<
From version < 60.6 >
edited by Xiaoling
on 2022/09/19 16:07
To version < 57.21 >
edited by Xiaoling
on 2022/07/14 10:12
>
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -13,13 +13,11 @@
13 13  This article provide the examples for RS485-LN to connect to different type of RS485 sensors.
14 14  
15 15  
16 -
17 17  == **1.1 Example 1: Connect to Leak relay and VFD** ==
18 18  
19 19  
20 20  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to Relay and VFD and communicate with Mobile. The structure is like below:
21 21  
22 -
23 23  [[image:image-20220527091852-1.png]]
24 24  
25 25  Connection
... ... @@ -33,8 +33,8 @@
33 33  
34 34  (% style="color:blue" %)**Related documents:**
35 35  
36 -* System Structure:  [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
37 -* Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code:  [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
34 +* System Structure:  [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||style="background-color: rgb(255, 255, 255);"]]
35 +* Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code:  [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||style="background-color: rgb(255, 255, 255);"]]
38 38  * [[Video Demo>>url:https://www.youtube.com/watch?v=TAFZ5eaf-MY&t=6s&ab_channel=XavierFlorensaBerenguer]]
39 39  
40 40  
... ... @@ -58,11 +58,10 @@
58 58  
59 59  (% style="color:blue" %)**Related documents:**
60 60  
61 -* Configure Document:  [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/||_mstmutation="1"]]
59 +* Configure Document:  [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/]]
62 62  * [[Dragino Solution in Farm>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/&file=Dragino%20on%20Farms.pptx]]
63 63  
64 64  
65 -
66 66  == **1.3 Example3: Use RS485-LN with energy meters** ==
67 67  
68 68  
... ... @@ -70,13 +70,11 @@
70 70  
71 71  
72 72  (((
73 -(% style="color:red" %)**Note**:**The specifications of each energy meter are different, please refer to your own energy meter specifications.**
70 +(% style="color:red" %)**Note**:The specifications of each energy meter are different, please refer to your own energy meter specifications.
74 74  )))
75 75  
76 76  (((
77 77  This example describes a single-phase meter.This is the connection between the RS485-LN and the energy meter.
78 -
79 -
80 80  )))
81 81  
82 82  [[image:image-20220527092419-5.png]]
... ... @@ -109,8 +109,6 @@
109 109  
110 110  (((
111 111  Once there is power, the RS485-LN will be on.
112 -
113 -
114 114  )))
115 115  
116 116  [[image:image-20220527092514-6.png]]
... ... @@ -118,7 +118,6 @@
118 118  Connection2
119 119  
120 120  
121 -
122 122  [[image:image-20220527092555-7.png]]
123 123  
124 124  Connection3
... ... @@ -179,8 +179,6 @@
179 179  
180 180  (((
181 181  If the configured parameters and commands are incorrect, the return value is not obtained.
182 -
183 -
184 184  )))
185 185  
186 186  [[image:image-20220601143201-9.png]]
... ... @@ -190,7 +190,7 @@
190 190  
191 191  (% class="box infomessage" %)
192 192  (((
193 - (% _mstmutation="1" %)**AT+DATACUTx **(%%):  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
183 + **AT+DATACUTx **:  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
194 194  )))
195 195  
196 196  a:  length for the return of AT+COMMAND
... ... @@ -224,14 +224,11 @@
224 224  
225 225  (((
226 226  
227 -
228 -
229 229  )))
230 230  
231 231  (((
232 232  (% style="color:blue" %)**Example**:
233 233  
234 -
235 235  (% style="color:red" %)**CMD1:**(%%) Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
236 236  )))
237 237  
... ... @@ -273,8 +273,6 @@
273 273  
274 274  (((
275 275  Payload: 01 00 02 39 85 08 DC 00 00 00 44
276 -
277 -
278 278  )))
279 279  
280 280  [[image:image-20220601142936-6.png]]
... ... @@ -282,10 +282,9 @@
282 282  AT COMMAND
283 283  
284 284  
270 +(% style="color:#4f81bd" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
285 285  
286 -(% style="color:blue" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
287 287  
288 -
289 289  [[image:image-20220601143642-2.png]]
290 290  
291 291  AT COMMAND
... ... @@ -317,9 +317,7 @@
317 317  )))
318 318  
319 319  (((
320 -(% style="color:red" %)**Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.**
321 -
322 -
304 +(% style="color:red" %)Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
323 323  )))
324 324  
325 325  (((
... ... @@ -396,7 +396,6 @@
396 396  
397 397  === **1.3.4 How to configure and output commands for RS485 to USB** ===
398 398  
399 -
400 400  (((
401 401  This step is not necessary, it is just to show how to use a normal RS485 to USB adapter to connect to the meter to check the input and output. This can be used to test the connection and RS485 command of the meter without RS485-LN.
402 402  )))
... ... @@ -483,7 +483,7 @@
483 483  
484 484  (((
485 485  (((
486 -We can use (% style="color:blue" %)**AT+CFGDEV**(%%) to set the device address.
467 +We can use **AT+CFGDEV** to set the device address.
487 487  )))
488 488  )))
489 489  
... ... @@ -532,6 +532,9 @@
532 532  * 08 DF is the valid value of the meter with device address 02.
533 533  * 43 62 is the valid value of the meter with device address 01.
534 534  
516 +
517 +
518 +
535 535  == 1.4 Example 4: Circuit Breaker Remote Open Close ==
536 536  
537 537  
... ... @@ -544,15 +544,18 @@
544 544  Connection
545 545  
546 546  
547 -* Configure Documen:  [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/||_mstmutation="1"]]
531 +* Configure Documen:  [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/]]
548 548  
533 +
534 +
535 +
549 549  == 1.5 Example 5: SEM Three Energy Meter with RS485-BL or RS485-LN ==
550 550  
551 551  
552 552  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-BL to connect to SEM Three Energy Meter and send the data to mobile phone for remote minitor. The structure is like below:
553 553  
554 -* Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
555 -* Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf||_mstmutation="1"]]
541 +* Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||style="background-color: rgb(255, 255, 255);"]]
542 +* Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf]]
556 556  
557 557  == 1.6 Example 6: CEM C31 485-T1-MID Energy Meter with RS485-LN ==
558 558  
... ... @@ -559,7 +559,7 @@
559 559  
560 560  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to CEM C31 485-T1-MID and send the data for remote minitor. The structure is like below:
561 561  
562 -* Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
549 +* Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||style="background-color: rgb(255, 255, 255);"]]
563 563  
564 564  == 1.7 Example 7: Schneider Electric PLC M221 with RS485-BL ==
565 565  
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0