562 562  It shows how to use RS485-LN to connect to an ultrasonic flow meter and read the data from the ultrasonic flow meter.
563 563  
564 564  
565 +Need to prepare RS485-LN, recharger, Electric wire
565 565  
566 -* **Specific steps**:  RS485-LN with ultrasonic flow meter
567 -*
567 +[[image:1720669739434-926.png]] [[image:1720669744315-613.png]]
568 +
569 +
570 +=== 1.9.1 Setting Ultrasonic Flowmeter ===
571 +
572 +
573 +Adjust the M option corresponding to the ultrasonic flowmeter as follows
574 +
575 +M52 sets RS485 Port.
576 +
577 +[[image:1720669933691-331.png]]
578 +
579 +
580 +M62 sets 9600, none, 1
581 +
582 +[[image:1720669981767-254.png]]
583 +
584 +
585 +M63 sets automatic
586 +
587 +[[image:1720670003601-544.png]]
588 +
589 +
590 +=== 1.9.2 Setting Dragino RS485-LN ===
591 +
592 +
593 +The RS485-LN wiring port is as shown below. Connect the power supply and RS485 A/B line according to the diagram.
594 +
595 +[[image:1720670016539-422.png]][[image:1720670019136-658.png]]
596 +
597 +
598 +=== 1.9.3 Connect the RS485-LN to Ultrasonic Flowmeter ===
599 +
600 +
601 +According to the instructions of the ultrasonic flow meter, 26 and 27 are the + and - of RS485, corresponding to the A and B ports of RS485.
602 +
603 +[[image:1720670035661-234.png]][[image:1720670041974-372.png||height="417" width="436"]]
604 +
605 +
606 +=== 1.9.4 Full wiring example ===
607 +
608 +
609 +The yellow wire connects port 26 and port A of RS485-LN.
610 +
611 +The green wire connects port 27 and port B of RS485-LN.
612 +
613 +[[image:1720670079781-764.png]]
614 +
615 +
616 +=== 1.9.5 How to read ultrasonic flow meter data via RS485 ===
617 +
618 +
619 +[[image:1720670090204-634.png]]
620 +
621 +
622 +For example, I want to read Positive
623 +
624 +Through M02, we can see that the POS data is 54.9862
625 +
626 +[[image:1720670103571-173.png]][[image:1720670108127-723.png||height="597" width="645"]]
627 +
628 +Registers are 9-12, so the read command is AT+CFGDEV=01 03 00 08 00 04,1(,1 is used for automatic complement)
629 +
630 +[[image:1720670123955-149.png]]
631 +
632 +AT+CFGDEV=01 03 00 08 00 04 c5 cb ,1
633 +
634 +RETURN DATA:
635 +
636 +01 03 08 00 36 00 00 78 79 3f 7c 1a bc
637 +
638 +
639 +OK
640 +
641 +
642 +00 36 00 00 is the integer of the read value
643 +
644 +78 79 3f 7c is a decimal, but it needs to be converted and parsed into floating point. The parsing order is CDAB, which is 3f 7c 78 79
645 +
646 +Conversion and parsing website:http:~/~/www.speedfly.cn/tools/hexconvert/
647 +
648 +[[image:1720670134750-980.png]]
649 +
650 +
1720670123955-149.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +22.1 KB
Content
1720670134750-980.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +116.5 KB
Content
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0