<
From version < 60.2 >
edited by Xiaoling
on 2022/07/22 17:43
To version < 57.19 >
edited by Xiaoling
on 2022/07/14 10:09
>
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -31,13 +31,10 @@
31 31  
32 32  (% style="color:blue" %)**Related documents:**
33 33  
34 -* System Structure:  [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
35 -* Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code:  [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
34 +* System Structure:  [[Solar Pump with Dragino>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||style="background-color: rgb(255, 255, 255);"]]
35 +* Explanation on how to integrate to Node-red and to the Mobile Phone, and with link to the Github code:  [[Configure Manual>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Relay_VFD/||style="background-color: rgb(255, 255, 255);"]]
36 36  * [[Video Demo>>url:https://www.youtube.com/watch?v=TAFZ5eaf-MY&t=6s&ab_channel=XavierFlorensaBerenguer]]
37 37  
38 -
39 -
40 -
41 41  == **1.2 Example 2: Connect to Pulse Counter** ==
42 42  
43 43  
... ... @@ -57,12 +57,11 @@
57 57  
58 58  (% style="color:blue" %)**Related documents:**
59 59  
60 -* Configure Document:  [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/||_mstmutation="1"]]
57 +* Configure Document:  [[Pickdata MIO40 water pulse counter to LoRa with Dragino RS485-LN>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Pulse-Counter/]]
61 61  * [[Dragino Solution in Farm>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/&file=Dragino%20on%20Farms.pptx]]
62 62  
63 63  
64 64  
65 -
66 66  == **1.3 Example3: Use RS485-LN with energy meters** ==
67 67  
68 68  
... ... @@ -107,8 +107,6 @@
107 107  
108 108  (((
109 109  Once there is power, the RS485-LN will be on.
110 -
111 -
112 112  )))
113 113  
114 114  [[image:image-20220527092514-6.png]]
... ... @@ -116,13 +116,11 @@
116 116  Connection2
117 117  
118 118  
119 -
120 120  [[image:image-20220527092555-7.png]]
121 121  
122 122  Connection3
123 123  
124 124  
125 -
126 126  === **1.3.2 How to use the parameters of the energy meter and MODBUS commands** ===
127 127  
128 128  
... ... @@ -169,7 +169,6 @@
169 169  RS485-LN provides two configuration methods: AT COMMAND and DOWNLINK.
170 170  
171 171  
172 -
173 173  ==== **1.3.3.1 via AT COMMAND** ====
174 174  
175 175  
... ... @@ -186,7 +186,7 @@
186 186  
187 187  (% class="box infomessage" %)
188 188  (((
189 - (% _mstmutation="1" %)**AT+DATACUTx **(%%):  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
180 + **AT+DATACUTx **:  This command defines how to handle the return from AT+COMMANDx, max reture length is 40 bytes. AT+DATACUTx=a,b,c
190 190  )))
191 191  
192 192  a:  length for the return of AT+COMMAND
... ... @@ -220,8 +220,6 @@
220 220  
221 221  (((
222 222  
223 -
224 -
225 225  )))
226 226  
227 227  (((
... ... @@ -275,7 +275,6 @@
275 275  AT COMMAND
276 276  
277 277  
278 -
279 279  (% style="color:#4f81bd" %)**01 is device address,00 02 is the current, 08 DC is the voltage,00 00 00 44 is the total active energy.**
280 280  
281 281  
... ... @@ -284,7 +284,6 @@
284 284  AT COMMAND
285 285  
286 286  
287 -
288 288  ==== **1.3.3.2 via LoRaWAN DOWNLINK** ====
289 289  
290 290  
... ... @@ -310,9 +310,7 @@
310 310  )))
311 311  
312 312  (((
313 -(% style="color:red" %)**Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.**
314 -
315 -
300 +(% style="color:red" %)Note: if user use AT+COMMANDx to add a new command, he also need to send AT+DATACUTx downlink.
316 316  )))
317 317  
318 318  (((
... ... @@ -386,10 +386,8 @@
386 386  DOWNLINK
387 387  
388 388  
389 -
390 390  === **1.3.4 How to configure and output commands for RS485 to USB** ===
391 391  
392 -
393 393  (((
394 394  This step is not necessary, it is just to show how to use a normal RS485 to USB adapter to connect to the meter to check the input and output. This can be used to test the connection and RS485 command of the meter without RS485-LN.
395 395  )))
... ... @@ -445,7 +445,6 @@
445 445  USB
446 446  
447 447  
448 -
449 449  === **1.3.5 How to configure multiple devices and modify device addresses** ===
450 450  
451 451  
... ... @@ -476,7 +476,7 @@
476 476  
477 477  (((
478 478  (((
479 -We can use (% style="color:blue" %)**AT+CFGDEV**(%%) to set the device address.
461 +We can use **AT+CFGDEV** to set the device address.
480 480  )))
481 481  )))
482 482  
... ... @@ -520,7 +520,7 @@
520 520  [[image:image-20220601142607-4.png]]
521 521  
522 522  
523 -(% style="color:blue" %)**PAYLOAD: 01 08 DF 43 62**
505 +**PAYLOAD:01 08 DF 43 62**
524 524  
525 525  * 08 DF is the valid value of the meter with device address 02.
526 526  * 43 62 is the valid value of the meter with device address 01.
... ... @@ -537,7 +537,7 @@
537 537  Connection
538 538  
539 539  
540 -* Configure Documen:  [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/||_mstmutation="1"]]
522 +* Configure Documen:  [[Circuit Breaker Remote Open Close>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/Circuit_Breaker_Remote_Open_Close/]]
541 541  
542 542  == 1.5 Example 5: SEM Three Energy Meter with RS485-BL or RS485-LN ==
543 543  
... ... @@ -544,8 +544,8 @@
544 544  
545 545  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-BL to connect to SEM Three Energy Meter and send the data to mobile phone for remote minitor. The structure is like below:
546 546  
547 -* Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
548 -* Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf||_mstmutation="1"]]
529 +* Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||style="background-color: rgb(255, 255, 255);"]]
530 +* Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf]]
549 549  
550 550  == 1.6 Example 6: CEM C31 485-T1-MID Energy Meter with RS485-LN ==
551 551  
... ... @@ -552,7 +552,7 @@
552 552  
553 553  This instruction is provided by Xavier Florensa Berenguer from [[NORIA GRUPO DE COMPRAS>>url:http://www.gruponovelec.com/]]. It is to show how to use RS485-LN to connect to CEM C31 485-T1-MID and send the data for remote minitor. The structure is like below:
554 554  
555 -* Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||_mstmutation="1" style="background-color: rgb(255, 255, 255);"]]
537 +* Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||style="background-color: rgb(255, 255, 255);"]]
556 556  
557 557  == 1.7 Example 7: Schneider Electric PLC M221 with RS485-BL ==
558 558  
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0