1169 +AB aa 01 03 xx xx xx  same as AT+SEARCHaa=1,xx xx xx
1170 +)))
1171 +* (((
1172 +AB aa 02 03 xx xx xx 02 yy yy(03 means there are 3 bytes after 03, they are xx xx xx;02 means there are 2 bytes after 02, they are yy yy) so the commands
1173 +)))
1057 1057  
1175 +(((
1058 1058  **AB aa 02 03 xx xx xx 02 yy yy**  same as **AT+SEARCHaa=2,xx xx xx+yy yy**
1177 +)))
1059 1059  
1060 1060  
1061 1061  
... ... @@ -1062,24 +1062,47 @@
1062 1062  
1063 1063  ==== **Fast command to handle MODBUS device** ====
1064 1064  
1184 +(((
1065 1065  AT+MBFUN is valid since v1.3 firmware version. The command is for fast configure to read Modbus devices. It is only valid for the devices which follow the [[MODBUS-RTU protocol>>url:https://www.modbustools.com/modbus.html]].
1186 +)))
1066 1066  
1188 +(((
1067 1067  This command is valid since v1.3 firmware version
1190 +)))
1068 1068  
1192 +(((
1193 +
1194 +)))
1069 1069  
1196 +(((
1070 1070  **AT+MBFUN has only two value:**
1198 +)))
1071 1071  
1072 -* **AT+MBFUN=1**: Enable Modbus reading. And get response base on the MODBUS return
1200 +* (((
1201 +**AT+MBFUN=1**: Enable Modbus reading. And get response base on the MODBUS return
1202 +)))
1073 1073  
1204 +(((
1074 1074  AT+MBFUN=1, device can auto read the Modbus function code: 01, 02, 03 or 04. AT+MBFUN has lower priority vs AT+DATACUT command. If AT+DATACUT command is configured, AT+MBFUN will be ignore.
1206 +)))
1075 1075  
1076 -* **AT+MBFUN=0**: Disable Modbus fast reading.
1208 +* (((
1209 +**AT+MBFUN=0**: Disable Modbus fast reading.
1210 +)))
1077 1077  
1212 +(((
1078 1078  **Example:**
1214 +)))
1079 1079  
1080 -* AT+MBFUN=1 and AT+DATACUT1/AT+DATACUT2 are not configure (0,0,0).
1081 -* AT+COMMAND1= 01 03 00 10 00 08,1 ~-~-> read slave address 01 , function code 03, start address 00 01, quantity of registers 00 08.
1082 -* AT+COMMAND2= 01 02 00 40 00 10,1 ~-~-> read slave address 01 , function code 02, start address 00 40, quantity of inputs 00 10.
1216 +* (((
1217 +AT+MBFUN=1 and AT+DATACUT1/AT+DATACUT2 are not configure (0,0,0).
1218 +)))
1219 +* (((
1220 +AT+COMMAND1= 01 03 00 10 00 08,1 ~-~-> read slave address 01 , function code 03, start address 00 01, quantity of registers 00 08.
1221 +)))
1222 +* (((
1223 +AT+COMMAND2= 01 02 00 40 00 10,1 ~-~-> read slave address 01 , function code 02, start address 00 40, quantity of inputs 00 10.
1224 +)))
1083 1083  
1084 1084  [[image:1654133913295-597.png]]
1085 1085  
... ... @@ -1087,67 +1087,120 @@
1087 1087  [[image:1654133954153-643.png]]
1088 1088  
1089 1089  
1090 -* **Downlink Commands:**
1232 +* (((
1233 +**Downlink Commands:**
1234 +)))
1091 1091  
1236 +(((
1092 1092  **A9 aa** ~-~-> Same as AT+MBFUN=aa
1238 +)))
1093 1093  
1094 1094  
1095 1095  
1242 +
1096 1096  ==== **RS485 command timeout** ====
1097 1097  
1245 +(((
1098 1098  Some Modbus device has slow action to send replies. This command is used to configure the RS485-BL to use longer time to wait for their action.
1247 +)))
1099 1099  
1249 +(((
1100 1100  Default value: 0, range:  0 ~~ 5 seconds
1251 +)))
1101 1101  
1253 +(((
1254 +
1255 +)))
1102 1102  
1103 -* **AT Command:**
1257 +* (((
1258 +**AT Command:**
1259 +)))
1104 1104  
1105 1105  (% class="box infomessage" %)
1106 1106  (((
1263 +(((
1107 1107  **AT+CMDDLaa=hex(bb cc)**
1108 1108  )))
1266 +)))
1109 1109  
1268 +(((
1110 1110  **Example:**
1270 +)))
1111 1111  
1272 +(((
1112 1112  **AT+CMDDL1=1000** to send the open time to 1000ms
1274 +)))
1113 1113  
1276 +(((
1277 +
1278 +)))
1114 1114  
1115 -* **Downlink Payload:**
1280 +* (((
1281 +**Downlink Payload:**
1282 +)))
1116 1116  
1284 +(((
1117 1117  0x AA aa bb cc
1286 +)))
1118 1118  
1288 +(((
1119 1119  Same as: AT+CMDDLaa=hex(bb cc)
1290 +)))
1120 1120  
1292 +(((
1121 1121   **Example:**
1294 +)))
1122 1122  
1296 +(((
1123 1123   **0xAA 01 03 E8**  ~-~-> Same as **AT+CMDDL1=1000 ms**
1298 +)))
1124 1124  
1125 1125  
1126 1126  
1302 +
1127 1127  ==== **Uplink payload mode** ====
1128 1128  
1305 +(((
1129 1129  Define to use one uplink or multiple uplinks for the sampling.
1307 +)))
1130 1130  
1309 +(((
1131 1131  The use of this command please see: [[Compose Uplink payload>>||anchor="H3.3.4Composetheuplinkpayload"]]
1311 +)))
1132 1132  
1133 -* **AT Command:**
1313 +* (((
1314 +**AT Command:**
1315 +)))
1134 1134  
1135 1135  (% class="box infomessage" %)
1136 1136  (((
1319 +(((
1137 1137  **AT+DATAUP=0**
1138 1138  )))
1322 +)))
1139 1139  
1140 1140  (% class="box infomessage" %)
1141 1141  (((
1326 +(((
1142 1142  **AT+DATAUP=1**
1143 1143  )))
1329 +)))
1144 1144  
1331 +(((
1332 +
1333 +)))
1145 1145  
1146 -* **Downlink Payload:**
1335 +* (((
1336 +**Downlink Payload:**
1337 +)))
1147 1147  
1339 +(((
1148 1148  **0xAD 00**  **~-~->** Same as AT+DATAUP=0
1341 +)))
1149 1149  
1343 +(((
1150 1150  **0xAD 01**  **~-~->** Same as AT+DATAUP=1
1345 +)))
1151 1151  
1152 1152  
1153 1153  
... ... @@ -1165,131 +1165,248 @@
1165 1165  
1166 1166  ==== **Clear RS485 Command** ====
1167 1167  
1363 +(((
1168 1168  The AT+COMMANDx and AT+DATACUTx settings are stored in special location, user can use below command to clear them.
1365 +)))
1169 1169  
1367 +(((
1368 +
1369 +)))
1170 1170  
1171 -* **AT Command:**
1371 +* (((
1372 +**AT Command:**
1373 +)))
1172 1172  
1375 +(((
1173 1173  (% style="color:#037691" %)**AT+CMDEAR=mm,nn** (%%) mm: start position of erase ,nn: stop position of erase Etc. AT+CMDEAR=1,10 means erase AT+COMMAND1/AT+DATACUT1 to AT+COMMAND10/AT+DATACUT10
1377 +)))
1174 1174  
1379 +(((
1175 1175  Example screen shot after clear all RS485 commands. 
1381 +)))
1176 1176  
1383 +(((
1384 +
1385 +)))
1177 1177  
1387 +(((
1178 1178  The uplink screen shot is:
1389 +)))
1179 1179  
1391 +(((
1180 1180  [[image:1654134704555-320.png]]
1393 +)))
1181 1181  
1395 +(((
1396 +
1397 +)))
1182 1182  
1183 -* **Downlink Payload:**
1399 +* (((
1400 +**Downlink Payload:**
1401 +)))
1184 1184  
1403 +(((
1185 1185  **0x09 aa bb** same as AT+CMDEAR=aa,bb
1405 +)))
1186 1186  
1187 1187  
1188 1188  
1409 +
1189 1189  ==== **Set Serial Communication Parameters** ====
1190 1190  
1412 +(((
1191 1191  Set the Rs485 serial communication parameters:
1414 +)))
1192 1192  
1193 -* **AT Command:**
1416 +* (((
1417 +**AT Command:**
1418 +)))
1194 1194  
1420 +(((
1195 1195  Set Baud Rate:
1422 +)))
1196 1196  
1197 1197  (% class="box infomessage" %)
1198 1198  (((
1426 +(((
1199 1199  **AT+BAUDR=9600**    ~/~/ Options: (1200,2400,4800,14400,19200,115200)
1200 1200  )))
1429 +)))
1201 1201  
1431 +(((
1202 1202  Set UART Parity
1433 +)))
1203 1203  
1204 1204  (% class="box infomessage" %)
1205 1205  (((
1437 +(((
1206 1206  **AT+PARITY=0**    ~/~/ Option: 0: no parity, 1: odd parity, 2: even parity
1207 1207  )))
1440 +)))
1208 1208  
1442 +(((
1209 1209  Set STOPBIT
1444 +)))
1210 1210  
1211 1211  (% class="box infomessage" %)
1212 1212  (((
1448 +(((
1213 1213  **AT+STOPBIT=0**    ~/~/ Option: 0 for 1bit; 1 for 1.5 bit ; 2 for 2 bits
1214 1214  )))
1451 +)))
1215 1215  
1453 +(((
1454 +
1455 +)))
1216 1216  
1217 -* **Downlink Payload:**
1457 +* (((
1458 +**Downlink Payload:**
1459 +)))
1218 1218  
1461 +(((
1219 1219  **A7 01 aa bb**: Same  AT+BAUDR=hex(aa bb)*100
1463 +)))
1220 1220  
1465 +(((
1221 1221  **Example:**
1467 +)))
1222 1222  
1223 -* A7 01 00 60   same as AT+BAUDR=9600
1224 -* A7 01 04 80  same as AT+BAUDR=115200
1469 +* (((
1470 +A7 01 00 60   same as AT+BAUDR=9600
1471 +)))
1472 +* (((
1473 +A7 01 04 80  same as AT+BAUDR=115200
1474 +)))
1225 1225  
1476 +(((
1226 1226  A7 02 aa: Same as  AT+PARITY=aa  (aa value: 00 , 01 or 02)
1478 +)))
1227 1227  
1480 +(((
1228 1228  A7 03 aa: Same as  AT+STOPBIT=aa  (aa value: 00 , 01 or 02)
1482 +)))
1229 1229  
1230 1230  
1231 1231  
1486 +
1232 1232  ==== **Control output power duration** ====
1233 1233  
1489 +(((
1234 1234  User can set the output power duration before each sampling.
1491 +)))
1235 1235  
1236 -* **AT Command:**
1493 +* (((
1494 +**AT Command:**
1495 +)))
1237 1237  
1497 +(((
1238 1238  **Example:**
1499 +)))
1239 1239  
1501 +(((
1240 1240  **AT+3V3T=1000**  ~/~/ 3V3 output power will open 1s before each sampling.
1503 +)))
1241 1241  
1505 +(((
1242 1242  **AT+5VT=1000**  ~/~/ +5V output power will open 1s before each sampling.
1507 +)))
1243 1243  
1509 +(((
1510 +
1511 +)))
1244 1244  
1245 -* **LoRaWAN Downlink Command:**
1513 +* (((
1514 +**LoRaWAN Downlink Command:**
1515 +)))
1246 1246  
1517 +(((
1247 1247  **07 01 aa bb**  Same as AT+5VT=(aa bb)
1519 +)))
1248 1248  
1521 +(((
1249 1249  **07 02 aa bb**  Same as AT+3V3T=(aa bb)
1523 +)))
1250 1250  
1251 1251  
1252 1252  
1253 1253  == 3.6 Buttons ==
1254 1254  
1255 -(% border="1" style="background-color:#ffffcc; color:green; width:233px" %)
1529 +(% border="1" cellspacing="10" style="background-color:#ffffcc; color:green; width:233px" %)
1256 1256  |=(% style="width: 89px;" %)**Button**|=(% style="width: 141px;" %)**Feature**
1257 1257  |(% style="width:89px" %)**RST**|(% style="width:141px" %)Reboot RS485-BL
1258 1258  
1533 +
1259 1259  == 3.7 +3V3 Output ==
1260 1260  
1536 +(((
1261 1261  RS485-BL has a Controllable +3V3 output, user can use this output to power external sensor.
1538 +)))
1262 1262  
1540 +(((
1263 1263  The +3V3 output will be valid for every sampling. RS485-BL will enable +3V3 output before all sampling and disable the +3V3 after all sampling. 
1542 +)))
1264 1264  
1544 +(((
1265 1265  The +3V3 output time can be controlled by AT Command.
1546 +)))
1266 1266  
1548 +(((
1549 +
1550 +)))
1267 1267  
1552 +(((
1268 1268  (% style="color:#037691" %)**AT+3V3T=1000**
1554 +)))
1269 1269  
1556 +(((
1557 +
1558 +)))
1270 1270  
1560 +(((
1271 1271  Means set +3v3 valid time to have 1000ms. So, the real +3v3 output will actually have 1000ms + sampling time for other sensors.
1562 +)))
1272 1272  
1564 +(((
1273 1273  By default, the AT+3V3T=0. This is a special case, means the +3V3 output is always on at any time
1566 +)))
1274 1274  
1275 1275  
1276 1276  == 3.8 +5V Output ==
1277 1277  
1571 +(((
1278 1278  RS485-BL has a Controllable +5V output, user can use this output to power external sensor.
1573 +)))
1279 1279  
1575 +(((
1280 1280  The +5V output will be valid for every sampling. RS485-BL will enable +5V output before all sampling and disable the +5v after all sampling. 
1577 +)))
1281 1281  
1579 +(((
1282 1282  The 5V output time can be controlled by AT Command.
1581 +)))
1283 1283  
1583 +(((
1584 +
1585 +)))
1284 1284  
1587 +(((
1285 1285  (% style="color:#037691" %)**AT+5VT=1000**
1589 +)))
1286 1286  
1591 +(((
1592 +
1593 +)))
1287 1287  
1595 +(((
1288 1288  Means set 5V valid time to have 1000ms. So, the real 5V output will actually have 1000ms + sampling time for other sensors.
1597 +)))
1289 1289  
1599 +(((
1290 1290  By default, the AT+5VT=0. If the external sensor which require 5v and require more time to get stable state, user can use this command to increase the power ON duration for this sensor.
1601 +)))
1291 1291  
1292 1292  
1604 +
1293 1293  == 3.9 LEDs ==
1294 1294  
1295 1295  (% border="1" style="background-color:#ffffcc; color:green; width:332px" %)
... ... @@ -1296,6 +1296,7 @@
1296 1296  |=**LEDs**|=(% style="width: 274px;" %)**Feature**
1297 1297  |**LED1**|(% style="width:274px" %)Blink when device transmit a packet.
1298 1298  
1611 +
1299 1299  == 3.10 Switch Jumper ==
1300 1300  
1301 1301  (% border="1" style="background-color:#ffffcc; color:green; width:515px" %)
... ... @@ -1311,9 +1311,13 @@
1311 1311  3.3v position: set to compatible with 3.3v I/O.,
1312 1312  )))
1313 1313  
1627 +(((
1314 1314  **+3.3V**: is always ON
1629 +)))
1315 1315  
1631 +(((
1316 1316  **+5V**: Only open before every sampling. The time is by default, it is AT+5VT=0.  Max open time. 5000 ms.
1633 +)))
1317 1317  
1318 1318  
1319 1319  = 4. Case Study =
... ... @@ -1325,17 +1325,23 @@
1325 1325  
1326 1326  == 5.1 Access AT Command ==
1327 1327  
1645 +(((
1328 1328  RS485-BL supports AT Command set. User can use a USB to TTL adapter plus the 3.5mm Program Cable to connect to RS485-BL to use AT command, as below.
1647 +)))
1329 1329  
1330 1330  [[image:1654135840598-282.png]]
1331 1331  
1332 1332  
1652 +(((
1333 1333  In PC, User needs to set (% style="color:blue" %)**serial tool**(%%)(such as [[putty>>url:https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to (% style="color:green" %)**9600**(%%) to access to access serial console of RS485-BL. The default password is 123456. Below is the output for reference:
1654 +)))
1334 1334  
1335 1335  [[image:1654136105500-922.png]]
1336 1336  
1337 1337  
1659 +(((
1338 1338  More detail AT Command manual can be found at [[AT Command Manual>>||anchor="H3.5ConfigureRS485-BLviaATorDownlink"]]
1661 +)))
1339 1339  
1340 1340  
1341 1341  == 5.2 Common AT Command Sequence ==
... ... @@ -1360,7 +1360,9 @@
1360 1360  )))
1361 1361  
1362 1362  
1686 +(((
1363 1363  If device already joined network:
1688 +)))
1364 1364  
1365 1365  (% class="box infomessage" %)
1366 1366  (((
... ... @@ -1399,10 +1399,12 @@
1399 1399  
1400 1400  (% style="color:red" %)**Note:**
1401 1401  
1727 +(((
1402 1402  (% style="color:red" %)1. Make sure the device is set to ABP mode in the IoT Server.
1403 1403  2. Make sure the LG01/02 gateway RX frequency is exactly the same as AT+CHS setting.
1404 1404  3. Make sure SF / bandwidth setting in LG01/LG02 match the settings of AT+DR. refer [[this link>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_Gateway/&file=LoRaWAN%201.0.3%20Regional%20Parameters.xlsx]] to see what DR means.
1405 1405  4. The command AT+RX2FQ and AT+RX2DR is to let downlink work. to set the correct parameters, user can check the actually downlink parameters to be used. As below. Which shows the RX2FQ should use 868400000 and RX2DR should be 5
1732 +)))
1406 1406  
1407 1407  [[image:1654136435598-589.png]]
1408 1408  
... ... @@ -1411,13 +1411,23 @@
1411 1411  
1412 1412  == 6.1 How to upgrade the image? ==
1413 1413  
1741 +(((
1414 1414  The RS485-BL LoRaWAN Controller is shipped with a 3.5mm cable, the cable is used to upload image to RS485-BL to:
1743 +)))
1415 1415  
1416 -* Support new features
1417 -* For bug fix
1418 -* Change LoRaWAN bands.
1745 +* (((
1746 +Support new features
1747 +)))
1748 +* (((
1749 +For bug fix
1750 +)))
1751 +* (((
1752 +Change LoRaWAN bands.
1753 +)))
1419 1419  
1755 +(((
1420 1420  Below shows the hardware connection for how to upload an image to RS485-BL:
1757 +)))
1421 1421  
1422 1422  [[image:1654136646995-976.png]]
1423 1423  
... ... @@ -1483,6 +1483,7 @@
1483 1483  * (% style="color:blue" %)**RU864**(%%): frequency bands RU864
1484 1484  * (% style="color:blue" %)**KZ865**(%%): frequency bands KZ865
1485 1485  
1823 +
1486 1486  = 9. Packing Info =
1487 1487  
1488 1488  (((