Xiaoling 1.2 1 = 1. Introduction =
Xiaoling 1.1 2
Xiaoling 1.2 3 This article provide the examples for RS485-LN to connect to different type of RS485 sensors.
Xiaoling 1.1 4
Xiaoling 1.2 5 == 1.1 Example 1: Connect to Leak relay and VFD ==
Xiaoling 1.1 6
Xiaoling 1.2 7 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to Relay and VFD and communicate with Mobile. The structure is like below:
Xiaoling 1.1 8
Xiaoling 1.3 9 [[image:https://wiki.dragino.com/images/thumb/5/5c/RS485_01.png/600px-RS485_01.png||height="297" width="534"]]
Xiaoling 1.1 10
Xiaoling 1.2 11 Connection
Xiaoling 1.1 12
Xiaoling 1.3 13 [[image:https://wiki.dragino.com/images/thumb/f/f2/RS485_02.png/600px-RS485_02.png||height="743" width="528"]](% style="display:none" %)
Xiaoling 1.1 14
Xiaoling 1.2 15 Connection
Xiaoling 1.1 16
Xiaoling 1.2 17 Related documents:
Xiaoling 1.1 18
Xiaoling 1.2 19 * [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/]] : System Structure
20 * [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/]] : Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code.
21 * [[Video Demo>>url:https://www.youtube.com/watch?v=TAFZ5eaf-MY&t=6s&ab_channel=XavierFlorensaBerenguer]]
Xiaoling 1.1 22
Xiaoling 1.2 23 == 1.2 Example 2: Connect to Pulse Counter ==
Xiaoling 1.1 24
Xiaoling 1.2 25 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to Pulse Counter and communicate with Mobile. This example and example 2 compose the structure for a farm IoT solution. The structure is like below:
Xiaoling 1.1 26
Xiaoling 1.2 27 [[image:https://wiki.dragino.com/images/thumb/3/34/RS485_02_1.png/600px-RS485_02_1.png||height="364" width="600"]]
Xiaoling 1.1 28
Xiaoling 1.2 29 Connection
Xiaoling 1.1 30
Xiaoling 1.2 31 [[image:https://wiki.dragino.com/images/thumb/5/5f/RS485_02_2.png/600px-RS485_02_2.png||height="337" width="600"]]
32
33 Connection
34
35 * [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/]] : Configure Document
36 * [[Dragino Solution in Farm>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/&file=Dragino%20on%20Farms.pptx]]
37
38 == 1.3 Example3: Use RS485-LN with energy meters ==
39
40 === 1.3.1 OverView ===
41
Xiaoling 1.5 42 (((
Xiaoling 1.6 43 **Note**:The specifications of each energy meter are different, please refer to your own energy meter specifications.
Xiaoling 1.5 44 )))
Xiaoling 1.2 45
Xiaoling 1.5 46 (((
Xiaoling 1.2 47 This example describes a single-phase meter.This is the connection between the RS485-LN and the energy meter.
Xiaoling 1.5 48 )))
Xiaoling 1.2 49
Xiaoling 1.11 50 [[image:https://wiki.dragino.com/images/thumb/f/f4/Meter1.jpg/600px-Meter1.jpg||height="726" width="545"]]
Xiaoling 1.2 51
52 Connection1
53
54 How to connect with Energy Meter:
55
56 Follow the instructions of the electric energy meter to connect the phase line and the neutral line, and then connect 485A+ and 485B- to RS485A and RA485B of RS485-LN respectively.
57
58 The RS485-LN can be powered by 7 ~~ 24V DC power source. Connection as below
59
60 Power Source VIN to RS485-LN VIN+
61
62 Power Source GND to RS485-LN VIN-
63
64 Once there is power, the RS485-LN will be on.
65
Xiaoling 1.11 66 [[image:https://wiki.dragino.com/images/thumb/1/15/Meter2.jpg/600px-Meter2.jpg||height="433" width="577"]]
Xiaoling 1.2 67
68 Connection2
69
70
Xiaoling 1.15 71 [[image:https://wiki.dragino.com/images/thumb/a/a5/Meter3.jpg/600px-Meter3.jpg||height="712" width="534"]]
Xiaoling 1.12 72
Xiaoling 1.2 73 Connection3
74
75
76 === 1.3.2 How to use the parameters of the energy meter and MODBUS commands ===
77
Xiaoling 1.7 78 If the user needs to read the parameters of the electric energy meter and use the modbus command,please refer to the appendix of the MODBUS communication protocol in the user manual of the energy meter.
Xiaoling 1.2 79
80 [[image:https://wiki.dragino.com/images/thumb/3/35/Meter4.png/600px-Meter4.png||alt="Meter4.png" height="193" width="600"]]
81
Xiaoling 1.8 82 (% class="box infomessage" %)
83 (((
Xiaoling 1.2 84 Example:AT+COMMAND1=01 03 00 00 00 01 84 0A
Xiaoling 1.8 85 )))
Xiaoling 1.2 86
87 * The first byte : slave address code (=001~247)
88 * The second byte : read register value function code
89 * 3rd and 4th bytes: start address of register to be read
90 * 5th and 6th bytes: Number of registers to read
91 * 7th and 8th bytes: CRC16 checksum from bytes 1 to 6.
92
Xiaoling 1.12 93 (((
Xiaoling 1.2 94 How to parse the reading of the return command of the parameter:
Xiaoling 1.12 95 )))
Xiaoling 1.2 96
Xiaoling 1.8 97 (% class="box infomessage" %)
98 (((
Xiaoling 1.2 99 Example:RETURN1:01 03 02 08 FD 7E 05
Xiaoling 1.8 100 )))
Xiaoling 1.2 101
102 * The first byte ARD: slave address code (=001~254)
103 * The second byte: Return to read function code
104 * 3rd byte: total number of bytes
105 * 4th~5th bytes: register data
106 * The 6th and 7th bytes: CRC16 checksum
107 * 08 FD is register data. Use short integer 16 bits to convert to decimal, get 2301, then 230.1V is the voltage.
108
109 === 1.3.3 How to configure RS485-LN and parse output commands ===
110
111 RS485-LN provides two configuration methods: AT COMMAND and DOWNLINK.
112
Xiaoling 1.8 113 ==== 1.3.3.1 via AT COMMAND: ====
Xiaoling 1.2 114
Xiaoling 1.8 115 First, we can use **AT+CFGDEV** to get the return value, and we can also judge whether the input parameters are correct.
Xiaoling 1.2 116
Xiaoling 1.8 117 (((
Xiaoling 1.2 118 If the configured parameters and commands are incorrect, the return value is not obtained.
Xiaoling 1.8 119 )))
Xiaoling 1.2 120
121 [[image:https://wiki.dragino.com/images/b/bc/AT_COMMAND1.png||height="358" width="456"]]
122
Xiaoling 1.12 123 AT COMMAND
Xiaoling 1.2 124
Xiaoling 1.8 125 (% class="box infomessage" %)
126 (((
Xiaoling 1.2 127 AT+DATACUTx : This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
Xiaoling 1.8 128 )))
Xiaoling 1.2 129
130 a: length for the return of AT+COMMAND
131
132 b:1: grab valid value by byte, max 6 bytes. 2: grab valid value by bytes section, max 3 sections.
133
134 c: define the position for valid value.
135
136 [[image:https://wiki.dragino.com/images/7/7d/AT_COMMAND2.png||height="278" width="477"]]
137
138 AT COMMAND
139
140 PAYLOAD is available after the valid value is intercepted.
141
Xiaoling 1.8 142
Xiaoling 1.2 143 [[image:https://wiki.dragino.com/images/3/3a/AT_COMMAND4.png||height="219" width="576"]]
144
145 AT COMMAND
146
147 You can get configured PAYLOAD on TTN.
148
Xiaoling 1.8 149
Xiaoling 1.2 150 [[image:https://wiki.dragino.com/images/thumb/c/c2/AT_COMMAND3.png/600px-AT_COMMAND3.png||height="138" width="600"]]
151
Xiaoling 1.12 152 (((
Xiaoling 1.2 153 AT COMMAND
Xiaoling 1.12 154 )))
Xiaoling 1.2 155
Xiaoling 1.12 156 (((
Xiaoling 1.13 157
158 )))
159
160 (((
Xiaoling 1.8 161 **Example**: CMD1:Read current data with MODBUS command. address:0x03 AT+COMMAND1= 01 03 00 03 00 01,1
Xiaoling 1.12 162 )))
Xiaoling 1.2 163
Xiaoling 1.12 164 (((
Xiaoling 1.2 165 RETURN1:01 03 02 00 02 39 85 00 00(return data)
Xiaoling 1.12 166 )))
Xiaoling 1.2 167
Xiaoling 1.12 168 (((
Xiaoling 1.2 169 AT+DATACUT1:9,1,4+5+6+7 Take the return value 00 02 39 85 as the valid value of reading current data and used to splice payload.
Xiaoling 1.12 170 )))
Xiaoling 1.2 171
Xiaoling 1.12 172 (((
Xiaoling 1.2 173 CMD2:Read voltage data with MODBUS command. address:0x00 AT+COMMAND2= 01 03 00 00 00 01,1
Xiaoling 1.12 174 )))
Xiaoling 1.2 175
Xiaoling 1.12 176 (((
Xiaoling 1.2 177 RETURN2:01 03 02 08 DC BE 1D(return data)
Xiaoling 1.12 178 )))
Xiaoling 1.2 179
Xiaoling 1.12 180 (((
Xiaoling 1.2 181 AT+DATACUT2:7,1,4+5 Take the return value 08 DC as the valid value of reading voltage data and used to splice payload.
Xiaoling 1.12 182 )))
Xiaoling 1.2 183
Xiaoling 1.12 184 (((
Xiaoling 1.2 185 CMD3:Read total active energy data with MODBUS command. address:0x0031 AT+COMMAND3= 01 03 00 31 00 02,1
Xiaoling 1.12 186 )))
Xiaoling 1.2 187
Xiaoling 1.12 188 (((
Xiaoling 1.2 189 RETURN3:01 03 04 00 00 00 44 FA 00(return data)
Xiaoling 1.12 190 )))
Xiaoling 1.2 191
Xiaoling 1.12 192 (((
Xiaoling 1.2 193 AT+DATACUT3:9,1,4+5+6+7 Take the return value 00 00 00 44 as the valid value of reading total active energy data and used to splice payload.
Xiaoling 1.12 194 )))
Xiaoling 1.2 195
Xiaoling 1.12 196 (((
Xiaoling 1.2 197 Payload:01 00 02 39 85 08 DC 00 00 00 44
Xiaoling 1.12 198 )))
Xiaoling 1.2 199
200 [[image:https://wiki.dragino.com/images/thumb/9/9b/AT_COMMAND10.png/600px-AT_COMMAND10.png||height="278" width="600"]]
201
202 AT COMMAND
203
204 01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.
205
Xiaoling 1.8 206
Xiaoling 1.2 207 [[~[~[image:https://wiki.dragino.com/images/thumb/b/b8/AT_COMMAND11.png/600px-AT_COMMAND11.png~|~|height="271" width="600"~]~]>>url:https://wiki.dragino.com/index.php/File:AT_COMMAND11.png]]
208
209 AT COMMAND
210
211
Xiaoling 1.8 212 ==== 1.3.3.2 via LoRaWAN DOWNLINK ====
213
Xiaoling 1.2 214 [[image:https://wiki.dragino.com/images/thumb/f/fc/DOWNLINK_METER1.png/600px-DOWNLINK_METER1.png||height="423" width="600"]]
215
Xiaoling 1.9 216 (((
Xiaoling 1.2 217 DOWNLINK
Xiaoling 1.9 218 )))
Xiaoling 1.2 219
Xiaoling 1.9 220 (((
221
222 )))
223
224 (((
Xiaoling 1.2 225 Type Code 0xAF
Xiaoling 1.9 226 )))
Xiaoling 1.2 227
Xiaoling 1.9 228 (((
Xiaoling 1.2 229 0xAF downlink command can be used to set AT+COMMANDx or AT+DATACUTx.
Xiaoling 1.9 230 )))
Xiaoling 1.2 231
Xiaoling 1.9 232 (((
Xiaoling 1.2 233 Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
Xiaoling 1.9 234 )))
Xiaoling 1.2 235
Xiaoling 1.9 236 (((
Xiaoling 1.2 237 Format: AF MM NN LL XX XX XX XX YY
Xiaoling 1.9 238 )))
Xiaoling 1.2 239
Xiaoling 1.9 240 (((
Xiaoling 1.2 241 Where:
Xiaoling 1.9 242 )))
Xiaoling 1.2 243
Xiaoling 1.9 244 (((
Xiaoling 1.2 245 MM: the ATCOMMAND or AT+DATACUT to be set. Value from 01 ~~ 0F,
Xiaoling 1.9 246 )))
Xiaoling 1.2 247
Xiaoling 1.9 248 (((
Xiaoling 1.2 249 NN: 0: no CRC; 1: add CRC-16/MODBUS ; 2: set the AT+DATACUT value.
Xiaoling 1.9 250 )))
Xiaoling 1.2 251
Xiaoling 1.9 252 (((
Xiaoling 1.2 253 LL: The length of AT+COMMAND or AT+DATACUT command
Xiaoling 1.9 254 )))
Xiaoling 1.2 255
Xiaoling 1.9 256 (((
Xiaoling 1.2 257 XX XX XX XX: AT+COMMAND or AT+DATACUT command
Xiaoling 1.9 258 )))
Xiaoling 1.2 259
Xiaoling 1.9 260 (((
Xiaoling 1.2 261 YY: If YY=0, RS485-LN will execute the downlink command without uplink; if YY=1, RS485-LN
Xiaoling 1.9 262 )))
Xiaoling 1.2 263
Xiaoling 1.9 264 (((
Xiaoling 1.2 265 will execute an uplink after got this command.
Xiaoling 1.9 266 )))
Xiaoling 1.2 267
Xiaoling 1.9 268 (((
Xiaoling 1.2 269 Example:
Xiaoling 1.9 270 )))
Xiaoling 1.2 271
Xiaoling 1.9 272 (((
Xiaoling 1.2 273 AF 03 01 06 0A 05 00 04 00 01 00: Same as AT+COMMAND3=0A 05 00 04 00 01,1
Xiaoling 1.9 274 )))
Xiaoling 1.2 275
276 [[image:https://wiki.dragino.com/images/thumb/4/45/DOWNLINK_METER2.png/600px-DOWNLINK_METER2.png||height="208" width="600"]]
277
278 DOWNLINK
279
Xiaoling 1.8 280
Xiaoling 1.2 281 [[~[~[image:https://wiki.dragino.com/images/thumb/2/20/DOWNLINK_METER3.png/600px-DOWNLINK_METER3.png~|~|height="105" width="600"~]~]>>url:https://wiki.dragino.com/index.php/File:DOWNLINK_METER3.png]]
282
283 DOWNLINK
284
Xiaoling 1.8 285
Xiaoling 1.2 286 [[image:https://wiki.dragino.com/images/thumb/2/27/DOWNLINK_METER4.png/600px-DOWNLINK_METER4.png||height="210" width="600"]]
287
288 DOWNLINK
289
Xiaoling 1.8 290
Xiaoling 1.2 291 [[~[~[image:https://wiki.dragino.com/images/thumb/3/39/DOWNLINK_METER5.png/600px-DOWNLINK_METER5.png~|~|height="176" width="600"~]~]>>url:https://wiki.dragino.com/index.php/File:DOWNLINK_METER5.png]]
292
293 DOWNLINK
294
Xiaoling 1.15 295
Xiaoling 1.2 296 [[image:https://wiki.dragino.com/images/thumb/a/a2/DOWNLINK_METER6.png/600px-DOWNLINK_METER6.png||height="365" width="600"]]
297
298 DOWNLINK
299
300
301 === 1.3.4 How to configure and output commands for RS485 to USB ===
302
Xiaoling 1.13 303 (((
Xiaoling 1.2 304 This step is not necessary, it is just to show how to use a normal RS485 to USB adapter to connect to the meter to check the input and output. This can be used to test the connection and RS485 command of the meter without RS485-LN.
Xiaoling 1.13 305 )))
Xiaoling 1.2 306
Xiaoling 1.13 307 (((
Xiaoling 1.2 308 First, connect the A+ and A- of the USB to the 485 A and 485 B of the energy meter.
Xiaoling 1.13 309 )))
Xiaoling 1.2 310
Xiaoling 1.13 311 (((
Xiaoling 1.2 312 Open the serial port debugging, set the send and receive to HEX.
Xiaoling 1.13 313 )))
Xiaoling 1.2 314
Xiaoling 1.13 315 (((
Xiaoling 1.2 316 Baud rate: 9600
Xiaoling 1.13 317 )))
Xiaoling 1.2 318
Xiaoling 1.13 319 (((
Xiaoling 1.2 320 check digit: Even
Xiaoling 1.13 321 )))
Xiaoling 1.2 322
Xiaoling 1.15 323 [[image:https://wiki.dragino.com/images/thumb/8/8f/Usb_meter2.jpg/600px-Usb_meter2.jpg||height="725" width="544"]]
Xiaoling 1.2 324
325 USB
326
Xiaoling 1.13 327
Xiaoling 1.15 328 [[image:https://wiki.dragino.com/images/thumb/6/62/Usb_meter1.jpg/600px-Usb_meter1.jpg||height="728" width="546"]]
Xiaoling 1.2 329
330 USB
331
Xiaoling 1.13 332
333 (((
Xiaoling 1.2 334 The configuration command is consistent with the AT command, input the hexadecimal command directly into the serial port, and the serial port will output the command.
Xiaoling 1.13 335 )))
Xiaoling 1.2 336
Xiaoling 1.13 337 (((
338 **Example:**  input:01 03 00 31 00 02 95 c4
339 )))
Xiaoling 1.2 340
Xiaoling 1.13 341 (((
342 output:01 03 04 00 00 00 42 7A 02
343 )))
Xiaoling 1.2 344
345 [[image:https://wiki.dragino.com/images/thumb/b/b3/Usb_meter3.jpg/600px-Usb_meter3.jpg||height="466" width="600"]]
346
347 USB
348
349 === 1.3.5 How to configure multiple devices and modify device addresses ===
350
351 If users need to read the parameters of multiple energy meters, they need to modify the device address, because the default device address of each energy meter is 01.
352
Xiaoling 1.14 353 (((
Xiaoling 1.15 354 (((
Xiaoling 1.2 355 Set the device address according to the parameters in the appendix of the MODBUS communication protocol.
Xiaoling 1.14 356 )))
Xiaoling 1.15 357 )))
Xiaoling 1.2 358
359 [[image:https://wiki.dragino.com/images/thumb/1/1f/Double_meter3.png/600px-Double_meter3.png||alt="Double meter3.png" height="83" width="600"]]
360
Xiaoling 1.16 361 **Example**:These two meters are examples of setting parameters and device addresses.
Xiaoling 1.2 362
Xiaoling 1.16 363 [[image:https://wiki.dragino.com/images/thumb/e/ee/Double_meter1.jpg/600px-Double_meter1.jpg||alt="Double meter1.jpg" height="737" width="553"]]
Xiaoling 1.2 364
Xiaoling 1.14 365 [[image:https://wiki.dragino.com/images/thumb/7/72/Double_meter2.jpg/600px-Double_meter2.jpg||alt="Double meter2.jpg" height="733" width="550"]]
Xiaoling 1.2 366
Xiaoling 1.14 367 (((
Xiaoling 1.16 368 (((
Xiaoling 1.2 369 First of all, since the default device address of the energy meter is 01, the configuration of two energy meters will conflict, so we first connect an energy meter and configure the device address.
Xiaoling 1.14 370 )))
Xiaoling 1.16 371 )))
Xiaoling 1.2 372
Xiaoling 1.14 373 (((
Xiaoling 1.16 374 (((
Xiaoling 1.2 375 We can use AT+CFGDEV to set the device address.
Xiaoling 1.14 376 )))
Xiaoling 1.16 377 )))
Xiaoling 1.2 378
Xiaoling 1.14 379 (((
Xiaoling 1.16 380 (((
Xiaoling 1.2 381 We modify the device address 01 of the first energy meter to 02.
Xiaoling 1.14 382 )))
Xiaoling 1.16 383 )))
Xiaoling 1.2 384
385 [[image:https://wiki.dragino.com/images/6/6b/Double_meter4.png||alt="Double meter4.png" height="141" width="456"]]
386
387 AT+CFGDEV:01 10 00 61 00 01 02 00 02,1
388
389 * 01:device adaress
390
391 * 10:function code
392
393 * 00 61:Register address
394
395 * 00 01:Number of Registers
396
397 * 02:Number of bytes
398
399 * 00 02:Modified device address
400
401 * 1:Check code
402
403 The device address setting of the energy meter is complete.
404
405 Another energy meter is a single active energy meter with a floating-point format.
406
407 Its default device address is 01, and the following are the parameters for configuring two energy meters.
408
409 [[image:https://wiki.dragino.com/images/1/13/Meter11.png||alt="Meter11.png" height="576" width="379"]]
410
411 [[image:https://wiki.dragino.com/images/thumb/7/7e/Meter12.png/600px-Meter12.png||alt="Meter12.png" height="262" width="600"]]
412
413 PAYLOAD:01 08 DF 43 62
414
415 * 08 DF is the valid value of the meter with device address 02.
416 * 43 62 is the valid value of the meter with device address 01.
417
418 == 1.4 Example 4: Circuit Breaker Remote Open Close ==
419
420 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to SCHNEIDER SMART and Monitor and control your cabinet remotely with no wires and with Dragino RS485-LN LoRaWAN technology. The structure is like below:
421
422 [[image:https://wiki.dragino.com/images/thumb/f/fa/RS485_04_2.png/600px-RS485_04_2.png||height="336" width="600"]]
423
424 Connection
425
426 * [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/]] : Configure Documen
427
428 == 1.5 Example 5: SEM Three Energy Meter with RS485-BL or RS485-LN ==
429
430 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-BL to connect to SEM Three Energy Meter and send the data to mobile phone for remote minitor. The structure is like below:
431
432 * [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf]] : Configure Document For RS485-BL
433
434 * [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf]] : Configure Document for RS485-LN
435
436 == 1.6 Example 6:CEM C31 485-T1-MID Energy Meter with RS485-LN ==
437
438 This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to CEM C31 485-T1-MID and send the data for remote minitor. The structure is like below:
439
440 * [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf]] : Configure Document For RS485-LN
441
442 == 1.7 Example 7:Schneider Electric PLC M221 with RS485-BL ==
443
444 [[image:https://wiki.dragino.com/images/thumb/9/97/PLC_M221.png/600px-PLC_M221.png||height="353" width="600"]]
445
446 Network Structure