... ... @@ -31,8 +31,8 @@
31 31  
32 32  (% style="color:blue" %)**Related documents:**
33 33  
34 -* System Structure:  [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
35 -* Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code:  [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
34 +* System Structure:  [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||style="background-color: rgb(255, 255, 255);"]]
35 +* Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code:  [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||style="background-color: rgb(255, 255, 255);"]]
36 36  * [[Video Demo>>url:https://www.youtube.com/watch?v=TAFZ5eaf-MY&t=6s&ab_channel=XavierFlorensaBerenguer]]
37 37  
38 38  
... ... @@ -56,11 +56,12 @@
56 56  
57 57  (% style="color:blue" %)**Related documents:**
58 58  
59 -* Configure Document:  [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/||_mstmutation="1"]]
59 +* Configure Document:  [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/]]
60 60  * [[Dragino Solution in Farm>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/&file=Dragino%20on%20Farms.pptx]]
61 61  
62 62  
63 63  
64 +
64 64  == **1.3 Example3: Use RS485-LN with energy meters** ==
65 65  
66 66  
... ... @@ -68,7 +68,7 @@
68 68  
69 69  
70 70  (((
71 -(% style="color:red" %)**Note**:**The specifications of each energy meter are different, please refer to your own energy meter specifications.**
72 +(% style="color:red" %)**Note**:The specifications of each energy meter are different, please refer to your own energy meter specifications.
72 72  )))
73 73  
74 74  (((
... ... @@ -105,8 +105,6 @@
105 105  
106 106  (((
107 107  Once there is power, the RS485-LN will be on.
108 -
109 -
110 110  )))
111 111  
112 112  [[image:image-20220527092514-6.png]]
... ... @@ -120,7 +120,6 @@
120 120  Connection3
121 121  
122 122  
123 -
124 124  === **1.3.2 How to use the parameters of the energy meter and MODBUS commands** ===
125 125  
126 126  
... ... @@ -167,7 +167,6 @@
167 167  RS485-LN provides two configuration methods: AT COMMAND and DOWNLINK.
168 168  
169 169  
170 -
171 171  ==== **1.3.3.1 via AT COMMAND** ====
172 172  
173 173  
... ... @@ -184,7 +184,7 @@
184 184  
185 185  (% class="box infomessage" %)
186 186  (((
187 - (% _mstmutation="1" %)**AT+DATACUTx **(%%):  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
184 + **AT+DATACUTx **:  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
188 188  )))
189 189  
190 190  a:  length for the return of AT+COMMAND
... ... @@ -218,14 +218,12 @@
218 218  
219 219  (((
220 220  
221 -
222 -
223 223  )))
224 224  
225 225  (((
226 226  (% style="color:blue" %)**Example**:
227 227  
228 -(% style="color:red" %)**CMD1:**(%%) Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
223 +CMD1: Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
229 229  )))
230 230  
231 231  (((
... ... @@ -239,7 +239,7 @@
239 239  )))
240 240  
241 241  (((
242 -(% style="color:red" %)**CMD2: **(%%)Read voltage data with MODBUS command. address: 0x00 AT+COMMAND2= 01 03 00 00 00 01,1
237 +CMD2: Read voltage data with MODBUS command. address: 0x00 AT+COMMAND2= 01 03 00 00 00 01,1
243 243  )))
244 244  
245 245  (((
... ... @@ -253,7 +253,7 @@
253 253  )))
254 254  
255 255  (((
256 -(% style="color:red" %)**CMD3:**(%%) Read total active energy data with MODBUS command. address: 0x0031 AT+COMMAND3= 01 03 00 31 00 02,1
251 +CMD3: Read total active energy data with MODBUS command. address: 0x0031 AT+COMMAND3= 01 03 00 31 00 02,1
257 257  )))
258 258  
259 259  (((
... ... @@ -273,7 +273,6 @@
273 273  AT COMMAND
274 274  
275 275  
276 -
277 277  (% style="color:#4f81bd" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
278 278  
279 279  
... ... @@ -282,7 +282,6 @@
282 282  AT COMMAND
283 283  
284 284  
285 -
286 286  ==== **1.3.3.2 via LoRaWAN DOWNLINK** ====
287 287  
288 288  
... ... @@ -308,9 +308,7 @@
308 308  )))
309 309  
310 310  (((
311 -(% style="color:red" %)**Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.**
312 -
313 -
304 +(% style="color:red" %)Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
314 314  )))
315 315  
316 316  (((
... ... @@ -384,10 +384,8 @@
384 384  DOWNLINK
385 385  
386 386  
387 -
388 388  === **1.3.4 How to configure and output commands for RS485 to USB** ===
389 389  
390 -
391 391  (((
392 392  This step is not necessary, it is just to show how to use a normal RS485 to USB adapter to connect to the meter to check the input and output. This can be used to test the connection and RS485 command of the meter without RS485-LN.
393 393  )))
... ... @@ -443,7 +443,6 @@
443 443  USB
444 444  
445 445  
446 -
447 447  === **1.3.5 How to configure multiple devices and modify device addresses** ===
448 448  
449 449  
... ... @@ -474,7 +474,7 @@
474 474  
475 475  (((
476 476  (((
477 -We can use (% style="color:blue" %)**AT+CFGDEV**(%%) to set the device address.
465 +We can use **AT+CFGDEV** to set the device address.
478 478  )))
479 479  )))
480 480  
... ... @@ -518,11 +518,13 @@
518 518  [[image:image-20220601142607-4.png]]
519 519  
520 520  
521 -(% style="color:blue" %)**PAYLOAD: 01 08 DF 43 62**
509 +**PAYLOAD:01 08 DF 43 62**
522 522  
523 523  * 08 DF is the valid value of the meter with device address 02.
524 524  * 43 62 is the valid value of the meter with device address 01.
525 525  
514 +
515 +
526 526  == 1.4 Example 4: Circuit Breaker Remote Open Close ==
527 527  
528 528  
... ... @@ -535,7 +535,7 @@
535 535  Connection
536 536  
537 537  
538 -* Configure Documen:  [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/||_mstmutation="1"]]
528 +* Configure Documen:  [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/]]
539 539  
540 540  
541 541  
... ... @@ -544,8 +544,8 @@
544 544  
545 545  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-BL to connect to SEM Three Energy Meter and send the data to mobile phone for remote minitor. The structure is like below:
546 546  
547 -* Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
548 -* Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf||_mstmutation="1"]]
537 +* Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||style="background-color: rgb(255, 255, 255);"]]
538 +* Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf]]
549 549  
550 550  
551 551  
... ... @@ -554,7 +554,7 @@
554 554  
555 555  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to CEM C31 485-T1-MID and send the data for remote minitor. The structure is like below:
556 556  
557 -* Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
547 +* Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||style="background-color: rgb(255, 255, 255);"]]
558 558  
559 559  
560 560  