Xiaoling 41.7 12 = **1. Introduction** =
Xiaoling 1.1 13
Xiaoling 57.6 14
Xiaoling 1.2 15 This article provide the examples for RS485-LN to connect to different type of RS485 sensors.
Xiaoling 1.1 16
Xiaoling 38.2 17
Xiaoling 41.7 18 == **1.1 Example 1: Connect to Leak relay and VFD** ==
Xiaoling 1.1 19
Xiaoling 57.6 20
Xiaoling 1.2 21 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to Relay and VFD and communicate with Mobile. The structure is like below:
Xiaoling 1.1 22
Xiaoling 10.2 23 [[image:image-20220527091852-1.png]]
Xiaoling 1.1 24
Xiaoling 1.2 25 Connection
Xiaoling 1.1 26
Xiaoling 1.18 27
Xiaoling 1.1 28
Xiaoling 10.2 29 [[image:image-20220527091942-2.png]](% style="display:none" %)
30
Xiaoling 1.2 31 Connection
Xiaoling 1.1 32
Xiaoling 10.2 33
Xiaoling 1.2 34 Related documents:
Xiaoling 1.1 35
Xiaoling 1.2 36 * [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/]] : System Structure
37 * [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/]] : Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code.
38 * [[Video Demo>>url:https://www.youtube.com/watch?v=TAFZ5eaf-MY&t=6s&ab_channel=XavierFlorensaBerenguer]]
Xiaoling 1.1 39
Xiaoling 41.7 40 == **1.2 Example 2: Connect to Pulse Counter** ==
Xiaoling 1.1 41
Xiaoling 57.7 42
Xiaoling 1.2 43 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to Pulse Counter and communicate with Mobile. This example and example 2 compose the structure for a farm IoT solution. The structure is like below:
Xiaoling 1.1 44
Xiaoling 57.7 45
Xiaoling 10.2 46 [[image:image-20220527092058-3.png]]
Xiaoling 1.1 47
Xiaoling 1.2 48 Connection
Xiaoling 1.1 49
Xiaoling 1.18 50
Xiaoling 41.11 51
Xiaoling 10.2 52 [[image:image-20220527092146-4.png]]
Xiaoling 1.2 53
54 Connection
55
Xiaoling 41.12 56
Xiaoling 57.7 57 * Configure Document: [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/]]
Xiaoling 1.2 58 * [[Dragino Solution in Farm>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/&file=Dragino%20on%20Farms.pptx]]
59
Xiaoling 41.7 60 == **1.3 Example3: Use RS485-LN with energy meters** ==
Xiaoling 1.2 61
Xiaoling 41.7 62 === **1.3.1 OverView** ===
Xiaoling 1.2 63
Xiaoling 57.8 64
Xiaoling 1.5 65 (((
Xiaoling 57.8 66 (% style="color:red" %)**Note**:The specifications of each energy meter are different, please refer to your own energy meter specifications.
Xiaoling 1.5 67 )))
Xiaoling 1.2 68
Xiaoling 1.5 69 (((
Xiaoling 1.2 70 This example describes a single-phase meter.This is the connection between the RS485-LN and the energy meter.
Xiaoling 1.5 71 )))
Xiaoling 1.2 72
Xiaoling 13.2 73 [[image:image-20220527092419-5.png]]
Xiaoling 1.2 74
75 Connection1
76
Xiaoling 13.2 77
Xiaoling 41.13 78
Xiaoling 1.19 79 (((
Xiaoling 57.8 80 **How to connect with Energy Meter:**
81
82
Xiaoling 1.19 83 )))
Xiaoling 1.2 84
Xiaoling 1.19 85 (((
Xiaoling 1.2 86 Follow the instructions of the electric energy meter to connect the phase line and the neutral line, and then connect 485A+ and 485B- to RS485A and RA485B of RS485-LN respectively.
Xiaoling 1.19 87 )))
Xiaoling 1.2 88
Xiaoling 1.19 89 (((
Xiaoling 1.2 90 The RS485-LN can be powered by 7 ~~ 24V DC power source. Connection as below
Xiaoling 1.19 91 )))
Xiaoling 1.2 92
Xiaoling 1.19 93 (((
Xiaoling 1.2 94 Power Source VIN to RS485-LN VIN+
Xiaoling 1.19 95 )))
Xiaoling 1.2 96
Xiaoling 1.19 97 (((
Xiaoling 1.2 98 Power Source GND to RS485-LN VIN-
Xiaoling 1.19 99 )))
Xiaoling 1.2 100
Xiaoling 1.19 101 (((
Xiaoling 1.2 102 Once there is power, the RS485-LN will be on.
Xiaoling 1.19 103 )))
Xiaoling 1.2 104
Xiaoling 13.2 105 [[image:image-20220527092514-6.png]]
Xiaoling 1.2 106
107 Connection2
108
109
Xiaoling 41.14 110
Xiaoling 20.2 111 [[image:image-20220527092555-7.png]]
Xiaoling 1.12 112
Xiaoling 1.2 113 Connection3
114
115
Xiaoling 41.7 116 === **1.3.2 How to use the parameters of the energy meter and MODBUS commands** ===
Xiaoling 1.2 117
Xiaoling 57.8 118
Xiaoling 1.7 119 If the user needs to read the parameters of the electric energy meter and use the modbus command,please refer to the appendix of the MODBUS communication protocol in the user manual of the energy meter.
Xiaoling 1.2 120
Xiaoling 51.2 121 [[image:image-20220601143257-10.png]]
Xiaoling 1.2 122
Xiaoling 20.2 123
Xiaoling 57.8 124 (% style="color:blue" %)**Example:**(%%)  AT+COMMAND1=01 03 00 00 00 01 84 0A
Xiaoling 1.2 125
126 * The first byte : slave address code (=001~247)
127 * The second byte : read register value function code
128 * 3rd and 4th bytes: start address of register to be read
129 * 5th and 6th bytes: Number of registers to read
130 * 7th and 8th bytes: CRC16 checksum from bytes 1 to 6.
131
Xiaoling 1.12 132 (((
Xiaoling 57.8 133
134
135
Xiaoling 1.2 136 How to parse the reading of the return command of the parameter:
137
Xiaoling 57.8 138 (% style="color:blue" %)**Example:**(%%) RETURN1:01 03 02 08 FD 7E 05
Xiaoling 1.8 139 )))
Xiaoling 1.2 140
141 * The first byte ARD: slave address code (=001~254)
142 * The second byte: Return to read function code
143 * 3rd byte: total number of bytes
144 * 4th~5th bytes: register data
145 * The 6th and 7th bytes: CRC16 checksum
146 * 08 FD is register data. Use short integer 16 bits to convert to decimal, get 2301, then 230.1V is the voltage.
147
Xiaoling 20.2 148 (% class="wikigeneratedid" %)
149 (((
150
Xiaoling 57.8 151
152
153
Xiaoling 20.2 154 )))
155
Xiaoling 41.2 156 === **1.3.3 How to configure RS485-LN and parse output commands** ===
Xiaoling 1.2 157
Xiaoling 57.8 158
Xiaoling 1.2 159 RS485-LN provides two configuration methods: AT COMMAND and DOWNLINK.
160
Xiaoling 20.2 161
Xiaoling 57.8 162 ==== **1.3.3.1 via AT COMMAND** ====
Xiaoling 1.2 163
164
Xiaoling 57.8 165 First, we can use (% style="color:blue" %)**AT+CFGDEV**(%%) to get the return value, and we can also judge whether the input parameters are correct.
166
Xiaoling 1.8 167 (((
Xiaoling 1.2 168 If the configured parameters and commands are incorrect, the return value is not obtained.
Xiaoling 1.8 169 )))
Xiaoling 1.2 170
Xiaoling 50.2 171 [[image:image-20220601143201-9.png]]
Xiaoling 1.2 172
Xiaoling 1.12 173 AT COMMAND
Xiaoling 1.2 174
Xiaoling 20.2 175
Xiaoling 1.8 176 (% class="box infomessage" %)
177 (((
Xiaoling 57.8 178 **AT+DATACUTx **:  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
Xiaoling 1.8 179 )))
Xiaoling 1.2 180
Xiaoling 41.15 181 a:  length for the return of AT+COMMAND
Xiaoling 1.2 182
Xiaoling 41.15 183 b: 1: grab valid value by byte, max 6 bytes;  2: grab valid value by bytes section, max 3 sections.
Xiaoling 1.2 184
Xiaoling 41.15 185 c:  define the position for valid value.
Xiaoling 1.2 186
Xiaoling 50.2 187 [[image:image-20220601143115-8.png]]
Xiaoling 1.2 188
189 AT COMMAND
190
Xiaoling 20.2 191
Xiaoling 41.15 192
Xiaoling 1.2 193 PAYLOAD is available after the valid value is intercepted.
194
Xiaoling 1.8 195
Xiaoling 48.2 196 [[image:image-20220601143046-7.png]]
Xiaoling 1.2 197
198 AT COMMAND
199
Xiaoling 20.2 200
Xiaoling 41.16 201
Xiaoling 1.2 202 You can get configured PAYLOAD on TTN.
203
Xiaoling 52.2 204 [[image:image-20220601143519-1.png]]
Xiaoling 1.8 205
Xiaoling 1.12 206 (((
Xiaoling 1.2 207 AT COMMAND
Xiaoling 1.12 208 )))
Xiaoling 1.2 209
Xiaoling 1.12 210 (((
Xiaoling 1.13 211
212 )))
213
214 (((
Xiaoling 57.8 215 (% style="color:blue" %)**Example**:
Xiaoling 39.3 216
Xiaoling 57.9 217 CMD1: Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
Xiaoling 1.12 218 )))
Xiaoling 1.2 219
Xiaoling 1.12 220 (((
Xiaoling 57.8 221 RETURN1: 01 03 02 00 02 39 85 00 00(return data)
Xiaoling 1.12 222 )))
Xiaoling 1.2 223
Xiaoling 1.12 224 (((
Xiaoling 57.8 225 AT+DATACUT1: 9,1,4+5+6+7 Take the return value 00 02 39 85 as the valid value of reading current data and used to splice payload.
Xiaoling 39.3 226
227
Xiaoling 1.12 228 )))
Xiaoling 1.2 229
Xiaoling 1.12 230 (((
Xiaoling 57.8 231 CMD2: Read voltage data with MODBUS command. address: 0x00 AT+COMMAND2= 01 03 00 00 00 01,1
Xiaoling 1.12 232 )))
Xiaoling 1.2 233
Xiaoling 1.12 234 (((
Xiaoling 57.8 235 RETURN2: 01 03 02 08 DC BE 1D(return data)
Xiaoling 1.12 236 )))
Xiaoling 1.2 237
Xiaoling 1.12 238 (((
Xiaoling 57.8 239 AT+DATACUT2: 7,1,4+5 Take the return value 08 DC as the valid value of reading voltage data and used to splice payload.
Xiaoling 39.3 240
241
Xiaoling 1.12 242 )))
Xiaoling 1.2 243
Xiaoling 1.12 244 (((
Xiaoling 57.8 245 CMD3: Read total active energy data with MODBUS command. address: 0x0031 AT+COMMAND3= 01 03 00 31 00 02,1
Xiaoling 1.12 246 )))
Xiaoling 1.2 247
Xiaoling 1.12 248 (((
Xiaoling 57.9 249 RETURN3: 01 03 04 00 00 00 44 FA 00(return data)
Xiaoling 1.12 250 )))
Xiaoling 1.2 251
Xiaoling 1.12 252 (((
Xiaoling 57.8 253 AT+DATACUT3: 9,1,4+5+6+7 Take the return value 00 00 00 44 as the valid value of reading total active energy data and used to splice payload.
Xiaoling 1.12 254 )))
Xiaoling 1.2 255
Xiaoling 1.12 256 (((
Xiaoling 57.8 257 Payload: 01 00 02 39 85 08 DC 00 00 00 44
Xiaoling 1.12 258 )))
Xiaoling 1.2 259
Xiaoling 47.2 260 [[image:image-20220601142936-6.png]]
Xiaoling 1.2 261
262 AT COMMAND
263
Xiaoling 20.2 264
Xiaoling 21.2 265 (% style="color:#4f81bd" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
Xiaoling 1.2 266
Xiaoling 41.17 267
Xiaoling 53.2 268 [[image:image-20220601143642-2.png]]
Xiaoling 1.8 269
Xiaoling 1.2 270 AT COMMAND
271
272
Xiaoling 41.2 273 ==== **1.3.3.2 via LoRaWAN DOWNLINK** ====
Xiaoling 1.8 274
Xiaoling 57.8 275
Xiaoling 21.2 276 [[image:image-20220527093358-15.png]]
Xiaoling 1.2 277
Xiaoling 1.9 278 (((
Xiaoling 1.2 279 DOWNLINK
Xiaoling 1.9 280 )))
Xiaoling 1.2 281
Xiaoling 1.9 282 (((
283
284 )))
285
286 (((
Xiaoling 39.4 287 (% style="color:#4f81bd" %)**Type Code 0xAF**
Xiaoling 1.9 288 )))
Xiaoling 1.2 289
Xiaoling 1.9 290 (((
Xiaoling 4.3 291 (% class="box infomessage" %)
292 (((
Xiaoling 1.2 293 0xAF downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
Xiaoling 1.9 294 )))
Xiaoling 4.3 295 )))
Xiaoling 1.2 296
Xiaoling 1.9 297 (((
Xiaoling 57.11 298 (% style="color:red" %)Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
Xiaoling 1.9 299 )))
Xiaoling 1.2 300
Xiaoling 1.9 301 (((
Xiaoling 1.2 302 Format: AF MM NN LL XX XX XX XX YY
Xiaoling 1.9 303 )))
Xiaoling 1.2 304
Xiaoling 1.9 305 (((
Xiaoling 1.2 306 Where:
Xiaoling 1.9 307 )))
Xiaoling 1.2 308
Xiaoling 1.9 309 (((
Xiaoling 1.2 310 MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
Xiaoling 1.9 311 )))
Xiaoling 1.2 312
Xiaoling 1.9 313 (((
Xiaoling 1.2 314 NN: 0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
Xiaoling 1.9 315 )))
Xiaoling 1.2 316
Xiaoling 1.9 317 (((
Xiaoling 1.2 318 LL: The length of AT+COMMAND or AT+DATACUT command
Xiaoling 1.9 319 )))
Xiaoling 1.2 320
Xiaoling 1.9 321 (((
Xiaoling 1.2 322 XX XX XX XX: AT+COMMAND or AT+DATACUT command
Xiaoling 1.9 323 )))
Xiaoling 1.2 324
Xiaoling 1.9 325 (((
Xiaoling 1.2 326 YY: If YY=0, RS485-LN will execute the downlink command without uplink; if YY=1, RS485-LN
Xiaoling 1.9 327 )))
Xiaoling 1.2 328
Xiaoling 1.9 329 (((
Xiaoling 1.2 330 will execute an uplink after got this command.
Xiaoling 1.9 331 )))
Xiaoling 1.2 332
Xiaoling 1.9 333 (((
Xiaoling 41.18 334
335
Xiaoling 57.11 336 (% style="color:blue" %)**Example:**
Xiaoling 1.9 337 )))
Xiaoling 1.2 338
Xiaoling 1.9 339 (((
Xiaoling 39.4 340 **AF 03 01 06 0A 05 00 04 00 01 00**: Same as AT+COMMAND3=0A 05 00 04 00 01,1
Xiaoling 1.9 341 )))
Xiaoling 1.2 342
Xiaoling 57.2 343 [[image:image-20220601144149-6.png]]
Xiaoling 1.2 344
345 DOWNLINK
346
Xiaoling 1.8 347
Xiaoling 41.19 348
Xiaoling 54.2 349 [[image:image-20220601143803-3.png]]
Xiaoling 1.2 350
351 DOWNLINK
352
Xiaoling 1.8 353
Xiaoling 41.20 354
Xiaoling 57.2 355 [[image:image-20220601144053-5.png]]
Xiaoling 1.2 356
357 DOWNLINK
358
Xiaoling 1.8 359
Xiaoling 41.21 360
Xiaoling 55.2 361 [[image:image-20220601143921-4.png]]
Xiaoling 1.2 362
363 DOWNLINK
364
Xiaoling 1.15 365
Xiaoling 41.22 366
Xiaoling 46.2 367 [[image:image-20220601142805-5.png]]
Xiaoling 1.2 368
369 DOWNLINK
370
371
Xiaoling 41.2 372 === **1.3.4 How to configure and output commands for RS485 to USB** ===
Xiaoling 1.2 373
Xiaoling 1.13 374 (((
Xiaoling 1.2 375 This step is not necessary, it is just to show how to use a normal RS485 to USB adapter to connect to the meter to check the input and output. This can be used to test the connection and RS485 command of the meter without RS485-LN.
Xiaoling 1.13 376 )))
Xiaoling 1.2 377
Xiaoling 1.13 378 (((
Xiaoling 1.2 379 First, connect the A+ and A- of the USB to the 485 A and 485 B of the energy meter.
Xiaoling 1.13 380 )))
Xiaoling 1.2 381
Xiaoling 1.13 382 (((
Xiaoling 1.2 383 Open the serial port debugging, set the send and receive to HEX.
Xiaoling 1.13 384 )))
Xiaoling 1.2 385
Xiaoling 1.13 386 (((
Xiaoling 1.2 387 Baud rate: 9600
Xiaoling 1.13 388 )))
Xiaoling 1.2 389
Xiaoling 1.13 390 (((
Xiaoling 1.2 391 check digit: Even
Xiaoling 57.11 392
393
Xiaoling 1.13 394 )))
Xiaoling 1.2 395
Xiaoling 27.2 396 [[image:image-20220527093708-21.png]]
Xiaoling 1.2 397
398 USB
399
Xiaoling 1.13 400
Xiaoling 41.23 401
Xiaoling 29.2 402 [[image:image-20220527093747-22.png]]
Xiaoling 1.2 403
404 USB
405
Xiaoling 1.13 406
Xiaoling 41.24 407
Xiaoling 1.13 408 (((
Xiaoling 1.2 409 The configuration command is consistent with the AT command, input the hexadecimal command directly into the serial port, and the serial port will output the command.
Xiaoling 57.11 410
411
Xiaoling 1.13 412 )))
Xiaoling 1.2 413
Xiaoling 1.13 414 (((
Xiaoling 57.11 415 (% style="color:blue" %)**Example:**  (%%)input:01 03 00 31 00 02 95 c4
Xiaoling 1.13 416 )))
Xiaoling 1.2 417
Xiaoling 1.13 418 (((
Xiaoling 4.6 419 output:01 03 04 00 00 00 42 7A 02
Xiaoling 57.11 420
421
Xiaoling 1.13 422 )))
Xiaoling 1.2 423
Xiaoling 29.2 424 [[image:image-20220527093821-23.png]]
Xiaoling 1.2 425
426 USB
427
Xiaoling 29.2 428
Xiaoling 41.2 429 === **1.3.5 How to configure multiple devices and modify device addresses** ===
Xiaoling 1.2 430
Xiaoling 57.11 431
Xiaoling 1.2 432 If users need to read the parameters of multiple energy meters, they need to modify the device address, because the default device address of each energy meter is 01.
433
Xiaoling 1.14 434 (((
Xiaoling 1.15 435 (((
Xiaoling 1.2 436 Set the device address according to the parameters in the appendix of the MODBUS communication protocol.
Xiaoling 1.14 437 )))
Xiaoling 1.15 438 )))
Xiaoling 1.2 439
Xiaoling 42.2 440 [[image:image-20220601142044-1.png]]
Xiaoling 1.2 441
Xiaoling 30.2 442
Xiaoling 57.11 443 (% style="color:blue" %)**Example**(%%): These two meters are examples of setting parameters and device addresses.
Xiaoling 1.2 444
Xiaoling 31.2 445 [[image:image-20220527093950-25.png]]
Xiaoling 1.2 446
Xiaoling 57.4 447
Xiaoling 32.2 448 [[image:image-20220527094028-26.png]]
Xiaoling 1.2 449
Xiaoling 1.14 450 (((
Xiaoling 1.16 451 (((
Xiaoling 1.2 452 First of all, since the default device address of the energy meter is 01, the configuration of two energy meters will conflict, so we first connect an energy meter and configure the device address.
Xiaoling 1.14 453 )))
Xiaoling 1.16 454 )))
Xiaoling 1.2 455
Xiaoling 1.14 456 (((
Xiaoling 1.16 457 (((
Xiaoling 1.2 458 We can use AT+CFGDEV to set the device address.
Xiaoling 1.14 459 )))
Xiaoling 1.16 460 )))
Xiaoling 1.2 461
Xiaoling 1.14 462 (((
Xiaoling 1.16 463 (((
Xiaoling 1.2 464 We modify the device address 01 of the first energy meter to 02.
Xiaoling 1.14 465 )))
Xiaoling 1.16 466 )))
Xiaoling 1.2 467
Xiaoling 43.2 468 [[image:image-20220601142354-2.png]]
Xiaoling 1.2 469
Xiaoling 35.2 470 (% class="box infomessage" %)
471 (((
472 **AT+CFGDEV:01 10 00 61 00 01 02 00 02,1**
473 )))
Xiaoling 1.2 474
475 * 01:device adaress
476
477 * 10:function code
478
479 * 00 61:Register address
480
481 * 00 01:Number of Registers
482
483 * 02:Number of bytes
484
485 * 00 02:Modified device address
486
487 * 1:Check code
488
489 The device address setting of the energy meter is complete.
490
491 Another energy meter is a single active energy meter with a floating-point format.
492
493 Its default device address is 01, and the following are the parameters for configuring two energy meters.
494
Xiaoling 44.2 495 [[image:image-20220601142452-3.png]]
Xiaoling 1.2 496
497
Xiaoling 45.2 498 [[image:image-20220601142607-4.png]]
Xiaoling 35.2 499
Xiaoling 39.5 500 **PAYLOAD:01 08 DF 43 62**
Xiaoling 1.2 501
502 * 08 DF is the valid value of the meter with device address 02.
503 * 43 62 is the valid value of the meter with device address 01.
504
505 == 1.4 Example 4: Circuit Breaker Remote Open Close ==
506
507 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to SCHNEIDER SMART and Monitor and control your cabinet remotely with no wires and with Dragino RS485-LN LoRaWAN technology. The structure is like below:
508
Xiaoling 36.2 509 [[image:image-20220527094330-30.png]]
Xiaoling 1.2 510
511 Connection
512
513 * [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/]] : Configure Documen
514
515 == 1.5 Example 5: SEM Three Energy Meter with RS485-BL or RS485-LN ==
516
517 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-BL to connect to SEM Three Energy Meter and send the data to mobile phone for remote minitor. The structure is like below:
518
519 * [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf]] : Configure Document For RS485-BL
520
521 * [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf]] : Configure Document for RS485-LN
522
523 == 1.6 Example 6:CEM C31 485-T1-MID Energy Meter with RS485-LN ==
524
525 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to CEM C31 485-T1-MID and send the data for remote minitor. The structure is like below:
526
527 * [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf]] : Configure Document For RS485-LN
528
529 == 1.7 Example 7:Schneider Electric PLC M221 with RS485-BL ==
530
Xiaoling 38.1 531 [[image:image-20220527094556-31.png]]
Xiaoling 1.2 532
533 Network Structure
534
535 * [[Reference Instruction>>url:https://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Schneider%20Electric%20PLC/]]