... ... @@ -60,10 +60,9 @@
60 60  * [[Dragino Solution in Farm>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/&file=Dragino%20on%20Farms.pptx]]
61 61  
62 62  
63 -
64 -
65 65  == **1.3 Example3: Use RS485-LN with energy meters** ==
66 66  
65 +
67 67  === **1.3.1 OverView** ===
68 68  
69 69  
... ... @@ -82,7 +82,7 @@
82 82  
83 83  
84 84  (((
85 -**How to connect with Energy Meter:**
84 +(% style="color:blue" %)**How to connect with Energy Meter:**
86 86  
87 87  
88 88  )))
... ... @@ -112,12 +112,12 @@
112 112  Connection2
113 113  
114 114  
115 -
116 116  [[image:image-20220527092555-7.png]]
117 117  
118 118  Connection3
119 119  
120 120  
119 +
121 121  === **1.3.2 How to use the parameters of the energy meter and MODBUS commands** ===
122 122  
123 123  
... ... @@ -164,6 +164,7 @@
164 164  RS485-LN provides two configuration methods: AT COMMAND and DOWNLINK.
165 165  
166 166  
166 +
167 167  ==== **1.3.3.1 via AT COMMAND** ====
168 168  
169 169  
... ... @@ -219,7 +219,7 @@
219 219  (((
220 220  (% style="color:blue" %)**Example**:
221 221  
222 -CMD1: Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
222 +(% style="color:red" %)**CMD1:**(%%) Read current data with MODBUS command. address: 0x03 AT+COMMAND1= 01 03 00 03 00 01,1
223 223  )))
224 224  
225 225  (((
... ... @@ -233,7 +233,7 @@
233 233  )))
234 234  
235 235  (((
236 -CMD2: Read voltage data with MODBUS command. address: 0x00 AT+COMMAND2= 01 03 00 00 00 01,1
236 +(% style="color:red" %)**CMD2: **(%%)Read voltage data with MODBUS command. address: 0x00 AT+COMMAND2= 01 03 00 00 00 01,1
237 237  )))
238 238  
239 239  (((
... ... @@ -247,7 +247,7 @@
247 247  )))
248 248  
249 249  (((
250 -CMD3: Read total active energy data with MODBUS command. address: 0x0031 AT+COMMAND3= 01 03 00 31 00 02,1
250 +(% style="color:red" %)**CMD3:**(%%) Read total active energy data with MODBUS command. address: 0x0031 AT+COMMAND3= 01 03 00 31 00 02,1
251 251  )))
252 252  
253 253  (((
... ... @@ -275,6 +275,7 @@
275 275  AT COMMAND
276 276  
277 277  
278 +
278 278  ==== **1.3.3.2 via LoRaWAN DOWNLINK** ====
279 279  
280 280  
... ... @@ -374,6 +374,7 @@
374 374  DOWNLINK
375 375  
376 376  
378 +
377 377  === **1.3.4 How to configure and output commands for RS485 to USB** ===
378 378  
379 379  (((
... ... @@ -431,6 +431,7 @@
431 431  USB
432 432  
433 433  
436 +
434 434  === **1.3.5 How to configure multiple devices and modify device addresses** ===
435 435  
436 436  
... ... @@ -505,7 +505,7 @@
505 505  [[image:image-20220601142607-4.png]]
506 506  
507 507  
508 -**PAYLOAD:01 08 DF 43 62**
511 +(% style="color:blue" %)**PAYLOAD: 01 08 DF 43 62**
509 509  
510 510  * 08 DF is the valid value of the meter with device address 02.
511 511  * 43 62 is the valid value of the meter with device address 01.
... ... @@ -512,6 +512,7 @@
512 512  
513 513  
514 514  
518 +
515 515  == 1.4 Example 4: Circuit Breaker Remote Open Close ==
516 516  
517 517  
... ... @@ -528,6 +528,7 @@
528 528  
529 529  
530 530  
535 +
531 531  == 1.5 Example 5: SEM Three Energy Meter with RS485-BL or RS485-LN ==
532 532  
533 533  
... ... @@ -536,8 +536,6 @@
536 536  * Configure Document For RS485-BL:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=LoRa_End_Node/RS485-BL/Application_Note/&file=Dragino%20RS485BL%20and%20pickdata%20SEM%20Three%20v1.pdf||style="background-color: rgb(255, 255, 255);"]]
537 537  * Configure Document for RS485-LN:  [[Connect to SEM Three>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/SEM_Three_Energy_Meter/&file=SEM%20three%20and%20Dragino%20RS485-LN%20v1.pdf]]
538 538  
539 -
540 -
541 541  == 1.6 Example 6: CEM C31 485-T1-MID Energy Meter with RS485-LN ==
542 542  
543 543  
... ... @@ -545,8 +545,6 @@
545 545  
546 546  * Configure Document For RS485-LN:  [[CEM C31 485-T1-MID>>url:http://www.dragino.com/downloads/index.php?dir=RS485-LN/Application_Note/ELECTRICAL%20CABINET/&file=ELECTRICAL%20CABINET%20READINGS.pdf||style="background-color: rgb(255, 255, 255);"]]
547 547  
548 -
549 -
550 550  == 1.7 Example 7: Schneider Electric PLC M221 with RS485-BL ==
551 551  
552 552  
Copyright ©2010-2024 Dragino Technology Co., LTD. All rights reserved
Dragino Wiki v2.0