948 948  (% style="color:#4f81bd" %)**Cause for this issue:**
949 949  
950 -(((
951 951  The fuse on LSE01 is not large enough, some of the soil probe require large current up to 5v 800mA, in a short pulse. When this happen, it cause the device reboot so user see rejoin.
952 -)))
953 953  
954 954  
955 955  (% style="color:#4f81bd" %)**Solution: **
... ... @@ -956,7 +956,7 @@
956 956  
957 957  All new shipped LSE01 after 2020-May-30 will have this to fix. For the customer who see this issue, please bypass the fuse as below:
958 958  
959 -[[image:1654500929571-736.png||height="458" width="832"]]
957 +[[image:1654500929571-736.png]]
960 960  
961 961  