... ... @@ -562,6 +562,70 @@
562 562  It shows how to use RS485-LN to connect to an ultrasonic flow meter and read the data from the ultrasonic flow meter.
563 563  
564 564  
565 +Need to prepare RS485-LN, recharger, Electric wire
565 565  
566 -* **Specific steps**:  RS485-LN with ultrasonic flow meter
567 -*
567 +[[image:1720669739434-926.png]] [[image:1720669744315-613.png]]
568 +
569 +
570 +=== 1.9.1 Setting Ultrasonic Flowmeter ===
571 +
572 +
573 +Adjust the M option corresponding to the ultrasonic flowmeter as follows
574 +
575 +M52 sets RS485 Port  M62 sets 9600, none, 1  M63 sets automatic
576 +
577 +[[image:1720669933691-331.png]][[image:1720669981767-254.png]][[image:1720670003601-544.png]]
578 +
579 +
580 +=== 1.9.2 Setting Dragino RS485-LN ===
581 +
582 +
583 +The RS485-LN wiring port is as shown below. Connect the power supply and RS485 A/B line according to the diagram.
584 +
585 +[[image:1720670016539-422.png]][[image:1720670019136-658.png]]
586 +
587 +
588 +=== 1.9.3 Connect the RS485-LN to Ultrasonic Flowmeter ===
589 +
590 +
591 +According to the instructions of the ultrasonic flow meter, 26 and 27 are the + and - of RS485, corresponding to the A and B ports of RS485.
592 +
593 +[[image:1720670035661-234.png]][[image:1720670041974-372.png||height="417" width="436"]]
594 +
595 +
596 +=== 1.9.4 Full wiring example ===
597 +
598 +
599 +The yellow wire connects port 26 and port A of RS485-LN.
600 +
601 +The green wire connects port 27 and port B of RS485-LN.
602 +
603 +[[image:1720670079781-764.png]]
604 +
605 +
606 +=== 1.9.5 How to read ultrasonic flow meter data via RS485 ===
607 +
608 +
609 +[[image:1720670090204-634.png]]
610 +
611 +
612 +For example, I want to read Positive
613 +
614 +Through M02, we can see that the POS data is 54.9862
615 +
616 +[[image:1720670103571-173.png]][[image:1720670108127-723.png||height="597" width="645"]]
617 +
618 +Registers are 9-12, so the read command is AT+CFGDEV=01 03 00 08 00 04,1(,1 is used for automatic complement)
619 +
620 +[[image:1720670123955-149.png]]
621 +
622 +
623 +00 36 00 00 is the integer of the read value
624 +
625 +78 79 3f 7c is a decimal, but it needs to be converted and parsed into floating point. The parsing order is CDAB, which is 3f 7c 78 79
626 +
627 +Conversion and parsing website:http:~/~/www.speedfly.cn/tools/hexconvert/
628 +
629 +[[image:1720670134750-980.png]]
630 +
631 +
1720670079781-764.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +614.7 KB
Content
1720670090204-634.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +30.6 KB
Content
1720670103571-173.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +492.1 KB
Content
1720670108127-723.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +111.5 KB
Content
1720670123955-149.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +22.1 KB
Content
1720670134750-980.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.karry
Size
... ... @@ -1,0 +1,1 @@
1 +116.5 KB
Content
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0