Last modified by Kilight Cao on 2025/07/14 15:15

From version 46.1
edited by Xiaoye
on 2023/11/10 18:01
Change comment: There is no comment for this version
To version 47.1
edited by Xiaoye
on 2023/11/11 09:40
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -243,11 +243,18 @@
243 243  
244 244  
245 245  
246 -=== Step 7: Configure Modbus RTU Slave ===
246 +== Step 7: Configure Modbus RTU Slave ==
247 247  
248 -The gateway can as a Modbus RTU slave to running, the user can
248 +The gateway can as a Modbus RTU slave to run, the user can set a range of the register to write a sensor node uplink data.
249 249  
250 250  
251 +For example, there is a sensor node EUI is 70b3d57ed0051e22, the register start is 0xABCD and the register length is 14, which means the uplink data will be written to the register starting at 0xABCD register and the maximum write length not to exceed 14 registers.
252 +
253 +So the sensor node 70b3d57ed0051e22 uplink data will be written to the 0xABCD - 0xABE1 register.
254 +
255 +**Note: Since the length of the payload is the same for different sensor nodes if The length of the data is greater than the configuration length, the data will be replaced with FFFF.**
256 +
257 +
251 251  Enable Modbus Slave  ~-~--> Enable Slave
252 252  
253 253  Show Sensor History  ~-~--> See the sensor data log
... ... @@ -258,7 +258,7 @@
258 258  
259 259  Register Start  ~-~-->  The
260 260  
261 -Register Length  ~-~--> 
268 +Register Length  ~-~-->  
262 262  
263 263  [[image:image-20231110175420-12.png||height="504" width="1161"]]
264 264