13 13  This article provide the examples for RS485-LN to connect to different type of RS485 sensors.
14 14  
15 15  
16 -
17 17  == **1.1 Example 1: Connect to Leak relay and VFD** ==
18 18  
19 19  
20 20  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to Relay and VFD and communicate with Mobile. The structure is like below:
21 21  
22 -
23 23  [[image:image-20220527091852-1.png]]
24 24  
25 25  Connection
... ... @@ -75,8 +75,6 @@
75 75  
76 76  (((
77 77  This example describes a single-phase meter.This is the connection between the RS485-LN and the energy meter.
78 -
79 -
80 80  )))
81 81  
82 82  [[image:image-20220527092419-5.png]]
... ... @@ -179,8 +179,6 @@
179 179  
180 180  (((
181 181  If the configured parameters and commands are incorrect, the return value is not obtained.
182 -
183 -
184 184  )))
185 185  
186 186  [[image:image-20220601143201-9.png]]
... ... @@ -231,7 +231,6 @@
231 231  (((
232 232  (% style="color:blue" %)**Example**:
233 233  
234 -
235 235  (% style="color:red" %)**CMD1:**(%%) Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
236 236  )))
237 237  
... ... @@ -273,8 +273,6 @@
273 273  
274 274  (((
275 275  Payload: 01 00 02 39 85 08 DC 00 00 00 44
276 -
277 -
278 278  )))
279 279  
280 280  [[image:image-20220601142936-6.png]]
... ... @@ -283,7 +283,7 @@
283 283  
284 284  
285 285  
286 -(% style="color:blue" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
277 +(% style="color:#4f81bd" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
287 287  
288 288  
289 289  [[image:image-20220601143642-2.png]]
... ... @@ -306,7 +306,7 @@
306 306  )))
307 307  
308 308  (((
309 -(% style="color:blue" %)**Type Code 0xAF**
300 +(% style="color:#4f81bd" %)**Type Code 0xAF**
310 310  )))
311 311  
312 312  (((
... ... @@ -469,7 +469,6 @@
469 469  
470 470  (% style="color:blue" %)**Example**(%%): These two meters are examples of setting parameters and device addresses.
471 471  
472 -
473 473  [[image:image-20220527093950-25.png]]
474 474  
475 475  
... ... @@ -533,9 +533,6 @@
533 533  * 08 DF is the valid value of the meter with device address 02.
534 534  * 43 62 is the valid value of the meter with device address 01.
535 535  
536 -
537 -
538 -
539 539  == 1.4 Example 4: Circuit Breaker Remote Open Close ==
540 540  
541 541  
... ... @@ -552,7 +552,6 @@
552 552  
553 553  
554 554  
555 -
556 556  == 1.5 Example 5: SEM Three Energy Meter with RS485-BL or RS485-LN ==
557 557  
558 558  
... ... @@ -563,7 +563,6 @@
563 563  
564 564  
565 565  
566 -
567 567  == 1.6 Example 6: CEM C31 485-T1-MID Energy Meter with RS485-LN ==
568 568  
569 569  
... ... @@ -573,7 +573,6 @@
573 573  
574 574  
575 575  
576 -
577 577  == 1.7 Example 7: Schneider Electric PLC M221 with RS485-BL ==
578 578  
579 579  