Version 54.2 by Xiaoling on 2025/04/24 09:46

Show last authors
1 (% style="text-align:center" %)
2 [[image:LHT65N-PIR1.jpg||alt="image-20221206143242-2.png" height="484" width="485"]]
3
4
5
6
7 **Table of Contents:**
8
9 {{toc/}}
10
11
12
13
14
15
16 = 1. Introduction =
17
18 == 1.1 What is LHT65N-PIR Temperature,Humidity & PIR Sensor ==
19
20
21 The Dragino (% style="color:blue" %)**LHT65N-PIR Temperature, Humidity & PIR sensor**(%%) is a Long Range LoRaWAN Sensor.It includes a (% style="color:blue" %)**built-in Temperature & Humidity sensor**(%%) and has an (% style="color:blue" %)**external PIR Probe**(%%)**.** LHT65N-PIR can detect environment Temperature & Humdity, it also detects (% style="color:blue" %)**People Activity**(%%) via PIR probe and them send these info to LoRaWAN IoT Server.
22
23 The LHT65N-PIR allows users to send data and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, building automation, and so on.
24
25 LHT65N-PIR has a (% style="color:blue" %)**built-in 2400mAh non-chargeable battery**(%%) which can be used for more than 5 years*.
26
27 LHT65N-PIR supports (% style="color:blue" %)**wireless configure & OTA update**(%%) which make user easy to use.
28
29 LHT65N-PIR is fully compatible with (% style="color:blue" %)**LoRaWAN v1.0.3 Class A protocol**(%%), it can work with a standard LoRaWAN gateway.
30
31 **~*~***The actual battery life depends on how often to send data, please see battery analyzer chapter.
32
33
34 == 1.2 Features ==
35
36
37 * LoRaWAN v1.0.3 Class A protocol
38 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915
39 * AT Commands to change parameters
40 * Remote configure parameters via LoRaWAN Downlink
41 * Support wireless OTA update firmware
42 * Firmware upgradeable via program port
43 * Built-in 2400mAh battery for up to 5 years of use.
44 * Built-in Temperature & Humidity sensor
45 * External PIR Sensor
46 * Tri-color LED to indicate working status
47
48 (% style="display:none" %)
49
50 == 1.3 Specification ==
51
52
53 (% style="color:#037691" %)**Built-in Temperature Sensor:**
54
55 * Resolution: 0.01 °C
56 * Accuracy Tolerance : Typ ±0.3 °C
57 * Long Term Drift: < 0.02 °C/yr
58 * Operating Range: -40 ~~ 85 °C
59
60 (% style="color:#037691" %)**Built-in Humidity Sensor:**
61
62 * Resolution: 0.04 %RH
63 * Accuracy Tolerance : Typ ±3 %RH
64 * Long Term Drift: < 0.25 RH/yr
65 * Operating Range: 0 ~~ 96 %RH
66
67 (% style="color:#037691" %)**External PIR Sensor:**
68
69 * Base on RDB223 Sensor
70 * Cable Length : 1 meter
71 * Stable detect distance : 0~~3 meter
72
73 = 2. Connect LHT65N-PIR to IoT Server =
74
75 == 2.1 How does LHT65N-PIR work? ==
76
77
78 LHT65N-PIR is configured as LoRaWAN OTAA Class A sensor by default. Each LHT65N-PIR is shipped with a worldwide unique set of OTAA keys. To use LHT65N-PIR in a LoRaWAN network, first, we need to put the OTAA keys in LoRaWAN Network Server and then activate LHT65N-PIR.
79
80 If LHT65N-PIR is within the coverage of this LoRaWAN network. LHT65N-PIR can join the LoRaWAN network automatically. After successfully joining, LHT65N-PIR will start to measure environment temperature, humidity & people activity, and start to transmit sensor data to the LoRaWAN server. The default period for each uplink is 20 minutes.
81
82
83 == 2.2 How to Activate LHT65N-PIR? ==
84
85
86 The LHT65N-PIR has two working modes:
87
88 * (% style="color:blue" %)**Deep Sleep Mode**(%%): LHT65N-PIR doesn't have any LoRaWAN activation. This mode is used for storage and shipping to save battery life.
89
90 * (% style="color:blue" %)**Working Mode**(%%):  In this mode, LHT65N-PIR works as LoRaWAN Sensor mode to Join LoRaWAN network and send out the sensor data to the server. Between each sampling/tx/rx periodically, LHT65N-PIR will be in STOP mode (IDLE mode), in STOP mode, the PIR sensor is still working to detect people activity in low power consumption.
91
92 The LHT65N-PIR is set in deep sleep mode by default; The ACT button on the front is to switch to different modes:
93
94
95 [[image:http://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N-E5%20LoRaWAN%20Temperature_Humidity%20%26%20Illuminance%20Sensor%20User%20Manual/WebHome/image-20220515123819-1.png?width=317&height=379&rev=1.1||alt="image-20220515123819-1.png" height="379" width="317"]]
96
97
98 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:510px" %)
99 |=(% style="width: 167px;background-color:#4F81BD;color:white" %)**Behavior on ACT**|=(% style="width: 117px;background-color:#4F81BD;color:white" %)**Function**|=(% style="width: 226px;background-color:#4F81BD;color:white" %)**Action**
100 |(% style="background-color:#f2f2f2; width:167px" %)Pressing ACT between 1s < time < 3s|(% style="background-color:#f2f2f2; width:117px" %)Test uplink status|(% style="background-color:#f2f2f2; width:225px" %)(((
101
102
103 If LHT65N-PIR is already Joined to rhe LoRaWAN network, LHT65N-PIR will send an uplink packet, if LHT65N-PIR has external sensor connected,Blue led will blink once. If LHT65N-PIR has not external sensor, Red led will blink once.
104 )))
105 |(% style="background-color:#f2f2f2; width:167px" %)Pressing ACT for more than 3s|(% style="background-color:#f2f2f2; width:117px" %)Active Device|(% style="background-color:#f2f2f2; width:225px" %)(((
106
107
108 Green led will fast blink 5 times, LHT65N-PIR will enter working mode and start to JOIN LoRaWAN network.
109 Green led will solidly turn on for 5 seconds after join in network.
110 )))
111 |(% style="background-color:#f2f2f2; width:167px" %)Fast press ACT 5 times.|(% style="background-color:#f2f2f2; width:117px" %)Deactivate Device|(% style="background-color:#f2f2f2; width:225px" %)Red led will solid on for 5 seconds. Means LHT65N-PIR is in Deep Sleep Mode.
112
113 == 2.3 Example to join LoRaWAN network ==
114
115
116 (% class="wikigeneratedid" %)
117 This section shows an example of how to join the TTN V3 LoRaWAN IoT server. Use with other LoRaWAN IoT servers is of a similar procedure.
118
119
120 (% class="wikigeneratedid" %)
121 [[image:image-20230409080812-1.png||height="487" width="785"]]
122
123
124 Assume the LPS8v2 is already set to connect to [[TTN V3 network>>url:https://eu1.cloud.thethings.network||_mstvisible="2"]], So it provides network coverage for LHT65N-PIR. Next we need to add the LHT65N-PIR device in TTN V3:
125
126
127 === 2.3.1 Step 1: Create Device n TTN ===
128
129
130 Create a device in TTN V3 with the OTAA keys from LHT65N-PIR.
131
132 Each LHT65N-PIR is shipped with a sticker with its device EUI, APP Key and APP EUI as below:
133
134 [[image:image-20230426083533-1.png||height="286" width="616"]]
135
136
137 User can enter these keys in the LoRaWAN Server portal. Below is TTN V3 screenshot:
138
139 **~1. Create application**
140
141 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/WebHome/image-20250424091200-1.jpeg?rev=1.1||alt="image-20250424091200-1.jpeg"]]
142
143 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/WebHome/image-20250424091207-2.jpeg?rev=1.1||alt="image-20250424091207-2.jpeg"]]
144
145
146 **2. Add devices to the created Application.**
147
148 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/WebHome/image-20250424091404-3.jpeg?rev=1.1||alt="image-20250424091404-3.jpeg"]]
149
150 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/WebHome/image-20250424091412-4.jpeg?rev=1.1||alt="image-20250424091412-4.jpeg"]]
151
152
153 **3. Enter end device specifics manually.**
154
155 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/WebHome/image-20250424091458-5.jpeg?rev=1.1||alt="image-20250424091458-5.jpeg"]]
156
157 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/WebHome/image-20250424091509-6.jpeg?rev=1.1||alt="image-20250424091509-6.jpeg"]]
158
159
160 === 2.3.2 Step 2: Add decoder ===
161
162
163 In TTN, user can add a custom payload so it shows friendly reading.
164
165 Click this link to get the decoder: [[https:~~/~~/github.com/dragino/dragino-end-node-decoder/tree/main/>>url:https://github.com/dragino/dragino-end-node-decoder/tree/main/]]
166
167 Below is TTN screen shot
168
169 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LWL04--LoRaWAN_Water_Leak_Sensor_User_Manual/WebHome/image-20240909162501-5.png?width=1084&height=516&rev=1.1||alt="image-20240909162501-5.png"]]
170
171 [[image:https://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LWL04--LoRaWAN_Water_Leak_Sensor_User_Manual/WebHome/image-20240909162647-6.png?width=1086&height=494&rev=1.1||alt="image-20240909162647-6.png"]]
172
173
174 === 2.3.3 Step 3: Activate LHT65N-PIR by pressing the ACT button for more than 5 seconds. ===
175
176
177 Use ACT button to activate LHT65N-PIR and it will auto-join to the TTN V3 network. After join success, it will start to upload sensor data to TTN V3 and user can see in the panel.
178
179
180 [[image:http://wiki.dragino.com/xwiki/bin/download/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N-E5%20LoRaWAN%20Temperature_Humidity%20%26%20Illuminance%20Sensor%20User%20Manual/WebHome/image-20220522233300-8.png?rev=1.1||alt="image-20220522233300-8.png" height="378" width="1248"]]
181
182
183 == 2.4 Uplink Payload~-~-Device Status, (Fport~=5)(% style="display:none" %) (%%) ==
184
185
186 Users can use the downlink command(**0x26 01**) to ask LHT65N-PIR to send device configure detail, include device configure status. LHT65N-PIR will uplink a payload via FPort=5 to server.
187
188 The Payload format is as below.
189
190 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:510px" %)
191 |(% colspan="6" style="background-color:#4f81bd; color:white" %)**Device Status (FPORT=5)**
192 |(% style="background-color:#f2f2f2; width:103px" %)**Size (bytes)**|(% style="background-color:#f2f2f2; width:72px" %)**1**|(% style="background-color:#f2f2f2" %)**2**|(% style="background-color:#f2f2f2; width:91px" %)**1**|(% style="background-color:#f2f2f2; width:86px" %)**1**|(% style="background-color:#f2f2f2; width:44px" %)**2**
193 |(% style="background-color:#f2f2f2; width:103px" %)Value|(% style="background-color:#f2f2f2; width:72px" %)Sensor Model|(% style="background-color:#f2f2f2" %)Firmware Version|(% style="background-color:#f2f2f2; width:91px" %)Frequency Band|(% style="background-color:#f2f2f2; width:86px" %)Sub-band|(% style="background-color:#f2f2f2; width:44px" %)BAT
194
195 Example parse in TTNv3
196
197 [[image:image-20230508151932-1.png||height="213" width="1245"]]
198
199
200 (% style="color:blue" %)**Sensor Model**(%%): For LHT65N-PIR, this value is 0x1A
201
202 (% style="color:blue" %)**Firmware Version**(%%): 0x0100, Means: v1.0.0 version
203
204 (% style="color:blue" %)**Frequency Band**:
205
206 0x01: EU868
207
208 0x02: US915
209
210 0x03: IN865
211
212 0x04: AU915
213
214 0x05: KZ865
215
216 0x06: RU864
217
218 0x07: AS923
219
220 0x08: AS923-1
221
222 0x09: AS923-2
223
224 0x0a: AS923-3
225
226 0x0b: CN470
227
228 0x0c: EU433
229
230 0x0d: KR920
231
232 0x0e: MA869
233
234
235 (% style="color:blue" %)**Sub-Band**:
236
237 AU915 and US915: value 0x00 ~~ 0x08
238
239 CN470: value 0x0B ~~ 0x0C
240
241 Other Bands: Always 0x00
242
243
244 (% style="color:blue" %)**Battery Info**:
245
246 Check the battery voltage.
247
248 Ex1: 0x0B45 = 2885mV
249
250 Ex2: 0x0B49 = 2889mV
251
252
253 == 2.5 Uplink Payload, Sensor Data  ( Fport~=2) ==
254
255
256 The uplink payload includes totally 11 bytes. Uplink packets use FPORT=2 and (% style="color:#4f81bd" %)**every 20 minutes**(%%) send one uplink by default.
257
258 After each uplink, the (% style="color:blue" %)**BLUE LED**(%%) will blink once.
259
260 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:390px" %)
261 |=(% style="width: 60px;background-color:#4F81BD;color:white" %)(((
262 **Size(bytes)**
263 )))|=(% style="width: 30px;background-color:#4F81BD;color:white" %)(((
264 **2**
265 )))|=(% style="width: 100px;background-color:#4F81BD;color:white" %)(((
266 **2**
267 )))|=(% style="width: 100px;background-color:#4F81BD;color:white" %)(((
268 **2**
269 )))|=(% style="width: 50px;background-color:#4F81BD;color:white" %)(((
270 **1**
271 )))|=(% style="width: 50px;background-color:#4F81BD;color:white" %)(((
272 **4**
273 )))
274 |(% style="width:97px" %)(((
275 Value
276 )))|(% style="width:39px" %)(((
277 [[BAT>>||anchor="H2.5.2BAT-BatteryInfo"]]
278 )))|(% style="width:100px" %)(((
279 (((
280 [[Built-In Temperature>>||anchor="H2.5.3Built-inTemperature"]]
281 )))
282 )))|(% style="width:77px" %)(((
283 (((
284 [[Built-in Humidity>>||anchor="H2.5.4Built-inHumidity"]]
285 )))
286 )))|(% style="width:47px" %)(((
287 Ext #
288 )))|(% style="width:51px" %)(((
289 [[Ext value>>||anchor="H2.5.5Extvalue"]]
290 )))
291
292 * The First 6 bytes: has fix meanings for every LHT65N-PIR.
293 * The 7th byte (EXT #): defines the external sensor model. It can be 0x0A for LHT65N-PIR
294 * The 8^^th^^ byte: Alarm Bit (if this uplink is from periodically or movement)
295 * The 9^^th^^ ~~ 11^^st^^  byte: Movement Detect Count.
296
297 === 2.5.1 Decoder in TTN V3 ===
298
299
300 When the uplink payload arrives TTNv3, it shows HEX format and not friendly to read. We can add LHT65N-PIR decoder in TTNv3 for friendly reading.
301
302 Below is the position to put the decoder and LHT65N-PIR decoder can be download from here: [[https:~~/~~/github.com/dragino/dragino-end-node-decoder>>https://github.com/dragino/dragino-end-node-decoder]]
303
304
305 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220522234118-10.png||_mstalt="451464" height="353" width="729"]]
306
307
308 === 2.5.2 BAT-Battery Info ===
309
310
311 These two bytes of BAT include the battery state and the actually voltage
312
313 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:477px" %)
314 |=(% style="width: 69px; background-color:#4F81BD;color:white" %)(((
315 **Bit(bit)**
316 )))|=(% style="width: 253px;background-color:#4F81BD;color:white" %)[15:14]|=(% style="width: 155px;background-color:#4F81BD;color:white" %)[13:0]
317 |(% style="width:66px" %)(((
318 Value
319 )))|(% style="width:250px" %)(((
320 BAT Status
321 00(b): Ultra Low ( BAT <= 2.50v)
322 01(b): Low (2.50v <=BAT <= 2.55v)
323 10(b): OK (2.55v <= BAT <=2.65v)
324 11(b): Good (BAT >= 2.65v)
325 )))|(% style="width:152px" %)Actually BAT voltage
326
327 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220522235639-1.png||_mstalt="431392" height="139" width="727"]]
328
329
330 Check the battery voltage for LHT65N-PIR.
331
332 * BAT status=(0xcba4>>14)&0xFF=11(B),very good
333 * Battery Voltage =0xCBF6&0x3FFF=0x0BA4=2980mV
334
335 === 2.5.3 Built-in Temperature ===
336
337
338 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220522235639-2.png||_mstalt="431756" height="138" width="722"]]
339
340 * Temperature:  0x0ABB/100=27.47℃
341
342 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220522235639-3.png||_mstalt="432120"]]
343
344 * Temperature:  (0xF5C6-65536)/100=-26.18℃
345
346 === 2.5.4 Built-in Humidity ===
347
348
349 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220522235639-4.png||_mstalt="432484" height="138" width="722"]]
350
351 * Humidity:    0x025C/10=60.4%
352
353 === 2.5.5 Ext value ===
354
355 ==== 2.5.5.1 Ext~=0x0E, PIR Sensor ====
356
357
358 [[image:ext=14.png||alt="image-20221224161634-2.png" height="166" width="1252"]]
359
360
361 ==== 2.5.5.2 Ext Value ====
362
363
364 There are 4 bytes in Ext Value field.
365
366 Bit0 of byte 8th shows if this uplink is generate by PIR activity.
367
368 (% border="1" cellspacing="4" style="background-color:#f2f2f2; width:393px" %)
369 |=(% style="width: 107px; background-color:#4F81BD;color:white" %)(((
370 **The 8^^th^^ byte**
371 )))|=(% style="width: 73px; background-color:#4F81BD;color:white" %)(((
372 **Bit 1~~7**
373 )))|=(% style="width: 213px; background-color:#4F81BD;color:white" %)(((
374 **Bit 0**
375 )))
376 |(% style="width:106px" %)(((
377 Value
378 )))|(% style="width:71px" %)(((
379 Reserve
380 )))|(% style="width:211px" %)(((
381 (((
382 0: Normal Uplink
383 1: Uplink by activity detected
384 )))
385 )))
386
387 (% style="color:red" %)**Note**:** Uplink by activity is disable by default.**
388
389 The 9^^th^^ ~~ 11^^st^^  byte: Movement Detect Count.
390
391 0x00 E5 09 : Total detect 58633 activity since end node start.
392
393
394 == 2.6 Show data on Datacake ==
395
396
397 Datacake IoT platform provides a human-friendly interface to show the sensor data, once we have sensor data in TTN V3, we can use Datacake to connect to TTN V3 and see the data in Datacake. Below are the steps:
398
399 (% style="color:blue" %)**Step 1**(%%): Be sure that your device is programmed and properly connected to the LoRaWAN network.
400
401 (% style="color:blue" %)**Step 2**(%%): Configure your Application to forward data to Datacake you will need to add integration. Go to TTN V3 Console ~-~-> Applications ~-~-> Integrations ~-~-> Add Integrations.
402
403 Add Datacake:
404
405 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220523000825-7.png||_mstalt="429884" height="262" width="583"]]
406
407
408
409 Select default key as Access Key:
410
411
412 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220523000825-8.png||_mstalt="430248" height="453" width="406"]]
413
414
415 In Datacake console ([[https:~~/~~/datacake.co/>>url:https://datacake.co/]]) , add LHT65 device.
416
417
418 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20221224161935-5.png||height="523" width="409"]]
419
420
421 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20221224161957-6.png||height="306" width="852"]]
422
423 == 2.7 Alarm Mode & Feature "Multi sampling, one uplink" ==
424
425
426 (((
427 when the device is in alarm mode, it checks the built-in sensor temperature for a short time. if the temperature exceeds the preconfigured range, it sends an uplink immediately.
428 )))
429
430 (((
431 (% style="color:red" %)**Note: alarm mode adds a little power consumption, and we recommend extending the normal read time when this feature is enabled.**
432
433
434 === 2.7.1 ALARM MODE ( Since v1.3.1 firmware) ===
435
436
437 **Internal GXHT30 temperature alarm(Acquisition time: fixed at one minute)**
438
439 (((
440 (% class="box infomessage" %)
441 (((
442 **AT+WMOD=3**:  Enable/disable alarm mode. (0: Disabled, 1: Enabled Temperature Alarm for onboard temperature sensor)
443
444 **AT+CITEMP=1**:  The interval between checking the alarm temperature. (In minutes)
445
446 **AT+ARTEMP**:  Gets or sets the alarm range of the internal temperature sensor
447
448 (% _mstmutation="1" %)**AT+ARTEMP=? **(%%):  Gets the alarm range of the internal temperature sensor(% style="display:none" %)
449
450 **AT+ARTEMP=45,105**:  Set the internal temperature sensor alarm range from 45 to 105.
451
452 **AT+LEDALARM=1** :       Enable LED visual Alarm.
453 )))
454 )))
455
456 (% style="color:#4f81bd" %)**Downlink Command:**
457
458 AT+WMOD=1:  A501  , AT+WMOD=0 :  A600
459
460 AT+CITEMP=1 : A60001
461
462 AT+ARTEMP=1,60  :  A70001003C
463
464 AT+ARTEMP=-16,60 :  A7FFF0003C
465
466 AT+LEDALARM=1  :  3601
467
468
469 (% style="color:#4f81bd" %)**Downlink Command: AAXXXXXXXXXXXXXX**
470
471 Total bytes: 8 bytes
472
473 **Example: **AA0100010001003C
474
475 WMOD=01
476
477 CITEMP=0001
478
479 TEMPlow=0001
480
481 TEMPhigh=003C
482
483
484 **DS18B20 and TMP117 Threshold Alarm**
485
486 **~ AT+WMOD=1,60,-10,20**
487
488 (% style="color:#4f81bd" %)**Downlink Command:**
489
490 **Example: **A5013CFC180014
491
492 MOD=01
493
494 CITEMP=3C(S)
495
496 TEMPlow=FC18
497
498 TEMPhigh=0014
499
500
501 **Fluctuation alarm for DS18B20 and TMP117(Acquisition time: minimum 1s)**
502
503 **AT+WMOD=2,60,5** 
504
505 (% style="color:#4f81bd" %)**Downlink Command:**
506
507 **Example: **A5023C05
508
509 MOD=02
510
511 CITEMP=3C(S)
512
513 temperature fluctuation=05
514
515
516 **Sampling multiple times and uplink together**
517
518 **AT+WMOD=3,1,60,20,-16,32,1**   
519
520 Explain:
521
522 * (% style="color:#037691" %)**parameter1: **(%%)Set Working Mode to **Mode 3**
523 * (% style="color:#037691" %)**parameter2:**(%%) Set the temperature sampling mode to** 1**(1:DS18B20;2:TMP117;3:** **Internal GXHT30).
524 * (% style="color:#037691" %)**parameter3: **(%%)Sampling Interval is **60**s.
525 * (% style="color:#037691" %)**parameter4: **(%%)When there is **20** sampling dats, Device will send these data via one uplink. (max value is 60, means max 60 sampling in one uplink)
526 * (% style="color:#037691" %)**parameter5 & parameter6: **(%%)Temperature alarm range is **-16** to **32**°C,
527 * (% style="color:#037691" %)**parameter7:**(%%) 1 to enable temperature alarm, **0** to disable the temperature alarm. If alarm is enabled, a data will be sent immediately  if temperate exceeds the Alarm range.
528
529 (% style="color:#4f81bd" %)**Downlink Command:**
530
531 **Example: **A50301003C14FFF0002001
532
533 MOD=03
534
535 TEMP=DS18B20
536
537 CITEMP=003C(S)
538
539 Total number of acquisitions=14
540
541 TEMPlow=FFF0
542
543 TEMPhigh=0020
544
545 ARTEMP=01
546
547
548 **Uplink payload( Fport=3)**
549
550 **Example: CBEA**01**0992**//0A41//**09C4**
551
552 BatV=CBEA
553
554 TEMP=DS18B20
555
556 Temp1=0992  ~/~/ 24.50℃
557
558 Temp2=0A41  ~/~/ 26.25℃
559
560 Temp3=09C4  ~/~/ 25.00℃
561
562 (% style="color:red" %)**Note: This uplink will automatically select the appropriate DR according to the data length**
563
564 (% style="color:red" %)** In this mode, the temperature resolution of ds18b20 is 0.25℃ to save power consumption**
565 )))
566
567
568 === 2.7.2 ALARM MODE ( Before v1.3.1 firmware) ===
569
570
571 (% class="box infomessage" %)
572 (((
573 (((
574 **AT+WMOD=1**:  Enable/disable alarm mode. (0: Disabled, 1: Enabled Temperature Alarm for onboard temperature sensor)
575 )))
576
577 (((
578 **AT+CITEMP=1**:  The interval between checking the alarm temperature. (In minutes)
579 )))
580
581 (((
582 **AT+ARTEMP**:  Gets or sets the alarm range of the internal temperature sensor
583 )))
584
585 (((
586 (% _mstmutation="1" %)**AT+ARTEMP=? **(%%):  Gets the alarm range of the internal temperature sensor(% style="display:none" %)
587 )))
588
589 (((
590 **AT+ARTEMP=45,105**:  Set the internal temperature sensor alarm range from 45 to 105.
591 )))
592 )))
593
594 (% style="color:#4f81bd" %)**Downlink Command: AAXXXXXXXXXXXXXX**
595
596 Total bytes: 8 bytes
597
598 **Example:**AA0100010001003C
599
600 WMOD=01
601
602 CITEMP=0001
603
604 TEMPlow=0001
605
606 TEMPhigh=003C
607
608
609 == 2.8 LED Indicator ==
610
611
612 The LHT65N-PIR has a triple color LED which for easy showing different stage .
613
614 While user press ACT button, the LED will work as per LED status with ACT button.
615
616 In a normal working state:
617
618 * For each uplink, the (% style="color:red" %)**RED LED**(%%) will blink once.
619 * For each success downlink, the (% style="color:purple" %)**PURPLE LED**(%%) will blink once.
620
621 == 2.9 installation ==
622
623
624 ~1. Don't install LHT65N-PIR outdoor or place where will get wet.
625
626 2. Towards the PIR probe to the place where need to monitor activity. Below is the detect beam.
627
628 Stable distance is 0~~3m. Some motion might not detected between 3~~5 m.
629
630 [[image:image-20230411135341-1.png||height="450" width="456"]]
631
632
633 (% style="color:red" %)**Notice: PIR can only detect motion activity, not to use to detect static people case.**
634
635 * 1. PIR Motion Detector should not be installed near the Air conditioner places where with cold wind or hot wind flow, because PIR motion detector is sensitive with the temperature changes of the environment. Environment changes quickly will cause a false alarm.
636
637 * 2. PIR should not be installed facing the glass window, facing glass window will be interfered by the outside sunlight and moving objects (people or vehicle). The infrared energy can penetrate the glass window.
638
639 * 3. PIR should not be installed facing the moving objects or background changing objects, movement object will cause airflow change, it may cause false alarm.
640
641 * 4. Between the detection range of PIR Motion detector, there is should be less objects.  Many objects may reduce the sensitive of detection range.
642
643 * 5. Do not install more than one (2 or above) Wireless PIR in the same detection space (like at the same room).
644
645 = 3. Sensors and Accessories =
646
647 == 3.1 E2 Extension Cable ==
648
649
650 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220619092222-1.png||_mstalt="429533" height="182" width="188"]][[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220619092313-2.png||_mstalt="430222" height="182" width="173"]]
651
652
653 **1m long breakout cable for LHT65N-PIR. Features:**
654
655 * (((
656 Use for AT Command
657 )))
658 * (((
659 Update firmware for LHT65N-PIR
660 )))
661
662 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220619092421-3.png||_mstalt="430547" height="371" width="529"]]
663
664
665 = 4. Configure LHT65N-PIR =
666
667 == 4.1 Configure Methods: ==
668
669
670 LHT65N-PIR supports below configure method:
671
672 * AT Command via UART Connection : See [[FAQ>>||anchor="H7.FAQ"]].
673
674 * LoRaWAN Downlink.  Instruction for different platforms: See [[IoT LoRaWAN Server>>url:http://wiki.dragino.com/xwiki/bin/view/Main/]] section.
675
676 == 4.2 General Commands ==
677
678
679 These commands are to configure:
680
681 * General system settings like: uplink interval.
682 * LoRaWAN protocol & radio related command.
683
684 They are same for all Dragino Devices which support DLWS-005 LoRaWAN Stack. These commands can be found on the wiki:
685
686 [[http:~~/~~/wiki.dragino.com/xwiki/bin/view/Main/End%20Device%20AT%20Commands%20and%20Downlink%20Command/>>url:http://wiki.dragino.com/xwiki/bin/view/Main/End%20Device%20AT%20Commands%20and%20Downlink%20Command/]]
687
688
689 == (% data-sider-select-id="b105c0ce-c4b4-457e-b159-018a39209e92" %)4.3 Commands special design for LHT65N-PIR(%%) ==
690
691
692 These commands only valid for LHT65N-PIR, as below:
693
694
695 === 4.3.1 Set Transmit Interval Time ===
696
697
698 Feature: Change LoRaWAN End Node Transmit Interval.
699
700 (% style="color:#4f81bd" %)**AT Command: **
701
702 (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:501px" %)
703 |(% style="background-color:#4f81bd; color:white; width:155px" %)**Command Example**|(% style="background-color:#4f81bd; color:white; width:166px" %)**Function**|(% style="background-color:#4f81bd; color:white; width:180px" %)**Response**
704 |(% style="width:155px" %)AT+TDC=?|(% style="width:162px" %)Show current transmit Interval|(% style="width:177px" %)30000 OK the interval is 30000ms = 30s
705 |(% style="width:155px" %)AT+TDC=60000|(% style="width:162px" %)Set Transmit Interval|(% style="width:177px" %)OK Set transmit interval to 60000ms = 60 seconds
706
707 (% style="color:#4f81bd" %)**Downlink Payload: 0x01**
708
709 Format: Command Code (0x01) followed by 3 bytes time value.
710
711 If the downlink payload=0100003C, it means set the END Node's Transmit Interval to 0x00003C=60(S), while type code is 01.
712
713 * **Example 1**: Downlink Payload: 0100001E  ~/~/ Set Transmit Interval (TDC) = 30 seconds
714
715 * **Example 2**: Downlink Payload: 0100003C  ~/~/ Set Transmit Interval (TDC) = 60 seconds
716
717 === 4.3.2 Get Device Status ===
718
719
720 Send a LoRaWAN downlink to ask device send Alarm settings.
721
722 * (% style="color:#4f81bd" %)**Downlink Payload**(%%)**:  **0x26 01
723
724 Sensor will upload Device Status via FPORT=5. See payload section for detail.
725
726
727 === 4.3.3 Set Password ===
728
729
730 Feature: Set device password, max 9 digits
731
732 (% style="color:#4f81bd" %)**AT Command: **
733
734 (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:372px" %)
735 |(% style="background-color:#4f81bd; color:white; width:155px" %)**Command Example**|(% style="background-color:#4f81bd; color:white; width:128px" %)**Function**|(% style="background-color:#4f81bd; color:white; width:89px" %)**Response**
736 |(% style="width:155px" %)AT+PWORD=?|(% style="width:124px" %)Show password|(% style="width:86px" %)(((
737 123456
738
739 OK
740 )))
741 |(% style="width:155px" %)AT+PWORD=999999|(% style="width:124px" %)Set password|(% style="width:86px" %)OK
742
743 (% style="color:#4f81bd" %)**Downlink Command:**
744
745 No downlink command for this feature.
746
747
748 === 4.3.4 Set to sleep mode ===
749
750
751 Feature: Set device to sleep mode
752
753 * (% style="color:#037691" %)**AT+Sleep=0**(%%)  : Normal working mode, device will sleep and use lower power when there is no LoRa message
754
755 * (% style="color:#037691" %)**AT+Sleep=1**(%%) :  Device is in deep sleep mode, no LoRa activation happen, used for storage or shipping.
756
757 (% style="color:#4f81bd" %)**AT Command: **
758
759 (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:513px" %)
760 |(% style="background-color:#4f81bd; color:white; width:155px" %)**Command Example**|(% style="background-color:#4f81bd; color:white; width:140px" %)**Function**|(% style="background-color:#4f81bd; color:white; width:218px" %)**Response**
761 |(% style="width:155px" %)AT+SLEEP|(% style="width:139px" %)Set to sleep mode|(% style="width:213px" %)(((
762 Clear all stored sensor data…
763
764 OK
765 )))
766
767 (% style="color:#4f81bd" %)**Downlink Command:**
768
769 * There is no downlink command to set to Sleep mode.
770
771 === 4.3.5 Set UOA (Uplink on Activity) ===
772
773
774 Feature: Enable / Disable Uplink on Activity.
775
776 After the UOA is enabled, the LHT65N-PIR sends an uplink when the count is triggered.
777
778 (% style="color:#4f81bd" %)**AT Command: **
779
780 * (% style="color:#037691" %)**AT+UOA=0**(%%)  : Disable UoA
781
782 * (% style="color:#037691" %)**AT+UOA=1,2**(%%) :  Enable UoA , Calm Down Time: 2 minutes. If device already send a uplink on activity, it will not send another uplink on activiy in 2 minutes, even detect activity.
783
784 (% style="color:red" %)**Notice: Calm Down time range is 1 ~~ 65535 minutes. If user set Calm Down time to low value, such as 1 minute, the sensor might send uplink very frequenctly and battery drain fast.**
785
786
787 (% style="color:#4f81bd" %)**Downlink Command:**
788
789 Format: Command Code (0xA1) followed by 1 byte or 3 bytes.
790
791 When followed by 3 bytes, the first byte is 01, and the second and third bytes are Calm Down Time.
792
793 * (% style="color:#037691" %)**A1 00    **(%%)** ==>    **AT+UOA=0**     **
794 * (% style="color:#037691" %)**A1 01 00 02  **(%%)** ==>    **AT+UOA=1,2
795
796 === (% data-sider-select-id="50a6265d-b76f-4699-846b-b82bee3a7ab0" %)4.3.6 Get data(%%) ===
797
798
799 Feature: Get the current sensor data
800
801 (% style="color:#4f81bd" %)**AT Command:**
802
803 * **AT+GETSENSORVALUE=0**      ~/~/ The serial port gets the reading of the current sensor
804 * **AT+GETSENSORVALUE=1**      ~/~/  The serial port gets the current sensor reading and uploads it.
805
806 === (% data-sider-select-id="14f87315-b24f-4278-9b6c-0a8c2f35ad00" %)4.3.7 Set count number(%%) ===
807
808
809 Feature: Manually set the count number
810
811 (% style="color:#4f81bd" %)**AT Command: AT+SETCNT**
812
813 (% border="1" cellspacing="3" style="background-color:#f2f2f2; width:481px" %)
814 |=(% style="width: 162px;background-color:#4F81BD;color:white" %)**Command Example**|=(% style="width: 224px;background-color:#4F81BD;color:white" %)**Function**|=(% style="width: 95px;background-color:#4F81BD;color:white" %)**Response**
815 |(% style="width:162px" %)AT+SETCNT=0|(% style="width:222px" %)Set the count number to 0.|(% style="width:93px" %)OK
816 |(% style="width:162px" %)AT+SETCNT=100|(% style="width:222px" %)Set the count number to 100.|(% style="width:93px" %)OK
817
818 = 5. Battery & Power Consumption =
819
820
821 LHT65N-PIR use **CR17450** battery pack. See below link for detail information about the battery info and how to replace.
822
823 [[**Battery Info & Power Consumption Analyze**>>url:http://wiki.dragino.com/xwiki/bin/view/Main/How%20to%20calculate%20the%20battery%20life%20of%20Dragino%20sensors%3F/]] .
824
825
826 = 6. OTA firmware update =
827
828
829 User can change firmware LHT65N-PIR to:
830
831 * Change Frequency band/ region.
832 * Update with new features.
833 * Fix bugs.
834
835 Firmware and changelog can be downloaded from : **[[Firmware download link>>https://www.dropbox.com/scl/fo/ztlw35a9xbkomu71u31im/AAAJrw0bI6-cH8sPI8uQL2U/LoRaWAN%20End%20Node/LHT65N-PIR?rlkey=ojjcsw927eaow01dgooldq3nu&subfolder_nav_tracking=1&dl=0]]**
836
837 Methods to Update Firmware:
838
839 * (Recommanded way) OTA firmware update via wireless: [[http:~~/~~/wiki.dragino.com/xwiki/bin/view/Main/Firmware%20OTA%20Update%20for%20Sensors/>>url:http://wiki.dragino.com/xwiki/bin/view/Main/Firmware%20OTA%20Update%20for%20Sensors/]]
840 * Update through UART TTL interface. **[[Instruction>>url:http://wiki.dragino.com/xwiki/bin/view/Main/UART%20Access%20for%20LoRa%20ST%20v4%20base%20model/#H1.LoRaSTv4baseHardware]]**.
841
842 = 7. FAQ =
843
844 == 7.1 How to use AT Command? ==
845
846 Refer this link for [[UART Hardware Connection>>url:http://wiki.dragino.com/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H6.1HowtoconnecttoLHT65NUARTinterface3F]].
847
848 In PC, User needs to set serial tool(such as [[**putty**>>https://www.chiark.greenend.org.uk/~~sgtatham/putty/latest.html]], SecureCRT) baud rate to (% style="color:green" %)**9600** (%%)to access to access serial console for LHT65N-PIR. The AT commands are disable by default and need to enter password (default:(% style="color:green" %)**123456**(% style="color:red" %))(%%) to active it. Timeout to input AT Command is 5 min, after 5-minute, user need to input password again. User can use AT+DISAT command to disable AT command before timeout.
849
850 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615154519-3.png||_mstalt="431925" height="672" width="807"]]
851
852
853 == 7.2 Where to use AT commands and Downlink commands ==
854
855
856 **AT commands:**
857
858 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220620153708-1.png||_mstalt="429806" height="603" width="723"]]
859
860
861 **Downlink commands:**
862
863
864
865 (% style="color:blue" %)**TTN:**
866
867 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615092124-2.png||_mstalt="429221" height="649" width="688"]]
868
869
870
871 (% style="color:blue" %)**Helium:**
872
873 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615092551-3.png||_mstalt="430794" height="423" width="835"]]
874
875
876
877 (% style="color:blue" %)**Chirpstack: The downlink window will not be displayed until the network is accessed**
878
879
880 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615094850-6.png||_mstalt="433082"]]
881
882
883 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615094904-7.png||_mstalt="433485" height="281" width="911"]]
884
885
886
887 (% style="color:blue" %)**Aws:**
888
889 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615092939-4.png||_mstalt="434460" height="448" width="894"]]
890
891
892 == 7.3 How to change the uplink interval? ==
893
894
895 Please see this link: [[http:~~/~~/wiki.dragino.com/xwiki/bin/view/Main/How%20to%20set%20the%20transmit%20time%20interval/>>url:http://wiki.dragino.com/xwiki/bin/view/Main/How%20to%20set%20the%20transmit%20time%20interval/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
896
897 [[image:Main.User Manual for LoRaWAN End Nodes.LHT65N-E5 LoRaWAN Temperature_Humidity & Illuminance Sensor User Manual.WebHome@image-20220615154519-3.png||_mstalt="431925" height="672" width="807"]]
898
899
900 == 7.4 How to upgrade firmware? ==
901
902 Please check [[update instruction>>url:http://wiki.dragino.com/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H6.5Howtoupgradefirmware3F]].
903
904
905 = 8. Order Info =
906
907
908 Part Number: (% style="color:#4f81bd" %)** LHT65N-PIR-XX**
909
910 (% style="color:#4f81bd" %)**XX **(%%): The default frequency band
911
912 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**AS923**(%%): LoRaWAN AS923 band
913 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**AU915**(%%): LoRaWAN AU915 band
914 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**EU433**(%%): LoRaWAN EU433 band
915 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**EU868**(%%): LoRaWAN EU868 band
916 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**KR920**(%%): LoRaWAN KR920 band
917 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**US915**(%%): LoRaWAN US915 band
918 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**IN865**(%%): LoRaWAN IN865 band
919 * (% style="color:#4f81bd" %)** **(% _mstmutation="1" style="color:red" %)**CN470**(%%): LoRaWAN CN470 band
920
921 = 9. Packing Info =
922
923
924 **Package Includes**:
925
926 * LHT65N-PIR Temperature/Humidity/PIR Sensor x 1
927
928 = 10. Reference material =
929
930
931 * [[Datasheet, photos, decoder, firmware>>https://www.dropbox.com/sh/una19zsni308dme/AACOKp6J2RF5TMlKWT5zU3RTa?dl=0]]
932
933 = 11. FCC Warning =
934
935
936 This device complies with part 15 of the FCC Rules.Operation is subject to the following two conditions:
937
938 (1) This device may not cause harmful interference;