Version 76.4 by Xiaoling on 2022/05/23 15:37

Show last authors
1 (% style="text-align:center" %)
2 [[image:image-20220523115324-1.jpeg||height="500" width="500"]]
3
4
5 **LHT65N LoRaWAN Temperature & Humidity Sensor Manual**
6
7
8
9 **Table of Contents:**
10
11 {{toc/}}
12
13
14
15 = 1.Introduction =
16
17 == 1.1 What is LHT65N Temperature & Humidity Sensor ==
18
19 (((
20 The Dragino LHT65N Temperature & Humidity sensor is a Long Range LoRaWAN Sensor. It includes a (% style="color:#4f81bd" %)**built-in Temperature & Humidity sensor**(%%) and has an external sensor connector to connect to an external (% style="color:#4f81bd" %)**Temperature Sensor**(%%)**.**
21 )))
22
23 (((
24 The LHT65N allows users to send data and reach extremely long ranges. It provides ultra-long range spread spectrum communication and high interference immunity whilst minimizing current consumption. It targets professional wireless sensor network applications such as irrigation systems, smart metering, smart cities, building automation, and so on.
25 )))
26
27 (((
28 LHT65N has a built-in 2400mAh non-chargeable battery which can be used for up to 10 years*.
29 )))
30
31 (((
32 LHT65N is full compatible with LoRaWAN v1.0.3 Class A protocol, it can work with a standard LoRaWAN gateway.
33 )))
34
35 (((
36 LHT65N supports (% style="color:#4f81bd" %)**Datalog Feature**(%%). It will record the data when there is no network coverage and users can retrieve the sensor value later to ensure no miss for every sensor reading.
37 )))
38
39 (((
40 *The actual battery life depends on how often to send data, please see the battery analyzer chapter.
41 )))
42
43 == 1.2 Features ==
44
45 * Wall mountable
46 * LoRaWAN v1.0.3 Class A protocol
47 * Frequency Bands: CN470/EU433/KR920/US915/EU868/AS923/AU915
48 * AT Commands to change parameters
49 * Remote configure parameters via LoRaWAN Downlink
50 * Firmware upgradeable via program port
51 * Built-in 2400mAh battery for up to 10 years of use.
52 * Built-in Temperature & Humidity sensor
53 * Optional External Sensors
54 * Tri-color LED to indicate working status
55 * Datalog feature
56
57 == 1.3 Specification ==
58
59 (((
60 **Built-in Temperature Sensor:**
61 )))
62
63 * (((
64 Resolution: 0.01 °C
65 )))
66 * (((
67 Accuracy Tolerance : Typ ±0.3 °C
68 )))
69 * (((
70 Long Term Drift: < 0.02 °C/yr
71 )))
72 * (((
73 Operating Range: -40 ~~ 85 °C
74 )))
75
76 (((
77 **Built-in Humidity Sensor:**
78 )))
79
80 * (((
81 Resolution: 0.04 %RH
82 )))
83 * (((
84 Accuracy Tolerance : Typ ±3 %RH
85 )))
86 * (((
87 Long Term Drift: < 0.02 °C/yr
88 )))
89 * (((
90 Operating Range: 0 ~~ 96 %RH
91 )))
92
93 (((
94 **External Temperature Sensor:**
95 )))
96
97 * (((
98 Resolution: 0.0625 °C
99 )))
100 * (((
101 ±0.5°C accuracy from -10°C to +85°C
102 )))
103 * (((
104 ±2°C accuracy from -55°C to +125°C
105 )))
106 * (((
107 Operating Range: -55 °C ~~ 125 °C
108 )))
109
110 = 2. Connect LHT65N to IoT Server =
111
112 == 2.1 How does LHT65N work? ==
113
114 (((
115 LHT65N is configured as LoRaWAN OTAA Class A mode by default. Each LHT65N is shipped with a worldwide unique set of OTAA keys. To use LHT65N in a LoRaWAN network, first, we need to put the OTAA keys in LoRaWAN Network Server and then activate LHT65N.
116 )))
117
118 (((
119 If LHT65N is under the coverage of this LoRaWAN network. LHT65N can join the LoRaWAN network automatically. After successfully joining, LHT65N will start to measure environment temperature and humidity, and start to transmit sensor data to the LoRaWAN server. The default period for each uplink is 20 minutes.
120 )))
121
122 == 2.2 How to Activate LHT65N? ==
123
124 The LHT65N has two working modes:
125
126 * **Deep Sleep Mode**: LHT65N doesn’t have any LoRaWAN activation. This mode is used for storage and shipping to save battery life.
127 * **Working Mode**: In this mode, LHT65N works as LoRaWAN Sensor mode to Join LoRaWAN network and send out the sensor data to the server. Between each sampling/tx/rx periodically, LHT65 will be in STOP mode (IDLE mode), in STOP mode, LHT65N has the same power consumption as Deep Sleep mode. 
128
129 (((
130 The LHT65N is set in deep sleep mode by default; The ACT button on the front is to switch to different modes:
131 )))
132
133 [[image:image-20220515123819-1.png||height="379" width="317"]]
134
135 [[image:image-20220523153201-19.png||height="163" width="739"]]
136
137 == 2.3 Example to join LoRaWAN network ==
138
139 (% class="wikigeneratedid" %)
140 This section shows an example of how to join the TTN V3 LoRaWAN IoT server. Use with other LoRaWAN IoT servers is of a similar procedure.
141
142 (% class="wikigeneratedid" %)
143 [[image:image-20220522232442-1.png||height="387" width="648"]]
144
145 Assume the LPS8N is already set to connect to [[TTN V3 network>>url:https://eu1.cloud.thethings.network]], So it provides network coverage for LHT65N. Next we need to add the LHT65N device in TTN V3:
146
147
148 === 2.3.1 Step 1: Create Device n TTN ===
149
150 Create a device in TTN V3 with the OTAA keys from LHT65N.
151
152 Each LHT65N is shipped with a sticker with its device EUI, APP Key and APP EUI as below:
153
154 [[image:image-20220522232812-2.png||height="219" width="279"]]
155
156 User can enter these keys in the LoRaWAN Server portal. Below is TTN V3 screenshot:
157
158 Add APP EUI in the application.
159
160 [[image:image-20220522232916-3.png]]
161
162 [[image:image-20220522232932-4.png]]
163
164 [[image:image-20220522232954-5.png]]
165
166 Note: LHT65N use same payload as LHT65.
167
168 [[image:image-20220522233026-6.png]]
169
170
171 Input APP EUI,  APP KEY and DEV EUI:
172
173 [[image:image-20220522233118-7.png]]
174
175
176 === 2.3.2 Step 2: Activate LHT65N by pressing the ACT button for more than 5 seconds. ===
177
178 Use ACT button to activate LHT65N and it will auto-join to the TTN V3 network. After join success, it will start to upload sensor data to TTN V3 and user can see in the panel.
179
180 [[image:image-20220522233300-8.png||height="219" width="722"]]
181
182
183 == 2.4 Uplink Payload ==
184
185 The uplink payload includes totally 11 bytes. Uplink packets use FPORT=2 and (% style="color:#4f81bd" %)**every 20 minutes**(%%) send one uplink by default.
186
187 After each uplink, the (% style="color:blue" %)**BLUE LED**(%%) will blink once.
188
189 (% border="1" style="background-color:#ffffcc; color:green; width:426px" %)
190 |(% style="width:97px" %)(((
191 **Size(bytes)**
192 )))|(% style="width:39px" %)(((
193 **2**
194 )))|(% style="width:100px" %)(((
195 **2**
196 )))|(% style="width:77px" %)(((
197 **2**
198 )))|(% style="width:47px" %)(((
199 **1**
200 )))|(% style="width:51px" %)(((
201 **4**
202 )))
203 |(% style="width:97px" %)(((
204 **Value**
205 )))|(% style="width:39px" %)(((
206 [[BAT>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.2BAT-BatteryInfo]]
207 )))|(% style="width:100px" %)(((
208 (((
209 [[Built-In Temperature>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.3Built-inTemperature]]
210 )))
211 )))|(% style="width:77px" %)(((
212 (((
213 [[Built-in>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.4Built-inHumidity]]
214 )))
215
216 (((
217 [[Humidity>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.4Built-inHumidity]]
218 )))
219 )))|(% style="width:47px" %)(((
220 [[Ext>>path:#Extension_Sensor]] #
221 )))|(% style="width:51px" %)(((
222 [[Ext value>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.6Extvalue]]
223 )))
224
225 * The First 6 bytes: has fix meanings for every LHT65N.
226 * The 7th byte (EXT #): defines the external sensor model.
227 * The 8^^th^^ ~~ 11^^th^^ byte: the value for external sensor value. The definition is based on external sensor type. (If EXT=0, there won’t be these four bytes.)
228
229 === 2.4.1 Decoder in TTN V3 ===
230
231 When the uplink payload arrives TTNv3, it shows HEX format and not friendly to read. We can add LHT65N decoder in TTNv3 for friendly reading.
232
233 Below is the position to put the decoder and LHT65N decoder can be download from here:
234
235 [[https:~~/~~/www.dropbox.com/sh/r2i3zlhsyrpavla/AAB1sZw3mdT0K7XjpHCITt13a?dl=0 >>https://www.dropbox.com/sh/r2i3zlhsyrpavla/AAB1sZw3mdT0K7XjpHCITt13a?dl=0]]
236
237 [[image:image-20220522234118-10.png||height="353" width="729"]]
238
239 === 2.4.2 BAT-Battery Info ===
240
241 These two bytes of BAT include the battery state and the actually voltage
242
243 [[image:image-20220523152839-18.png]]
244
245 [[image:image-20220522235639-1.png||height="139" width="727"]]
246
247 Check the battery voltage for LHT65N.
248
249 * BAT status=(0Xcba4>>14)&0xFF=11(B),very good
250 * Battery Voltage =0xCBF6&0x3FFF=0x0BA4=2980mV
251
252 === 2.4.3 Built-in Temperature ===
253
254 [[image:image-20220522235639-2.png||height="138" width="722"]]
255
256 * Temperature:  0x0ABB/100=27.47℃
257
258 [[image:image-20220522235639-3.png]]
259
260 * Temperature:  (0xF5C6-65536)/100=-26.18℃
261
262 === 2.4.4 Built-in Humidity ===
263
264 [[image:image-20220522235639-4.png||height="138" width="722"]]
265
266 * Humidity:    0x025C/10=60.4%
267
268 === 2.4.5 Ext # ===
269
270 Bytes for External Sensor:
271
272 [[image:image-20220523152822-17.png]]
273
274 === 2.4.6 Ext value ===
275
276 ==== 2.4.6.1 Ext~=1, E3 Temperature Sensor ====
277
278 [[image:image-20220522235639-5.png]]
279
280 * DS18B20 temp=0x0ADD/100=27.81℃
281
282 The last 2 bytes of data are meaningless
283
284 [[image:image-20220522235639-6.png]]
285
286 * External temperature= (0xF54F-65536)/100=-27.37℃
287
288 (((
289 The last 2 bytes of data are meaningless
290 )))
291
292 (((
293 If the external sensor is 0x01, and there is no external temperature connected. The temperature will be set to 7FFF which is 327.67℃
294 )))
295
296
297 ==== 2.4.6.2 Ext~=9, E3 sensor with Unix Timestamp ====
298
299 Timestamp mode is designed for LHT65N with E3 probe, it will send the uplink payload with Unix timestamp. With the limitation of 11 bytes (max distance of AU915/US915/AS923 band), the time stamp mode will be lack of BAT voltage field, instead, it shows the battery status. The payload is as below:
300
301 (% border="1" style="background-color:#ffffcc; color:green; width:468px" %)
302 |(% style="width:96px" %)(((
303 **Size(bytes)**
304 )))|(% style="width:71px" %)(((
305 **2**
306 )))|(% style="width:99px" %)(((
307 **2**
308 )))|(% style="width:132px" %)(((
309 **2**
310 )))|(% style="width:54px" %)(((
311 **1**
312 )))|(% style="width:64px" %)(((
313 **4**
314 )))
315 |(% style="width:96px" %)(((
316 **Value**
317 )))|(% style="width:71px" %)(((
318 [[External temperature>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H4.2SetExternalSensorMode]]
319 )))|(% style="width:99px" %)(((
320 (((
321 [[Built-In>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.3Built-inTemperature]]
322 )))
323
324 (((
325 [[Temperature>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.3Built-inTemperature]]
326 )))
327 )))|(% style="width:132px" %)(((
328 (((
329 BAT Status &
330 )))
331
332 (((
333 [[Built-in Humidity>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.4Built-inHumidity]]
334 )))
335 )))|(% style="width:54px" %)(((
336 Status & Ext
337 )))|(% style="width:64px" %)(((
338 (((
339 [[Unix Time Stamp>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H4.1SetTransmitIntervalTime]]
340 )))
341 )))
342
343 * **Battery status & (% class="wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink wikiinternallink" %)Built-in Humidity(%%)**
344
345 (% border="1" style="background-color:#ffffcc; color:green; width:469px" %)
346 |(% style="width:65px" %)Bit(bit)|(% style="width:267px" %)[15:14]|(% style="width:134px" %)[11:0]
347 |(% style="width:65px" %)Value|(% style="width:267px" %)(((
348 BAT Status
349
350 00(b): Ultra Low ( BAT <= 2.50v)
351
352 01(b): Low  (2.50v <=BAT <= 2.55v)
353
354 10(b): OK   (2.55v <= BAT <=2.65v)
355
356 11(b): Good   (BAT >= 2.65v)
357 )))|(% style="width:134px" %)(((
358 [[Built-in Humidity>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.4Built-inHumidity]]
359
360
361 )))
362
363 * **Status & Ext Byte**
364
365 [[image:image-20220523152434-16.png]]
366
367 * Poll Message Flag: 1: This message is a poll message reply, 0: means this is a normal uplink.
368 * Sync time OK: 1: Set time ok,0: N/A. After time SYNC request is sent, LHT65N will set this bit to 0 until got the time stamp from the application server.
369 * Unix Time Request:1: Request server downlink Unix time, 0 : N/A. In this mode, LHT65N will set this bit to 1 every 10 days to request a time SYNC. (AT+SYNCMOD to set this)
370
371 == 2.5 Show data on Datacake ==
372
373 Datacake IoT platform provides a human-friendly interface to show the sensor data, once we have sensor data in TTN V3, we can use Datacake to connect to TTN V3 and see the data in Datacake. Below are the steps:
374
375 (((
376 **Step 1**: Be sure that your device is programmed and properly connected to the LoRaWAN network.
377 )))
378
379 (((
380 **Step 2**: Configure your Application to forward data to Datacake you will need to add integration. Go to TTN V3 Console ~-~-> Applications ~-~-> Integrations ~-~-> Add Integrations.
381 )))
382
383 (((
384 Add Datacake:
385 )))
386
387 [[image:image-20220523000825-7.png||height="262" width="583"]]
388
389
390 Select default key as Access Key:
391
392 [[image:image-20220523000825-8.png||height="453" width="406"]]
393
394 In Datacake console ([[https:~~/~~/datacake.co/>>url:https://datacake.co/]]) , add LHT65 device.
395
396 [[image:image-20220523000825-9.png||height="366" width="392"]]
397
398 [[image:image-20220523000825-10.png||height="413" width="728"]]
399
400 == 2.6 Datalog Feature ==
401
402 This feature is always enabled. When user wants to retrieve the sensor value, he can send a poll command from the IoT platform to ask LHT65N to send the value in the required time slot.
403
404 === 2.6.1 Unix TimeStamp ===
405
406 LHT65N uses Unix TimeStamp format based on
407
408 [[image:image-20220523001219-11.png||height="97" width="627"]]
409
410
411 (((
412 User can get this time from link:  [[https:~~/~~/www.epochconverter.com/>>url:https://www.epochconverter.com/]] :
413 )))
414
415 (((
416 Below is the converter example
417 )))
418
419 [[image:image-20220523001219-12.png||height="298" width="720"]]
420
421 So, we can use AT+TIMESTAMP=1611889405 or downlink 3060137afd00 to set the current time 2021 – Jan ~-~- 29 Friday 03:03:25
422
423 === 2.6.2 Set Device Time ===
424
425 (((
426 There are two ways to set device’s time:
427 )))
428
429 (((
430 **~1. Through LoRaWAN MAC Command (Default settings)**
431 )))
432
433 (((
434 User need to set SYNCMOD=1 to enable sync time via MAC command.
435 )))
436
437 (((
438 Once LHT65N Joined LoRaWAN network, it will send the MAC command (DeviceTimeReq) and the server will reply with (DeviceTimeAns) to send the current time to LHT65N. If LHT65N fails to get the time from the server, LHT65N will use the internal time and wait for next time request (AT+SYNCTDC to set the time request period, default is 10 days).
439 )))
440
441 (((
442 Note: LoRaWAN Server need to support LoRaWAN v1.0.3(MAC v1.0.3) or higher to support this MAC command feature, Chirpstack,TTN V3 v3 and loriot support but TTN V3 v2 doesn’t support. If server doesn’t support this command, it will through away uplink packet with this command, so user will lose the packet with time request for TTN V3 v2 if SYNCMOD=1.
443 )))
444
445 (((
446
447 )))
448
449 (((
450 **2. Manually Set Time**
451 )))
452
453 (((
454 User needs to set SYNCMOD=0 to manual time, otherwise, the user set time will be overwritten by the time set by the server.
455 )))
456
457 === 2.6.3 Poll sensor value ===
458
459 User can poll sensor value based on timestamps from the server. Below is the downlink command.
460
461 [[image:image-20220523152302-15.png]]
462
463 (((
464 Timestamp start and Timestamp end use Unix TimeStamp format as mentioned above. Devices will reply with all data log during this time period, use the uplink interval.
465 )))
466
467 (((
468 For example, downlink command **31 5FC5F350 5FC6 0160 05**
469 )))
470
471 (((
472 Is to check 2020/12/1 07:40:00 to 2020/12/1 08:40:00’s data
473 )))
474
475 (((
476 Uplink Internal =5s,means LHT65N will send one packet every 5s. range 5~~255s.
477 )))
478
479
480 === 2.6.4 Datalog Uplink payload ===
481
482 The Datalog poll reply uplink will use below payload format.
483
484 (((
485 **Retrieval data payload**
486 )))
487
488 (% border="1" style="background-color:#ffffcc; color:green; width:545px" %)
489 |(% style="width:93px" %)(((
490 **Size(bytes)**
491 )))|(% style="width:71px" %)(((
492 **2**
493 )))|(% style="width:102px" %)(((
494 **2**
495 )))|(% style="width:86px" %)(((
496 **2**
497 )))|(% style="width:90px" %)(((
498 **1**
499 )))|(% style="width:85px" %)(((
500 **4**
501 )))
502 |(% style="width:93px" %)(((
503 **Value**
504 )))|(% style="width:71px" %)(((
505 [[External sensor data>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.6Extvalue]]
506 )))|(% style="width:102px" %)(((
507 (((
508 [[Built In>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.3Built-inTemperature]]
509 )))
510
511 (((
512 [[Temperature>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.3Built-inTemperature]]
513 )))
514 )))|(% style="width:86px" %)(((
515 (((
516 [[Built-in>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.4Built-inHumidity]]
517 )))
518
519 (((
520 [[Humidity>>http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.4.4Built-inHumidity]]
521 )))
522 )))|(% style="width:90px" %)(((
523 [[Poll message flag & Ext>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.6.4DatalogUplinkpayload]]
524 )))|(% style="width:85px" %)(((
525 (((
526 [[Unix Time Stamp>>path:http://8.211.40.43/xwiki/bin/view/Main/User%20Manual%20for%20LoRaWAN%20End%20Nodes/LHT65N%20LoRaWAN%20Temperature%20%26%20Humidity%20Sensor%20Manual/#H2.6.1UnixTimeStamp]]
527 )))
528
529 (((
530
531 )))
532 )))
533
534 **Poll message flag & Ext**
535
536 [[image:image-20220523152208-14.png]]
537
538 (((
539 (((
540 Poll Message Flag: 1: This message is a poll message reply.
541 )))
542 )))
543
544 * (((
545 (((
546 Poll Message Flag is set to 1.
547 )))
548 )))
549 * (((
550 (((
551 Each data entry is 11 bytes, to save airtime and battery, devices will send max bytes according to the current DR and Frequency bands.
552 )))
553 )))
554
555 (((
556 (((
557 For example, in US915 band, the max payload for different DR is:
558 )))
559 )))
560
561 (((
562 (((
563 a) DR0: max is 11 bytes so one entry of data
564 )))
565 )))
566
567 (((
568 (((
569 b) DR1: max is 53 bytes so devices will upload 4 entries of data (total 44 bytes)
570 )))
571 )))
572
573 (((
574 (((
575 c) DR2: total payload includes 11 entries of data
576 )))
577 )))
578
579 (((
580 (((
581 d) DR3: total payload includes 22 entries of data.
582 )))
583 )))
584
585 (((
586 (((
587 If devise doesn’t have any data in the polling time. Device will uplink 11 bytes of 0   
588 )))
589 )))
590
591
592 **Example:**
593
594 If LHT65N has below data inside Flash:
595
596 [[image:image-20220523144455-1.png||height="335" width="735"]]
597
598 If user sends below downlink command: (% style="background-color:yellow" %)3160065F9760066DA705
599
600 Where : Start time: 60065F97 = time 21/1/19 04:27:03
601
602 Stop time 60066DA7= time 21/1/19 05:27:03
603
604
605 LHT65N will uplink this payload.
606
607 [[image:image-20220523001219-13.png||height="421" width="727"]]
608
609 7FFF089801464160065F977FFF088E014B41600660097FFF0885014E41600660667FFF0875015141600662BE7FFF086B015541600665167FFF08660155416006676E7FFF085F015A41600669C67FFF0857015D4160066C1E
610
611 Where the first 11 bytes is for the first entry:
612
613 7FFF089801464160065F97
614
615 Ext sensor data=0x7FFF/100=327.67
616
617 Temp=0x0898/100=22.00
618
619 Hum=0x0146/10=32.6
620
621 poll message flag & Ext=0x41,means reply data,Ext=1
622
623 Unix time is 0x60065F97=1611030423s=21/1/19 04:27:03
624
625 == 2.7 Alarm Mode ==
626
627 Alarm mode feature is added since firmware v1.5. When device is in Alarm mode, it will check the built-in sensor temperature in a short interval. If the temperature exceeds the pre-configure range, it will send an uplink immediately.
628
629 (% style="color:red" %)Note: Alarm mode will increase a little big the power consumption, we recommend extending the normal reading time when enabling this feature.
630
631 **AT Commands for Alarm mode:**
632
633 (% class="box infomessage" %)
634 (((
635 **AT+WMOD=1**: Enable/Disable Alarm Mode. (0:Disable, 1: Enable)
636 )))
637
638 (% class="box infomessage" %)
639 (((
640 **AT+CITEMP=1**: The interval to check the temperature for Alarm. (Unit: minute)
641 )))
642
643 == 2.8 LED Indicator ==
644
645 (((
646 The LHT65N has a triple color LED which for easy shows different stage.
647 )))
648
649 (((
650 While pressing ACT button, the LED will work as per LED status with ACT button.
651 )))
652
653 (((
654 In a normal working state:
655 )))
656
657 * (((
658 For each uplink, the BLUE LED or RED LED will blink once.
659 )))
660 * (((
661 BLUE LED when an external sensor is connected
662 )))
663 * (((
664 RED LED when an external sensor is not connected
665 )))
666 * (((
667 For each success downlink, the PURPLE LED will blink once
668 )))
669
670 ----
671
672 == 2.9 Installation ==
673
674 [[image:image-20220516231650-1.png||height="436" width="428"]]
675
676 = 3. Sensors & Accessories =
677
678 == 3.1 E3 Temperature Probe ==
679
680 [[image:image-20220515080154-4.png||height="182" width="161"]] [[image:image-20220515080330-5.png||height="201" width="195"]]
681
682
683 With Temperature sensor with 2 meters cable long
684
685 * Resolution: 0.0625 °C
686 * ±0.5°C accuracy from -10°C to +85°C
687 * ±2°C accuracy from -55°C to +125°C
688 * Operating Range: -40 ~~ 125 °C
689 * -55°C to 125°C
690 * Working voltage 2.35v ~~ 5v
691
692 = 4. Configure LHT65N via AT Command or LoRaWAN Downlink =
693
694 Use can configure LHT65N via AT Command or LoRaWAN Downlink.
695
696 * AT Command Connection: See [[FAQ>>path:#AT_COMMAND]].
697 * LoRaWAN Downlink instruction for different platforms:
698
699 [[http:~~/~~/wiki.dragino.com/index.php?title=Main_Page#Use_Note_for_Server>>url:http://wiki.dragino.com/index.php?title=Main_Page#Use_Note_for_Server]]
700
701 There are two kinds of commands to configure LHT65N, they are:
702
703 (% style="color:#4f81bd" %)* **General Commands**.
704
705 These commands are to configure:
706
707 * General system settings like: uplink interval.
708 * LoRaWAN protocol & radio-related commands.
709
710 They are the same for all Dragino Devices which supports DLWS-005 LoRaWAN Stack(Note~*~*). These commands can be found on the wiki:
711
712 [[http:~~/~~/wiki.dragino.com/index.php?title=End_Device_Downlink_Command>>url:http://wiki.dragino.com/index.php?title=End_Device_Downlink_Command]]
713
714 (% style="color:#4f81bd" %)* **Commands special design for LHT65N**
715
716 These commands are only valid for LHT65N, as below:
717
718 == 4.1 Set Transmit Interval Time ==
719
720 Feature: Change LoRaWAN End Node Transmit Interval.
721
722 **AT Command: AT+TDC**
723
724 [[image:image-20220523150701-2.png]]
725
726 **Downlink Command: 0x01**
727
728 Format: Command Code (0x01) followed by 3 bytes time value.
729
730 If the downlink payload=0100003C, it means set the END Node’s Transmit Interval to 0x00003C=60(S), while type code is 01.
731
732 * **Example 1**: Downlink Payload: 0100001E ~/~/ Set Transmit Interval (TDC) = 30 seconds
733 * **Example 2**: Downlink Payload: 0100003C ~/~/ Set Transmit Interval (TDC) = 60 seconds
734
735 == 4.2 Set External Sensor Mode ==
736
737 Feature: Change External Sensor Mode.
738
739 **AT Command: AT+EXT**
740
741 [[image:image-20220523150759-3.png]]
742
743 **Downlink Command: 0xA2**
744
745 Total bytes: 2 ~~ 5 bytes
746
747 **Example:**
748
749 * 0xA201: Set external sensor type to E1
750 * 0xA209: Same as AT+EXT=9
751 * 0xA20702003c,Same as AT+SETCNT=60
752
753 == 4.3 Enable/Disable uplink Temperature probe ID ==
754
755 Feature: If PID is enabled, device will send the temperature probe ID on:
756
757 * First Packet after OTAA Join
758 * Every 24 hours since the first packet.
759
760 PID is default set to disable (0)
761
762 **AT Command:**
763
764 [[image:image-20220523150928-4.png]]
765
766 **Downlink Command:**
767
768 * 0xA800  **~-~->** AT+PID=0
769 * 0xA801     **~-~->** AT+PID=1
770
771 == 4.4 Set Password ==
772
773 Feature: Set device password, max 9 digits
774
775 **AT Command: AT+PWORD**
776
777 [[image:image-20220523151052-5.png]]
778
779 **Downlink Command:**
780
781 No downlink command for this feature.
782
783 == 4.5 Quit AT Command ==
784
785 Feature: Quit AT Command mode, so user needs to input password again before use AT Commands.
786
787 **AT Command: AT+DISAT**
788
789 [[image:image-20220523151132-6.png]]
790
791 **Downlink Command:**
792
793 No downlink command for this feature.
794
795 == 4.6 Set to sleep mode ==
796
797 Feature: Set device to sleep mode
798
799 **AT Command: AT+SLEEP**
800
801 [[image:image-20220523151218-7.png]]
802
803 **Downlink Command:**
804
805 * There is no downlink command to set to Sleep mode.
806
807 == 4.7 Set system time ==
808
809 Feature: Set system time, unix format. [[See here for format detail.>>path:#TimeStamp]]
810
811 **AT Command:**
812
813 [[image:image-20220523151253-8.png]]
814
815 **Downlink Command:**
816
817 0x306007806000 ~/~/ Set timestamp to 0x(6007806000),Same as AT+TIMESTAMP=1611104352
818
819 == 4.8 Set Time Sync Mode ==
820
821 Feature: Enable/Disable Sync system time via LoRaWAN MAC Command (DeviceTimeReq), LoRaWAN server must support v1.0.3 protocol to reply this command.
822
823 SYNCMOD is set to 1 by default. If user want to set a different time from LoRaWAN server, user need to set this to 0.
824
825 **AT Command:**
826
827 [[image:image-20220523151336-9.png]]
828
829 **Downlink Command:**
830
831 0x28 01 ~/~/ Same As AT+SYNCMOD=1
832
833 0x28 00 ~/~/ Same As AT+SYNCMOD=0
834
835 == 4.9 Set Time Sync Interval ==
836
837 Feature: Define System time sync interval. SYNCTDC default value: 10 days.
838
839 **AT Command:**
840
841 [[image:image-20220523151411-10.png]]
842
843 **Downlink Command:**
844
845 0x29 0A ~/~/ Same as AT+SYNCTDC=0x0A
846
847 == 4.10 Print data entries base on page. ==
848
849 Feature: Print the sector data from start page to stop page (max is 416 pages).
850
851 **AT Command: AT+PDTA**
852
853 [[image:image-20220523151450-11.png]]
854
855 **Downlink Command:**
856
857 No downlink commands for feature
858
859 == 4.11 Print last few data entries. ==
860
861 Feature: Print the last few data entries
862
863 **AT Command: AT+PLDTA**
864
865 [[image:image-20220523151524-12.png]]
866
867 **Downlink Command:**
868
869 No downlink commands for feature
870
871 == 4.12 Clear Flash Record ==
872
873 Feature: Clear flash storage for data log feature.
874
875 **AT Command: AT+CLRDTA**
876
877 [[image:image-20220523151556-13.png]]
878
879 **Downlink Command: 0xA3**
880
881 * Example: 0xA301 ~/~/Same as AT+CLRDTA
882
883 = 5. Battery & How to replace =
884
885 == 5.1 Battery Type ==
886
887 LHT65N is equipped with a 2400mAH Li-MnO2 (CR17505) battery . The battery is an un-rechargeable battery with low discharge rate targeting for up to 8~~10 years use. This type of battery is commonly used in IoT devices for long-term running, such as water meters.
888
889 (((
890 The discharge curve is not linear so can’t simply use percentage to show the battery level. Below is the battery performance.
891 [[image:image-20220515075034-1.png||height="208" width="644"]]
892 )))
893
894 (((
895 The minimum Working Voltage for the LHT65N is ~~ 2.5v. When battery is lower than 2.6v, it is time to change the battery.
896
897 )))
898
899 == 5.2 Replace Battery ==
900
901 LHT65N has two screws on the back, Unscrew them, and changing the battery inside is ok. The battery is a general CR17450 battery. Any brand should be ok.
902
903 [[image:image-20220515075440-2.png||height="338" width="272"]][[image:image-20220515075625-3.png||height="193" width="257"]]
904
905 == 5.3 Battery Life Analyze ==
906
907 (((
908 Dragino battery-powered products are all run in Low Power mode. User can check the guideline from this link to calculate the estimated battery life:
909 https:~/~/www.dragino.com/downloads/downloads/LoRa_End_Node/Battery_Analyze/DRAGINO_Battery_Life_Guide.pdf
910 )))
911
912 = 6. Order Info =
913
914 (((
915 Part Number: (% style="color:#4f81bd" %)** LHT65N-XX**
916 )))
917
918 (((
919 (% style="color:#4f81bd" %)**XX **(%%): The default frequency band
920 )))
921
922 * (((
923 (% style="color:#4f81bd" %)** AS923**(%%): LoRaWAN AS923 band
924 )))
925 * (((
926 (% style="color:#4f81bd" %)** AU915**(%%): LoRaWAN AU915 band
927 )))
928 * (((
929 (% style="color:#4f81bd" %)** EU433**(%%): LoRaWAN EU433 band
930 )))
931 * (((
932 (% style="color:#4f81bd" %)** EU868**(%%): LoRaWAN EU868 band
933 )))
934 * (((
935 (% style="color:#4f81bd" %)** KR920**(%%): LoRaWAN KR920 band
936 )))
937 * (((
938 (% style="color:#4f81bd" %)** US915**(%%): LoRaWAN US915 band
939 )))
940 * (((
941 (% style="color:#4f81bd" %)** IN865**(%%): LoRaWAN IN865 band
942 )))
943 * (((
944 (% style="color:#4f81bd" %)** CN470**(%%): LoRaWAN CN470 band
945 )))
946
947 (((
948 (% style="color:#4f81bd" %)**YY**(%%): Sensor Accessories
949 )))
950
951 * (((
952 (% style="color:#4f81bd" %)**E3**(%%): External Temperature Probe
953 )))
954
955 = 7. Packing Info =
956
957 (((
958 **Package Includes**:
959 )))
960
961 * (((
962 LHT65N Temperature & Humidity Sensor x 1
963 )))
964 * (((
965 Program cable x 1
966 )))
967 * (((
968 Optional external sensor
969 )))
970
971 (((
972 **Dimension and weight**:
973 )))
974
975 * (((
976 Device Size:  13.5 x 7 x 3 cm
977 )))
978 * (((
979 Device Weight: 105g
980 )))
981 * (((
982 Package Size / pcs : 14.5 x 8 x 5 cm
983 )))
984 * (((
985 Weight / pcs : 170g
986 )))
987
988 = 8. FCC Warning =
989
990 (((
991 This device complies with part 15 of the FCC Rules.Operation is subject to the following two conditions:
992 )))
993
994 (((
995 (1) This device may not cause harmful interference;
996 )))
997
998 (((